	<entry>
		<id>https://firealarmpedia.org/index.php?title=Calgary_Dream_Centre&amp;diff=12633&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Edwards iO1000 &lt;br /&gt;FACP Location: Main Electrical/Mech Room &lt;br /&gt;System Type: Single-Stage Addressable &lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VFWR (FACP) &lt;br&gt;24VDC (Boosters) &lt;br /&gt;System Coding: Temporal &lt;br&gt;Strobes Synchronized: Yes, Genesis &lt;br /&gt;Date of last known Upgrade: 2004 &lt;br /&gt;Most Recent Known Modification: 2024, FACP &lt;br&gt;Year Opened: 1972 |}  The &#039;&#039;&#039;Ca...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Calgary_Dream_Centre&amp;diff=12633&amp;oldid=prev"/>
		<updated>2025-04-29T03:35:36Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Edwards iO1000 &amp;lt;br /&amp;gt;FACP Location: Main Electrical/Mech Room &amp;lt;br /&amp;gt;System Type: Single-Stage Addressable &amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VFWR (FACP) &amp;lt;br&amp;gt;24VDC (Boosters) &amp;lt;br /&amp;gt;System Coding: Temporal &amp;lt;br&amp;gt;Strobes Synchronized: Yes, Genesis &amp;lt;br /&amp;gt;Date of last known Upgrade: 2004 &amp;lt;br /&amp;gt;Most Recent Known Modification: 2024, FACP &amp;lt;br&amp;gt;Year Opened: 1972 |}  The &amp;#039;&amp;#039;&amp;#039;Ca...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Edwards iO1000 &amp;lt;br /&amp;gt;FACP Location: Main Electrical/Mech Room &amp;lt;br /&amp;gt;System Type: Single-Stage Addressable &amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VFWR (FACP) &amp;lt;br&amp;gt;24VDC (Boosters) &amp;lt;br /&amp;gt;System Coding: Temporal &amp;lt;br&amp;gt;Strobes Synchronized: Yes, Genesis &amp;lt;br /&amp;gt;Date of last known Upgrade: 2004 &amp;lt;br /&amp;gt;Most Recent Known Modification: 2024, FACP &amp;lt;br&amp;gt;Year Opened: 1972&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The &amp;#039;&amp;#039;&amp;#039;Calgary Dream Centre&amp;#039;&amp;#039;&amp;#039; is a rehab facility located at 4510 Macleod Trail SW, in Calgary, Alberta, Canada.  The building was built in 1972 as a hotel, though sources are inconclusive of the hotel&amp;#039;s name.  The facility was converted into the Dream Centre in 2004, and the fire alarm system was upgraded during the conversion; the FACP was replaced in 2024.&lt;br /&gt;
&lt;br /&gt;
==System Specifications (2004-present)==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by an Edwards iO1000 addressable fire alarm system.  The panel is located in the main electrical/mechanical room.  The system runs Edwards&amp;#039; Signature addressable protocol, and the system coding is temporal.  &amp;lt;br&amp;gt;This panel replaced an EST QuickStart QS1.&lt;br /&gt;
&lt;br /&gt;
=====Annunciators=====&lt;br /&gt;
There is an Edwards RLCD-C annunciator behind the main reception.&lt;br /&gt;
&lt;br /&gt;
=====Booster Panels=====&lt;br /&gt;
There are Edwards BPS6A 6-amp booster power supplies in the laundry rooms on the second, fourth and sixth floors.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
All common areas have EST &amp;quot;Genesis&amp;quot; G1R-HOV15 horn/strobes (red, wall-mount, no marking, 15cd).  &amp;lt;br&amp;gt;All suites but two have Edwards 683-1C silenceable mini-horns (white) paired with EST G1R-V15 remote strobes (red, wall-mount, no marking, 15cd).  &amp;lt;br&amp;gt;One suite has a Potter HPS-24 silenceable mini-horn (red), while another has a Mircom MH-S25WA silenceable mini-horn (white); both are deficiency replacements, original strobes remain.&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are EST SIGA-270 addressable single-action pull stations.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are EST SIGA-PS addressable photoelectric smoke detectors in all upper floor corridors, with Edwards SIGA-PD addressable photoelectric smoke detectors installed as deficiency replacements.  &amp;lt;br&amp;gt;There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in the penthouse, plus all mechanical, janitor and electrical rooms.  &amp;lt;br&amp;gt;All aforementioned detectors are mounted on EST SIGA-SB bases.  &amp;lt;br&amp;gt;There is an EST &amp;quot;SuperDuct&amp;quot; SIGA-SD addressable photoelectric duct smoke detector on the penthouse supply air duct.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are EST SIGA-WTM addressable monitor modules supervising the sprinkler system&amp;#039;s tamper and flow switches.  &amp;lt;br&amp;gt;There is an EST SIGA-CT1 addressable monitor module supervising the kitchen suppression system.  &amp;lt;br&amp;gt;There are EST SIGA-CR addressable relay modules serving various purposes.  &amp;lt;br&amp;gt;There are EST SIGA-IM addressable isolator modules on the SLC.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Edwards EOL-P1 end of line resistor plates on the kitchen suppression system circuit, and on all sprinkler and signal circuits.&lt;br /&gt;
&lt;br /&gt;
[[Category:Calgary]]&lt;br /&gt;
[[Category:Healthcare]]&lt;/div&gt;</summary>