<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=Cedars_of_Calgary_Building_F</id>
	<title>Cedars of Calgary Building F - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=Cedars_of_Calgary_Building_F"/>
	<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Cedars_of_Calgary_Building_F&amp;action=history"/>
	<updated>2026-04-28T03:04:42Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.41.0</generator>
	<entry>
		<id>https://firealarmpedia.org/index.php?title=Cedars_of_Calgary_Building_F&amp;diff=12900&amp;oldid=prev</id>
		<title>TwentyThree33: Created page with &quot; {| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Edwards FireShield Plus FSP302G&lt;br /&gt;FACP Location: F1 Electrical Room&lt;br /&gt;System Type: Single-Stage Conventional&lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VFWR&lt;br /&gt;System Coding: Temporal&lt;br&gt;Strobes Synchronized: Yes, Genesis&lt;br /&gt;Date of last known Upgrade: 2018&lt;br /&gt;Most Recent Known Modification: N/A&lt;br /&gt;Year Opened: 1977 |}  &#039;&#039;&#039;Cedars of Calgary&#039;&#039;&#039; is an apartmen...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Cedars_of_Calgary_Building_F&amp;diff=12900&amp;oldid=prev"/>
		<updated>2025-06-17T03:56:49Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot; {| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Edwards FireShield Plus FSP302G&amp;lt;br /&amp;gt;FACP Location: F1 Electrical Room&amp;lt;br /&amp;gt;System Type: Single-Stage Conventional&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VFWR&amp;lt;br /&amp;gt;System Coding: Temporal&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Genesis&amp;lt;br /&amp;gt;Date of last known Upgrade: 2018&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 1977 |}  &amp;#039;&amp;#039;&amp;#039;Cedars of Calgary&amp;#039;&amp;#039;&amp;#039; is an apartmen...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;&lt;br /&gt;
{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Edwards FireShield Plus FSP302G&amp;lt;br /&amp;gt;FACP Location: F1 Electrical Room&amp;lt;br /&amp;gt;System Type: Single-Stage Conventional&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VFWR&amp;lt;br /&amp;gt;System Coding: Temporal&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Genesis&amp;lt;br /&amp;gt;Date of last known Upgrade: 2018&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 1977&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Cedars of Calgary&amp;#039;&amp;#039;&amp;#039; is an apartment complex located at 215 86 Ave SE, in Calgary, Alberta, Canada.  The complex is owned and operated by Shelter Canadian Properties.  This page will cover Building F, which was built in 1977.  The fire alarm system was partially upgraded in 2018.&lt;br /&gt;
&lt;br /&gt;
==System Specifications (2018-present)==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by an Edwards FireShield Plus FSP302G conventional fire alarm system.  The panel is located in the F1 electrical room.  The system coding is temporal.  &amp;lt;br&amp;gt;This panel replaced an Edwards 1523.&lt;br /&gt;
&lt;br /&gt;
=====Annunciators=====&lt;br /&gt;
There is an Edwards FSRSI annunciator equipped with an FSRZI-A module outside the F1 west entrance.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
All indoor notification appliances are Edwards &amp;quot;Genesis&amp;quot; G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd) mounted on Edwards G1TR trim plates.  &amp;lt;br&amp;gt;For outdoor notification, there is an Edwards WG4RF-H weatherproof remote horn (red, FIRE marking) outside the F1 entrance.&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations but one are Edwards 270-SPO conventional single-action pull stations.  &amp;lt;br&amp;gt;There is a Notifier NFM-950B conventional single-action pull station in the F2 first floor corridor as a deficiency replacement.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are System Sensor C2W-BA conventional photoelectric smoke detectors in all corridors.  &amp;lt;br&amp;gt;There are Potter CF-135W conventional 135°F fixed-temperature heat detectors in all mechanical and electrical rooms.  &amp;lt;br&amp;gt;There are System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors at the top of each stairwell.  &amp;lt;br&amp;gt;There are Edwards 284A conventional 194°F fixed-temperature heat detectors in all laundry rooms.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
All end of line resistors are in field devices.&lt;br /&gt;
&lt;br /&gt;
[[Category:Calgary]]&lt;br /&gt;
[[Category:Residential]]&lt;/div&gt;</summary>