		<id>https://firealarmpedia.org/index.php?title=CN_Walker_Operations_B&amp;diff=13359&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Simplex 4100U&lt;br /&gt;FACP Location: Main Electrical Room&lt;br /&gt;System Type: Two-Stage Addressable&lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VDC&lt;br /&gt;System Coding: 20BPM (Alert)&lt;br&gt;Temporal (Alarm)&lt;br&gt;Strobes Synchronized: Yes, SmartSync&lt;br /&gt;Date of last known Upgrade: N/A&lt;br /&gt;Most Recent Known Modification: N/A&lt;br /&gt;Year Opened: 2008 |}  &#039;&#039;&#039;Canadian National&#039;&#039;&#039; is a railw...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=CN_Walker_Operations_B&amp;diff=13359&amp;oldid=prev"/>
		<updated>2025-09-05T01:53:24Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Simplex 4100U&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Two-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: 20BPM (Alert)&amp;lt;br&amp;gt;Temporal (Alarm)&amp;lt;br&amp;gt;Strobes Synchronized: Yes, SmartSync&amp;lt;br /&amp;gt;Date of last known Upgrade: N/A&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 2008 |}  &amp;#039;&amp;#039;&amp;#039;Canadian National&amp;#039;&amp;#039;&amp;#039; is a railw...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Simplex 4100U&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Two-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: 20BPM (Alert)&amp;lt;br&amp;gt;Temporal (Alarm)&amp;lt;br&amp;gt;Strobes Synchronized: Yes, SmartSync&amp;lt;br /&amp;gt;Date of last known Upgrade: N/A&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 2008&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Canadian National&amp;#039;&amp;#039;&amp;#039; is a railway headquartered in Montreal, Quebec.  This page will cover the Walker Yard&amp;#039;s Operations Building B, located at 10229 127 Ave NW, in Edmonton, Alberta, Canada.  The building was built in 2008, and the fire alarm system is original.&lt;br /&gt;
&lt;br /&gt;
==System Specifications==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by a Simplex 4100U addressable fire alarm system.  The panel is located in the main electrical room.  The system runs Simplex&amp;#039;s IDNet addressable protocol, and is configured for two-stage operation.  The alert signal coding is 20BPM, and the alarm signal coding is temporal.  The system is programmed for audible silence.  &amp;lt;br&amp;gt;This panel is connected to the panel in Building A via a 4120 network.&lt;br /&gt;
&lt;br /&gt;
=====Annunciators=====&lt;br /&gt;
There is a Simplex 4603-9101 annunciator in the main entrance vestibule.&lt;br /&gt;
&lt;br /&gt;
=====Booster Panels=====&lt;br /&gt;
There are Simplex 4009 booster power supplies in the third floor electrical room and the generator room.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
Most notification appliances are Simplex &amp;quot;TrueAlert&amp;quot; 4906-9127 horn/strobes (red, wall-mount, set to 15cd).  &amp;lt;br&amp;gt;The control centre and all washrooms have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).  &amp;lt;br&amp;gt;For outdoor notification, there is a Wheelock MTWP-2475W-FR weatherproof horn/strobe (red, 175cd, set to continuous horn) outside the generator room.  This device will sound in a continuous pattern if an alarm is initiated in the generator room, and will not sound if a main building alarm occurs.&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations but one are Simplex 4099-9004CA addressable two-stage single-action pull stations.  &amp;lt;br&amp;gt;There is a Simplex 4099-9001 addressable single-action pull station in the generator room.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are Simplex &amp;quot;TrueAlarm&amp;quot; 4098-9714 addressable photoelectric smoke detectors in the atrium, all electrical rooms and all LAN rooms.  &amp;lt;br&amp;gt;There are Simplex 4098-9733 addressable 135°F fixed-temperature/rate-of-rise heat detectors in all electrical and LAN rooms next to the smoke detectors.  &amp;lt;br&amp;gt;All aforementioned detectors are mounted on Simplex 4098-9792 bases.  &amp;lt;br&amp;gt;There are Simplex 4098-9755 addressable photoelectric duct smoke detectors on all air handling units.  &amp;lt;br&amp;gt;There is a Simplex 4255-54 conventional 200°F fixed-temperature heat detector in the generator room, wired to a Simplex 4090-9001 addressable monitor module; the EOL is located in the device.  &amp;lt;br&amp;gt;There is a VESDA aspirating smoke detection system on the system.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system&amp;#039;s tamper and flow switches.  &amp;lt;br&amp;gt;There are Simplex 4090-9002 addressable relay modules serving various purposes.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.&lt;br /&gt;