	<entry>
		<id>https://firealarmpedia.org/index.php?title=Deerfoot_Atria_South&amp;diff=13305&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: EST QuickStart QS4&lt;br /&gt;FACP Location: Main Electrical Room&lt;br /&gt;System Type: Single-Stage Addressable&lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VDC&lt;br /&gt;System Coding: Temporal&lt;br&gt;Strobes Synchronized: Yes, Self-Sync&lt;br /&gt;Date of last known Upgrade: 2006&lt;br /&gt;Most Recent Known Modification: N/A&lt;br /&gt;Year Opened: 1980 |}  &#039;&#039;&#039;Deerfoot Atria South&#039;&#039;&#039; is an office building l...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Deerfoot_Atria_South&amp;diff=13305&amp;oldid=prev"/>
		<updated>2025-09-04T03:08:04Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: EST QuickStart QS4&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Single-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: Temporal&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Self-Sync&amp;lt;br /&amp;gt;Date of last known Upgrade: 2006&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 1980 |}  &amp;#039;&amp;#039;&amp;#039;Deerfoot Atria South&amp;#039;&amp;#039;&amp;#039; is an office building l...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: EST QuickStart QS4&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Single-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: Temporal&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Self-Sync&amp;lt;br /&amp;gt;Date of last known Upgrade: 2006&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 1980&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Deerfoot Atria South&amp;#039;&amp;#039;&amp;#039; is an office building located at 6715 8 St NE, in Calgary, Alberta, Canada.  The building is owned and operated by Groupthree Property Management.  The building was built in 1980, and the fire alarm system was upgraded in 2006.&lt;br /&gt;
&lt;br /&gt;
==System Specifications (2006-present)==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by an EST QuickStart QS4 addressable fire alarm system.  The panel is located in the main electrical/fire control room on the P1 level.  The system runs EST&amp;#039;s Signature addressable protocol, and the system coding is temporal.  The panel&amp;#039;s onboard NACs are not utilized; all notification appliances are powered off booster panels.&lt;br /&gt;
&lt;br /&gt;
=====Annunciators=====&lt;br /&gt;
There is an EST QSA-2-S annunciator in the main entrance vestibule.&lt;br /&gt;
&lt;br /&gt;
=====Booster Panels=====&lt;br /&gt;
There are Edwards BPS6AC 6-amp booster power supplies in the main electrical room and in some other areas.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
Most notification appliances are Edwards &amp;quot;Genesis&amp;quot; G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).  &amp;lt;br&amp;gt;Some areas have Edwards GC-HDVM horn/strobes (white, ceiling-mount, no marking, set to 15cd).  &amp;lt;br&amp;gt;Some areas have Edwards G4AVRF horn/strobes (red, wall-mount, FIRE marking, set to 15cd) as deficiency replacements.&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are EST SIGA-270 addressable single-action pull stations.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are EST SIGA-PS addressable photoelectric smoke detectors in all electrical and telephone rooms, at the top of each stairwell, and in some other areas.  &amp;lt;br&amp;gt;There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical rooms and elevator pits.  &amp;lt;br&amp;gt;All detectors are mounted on EST SIGA-SB bases.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are EST SIGA-CT1 addressable monitor modules supervising the generator&amp;#039;s run and trouble contacts, and the sprinkler system&amp;#039;s tamper and flow switches.  &amp;lt;br&amp;gt;There are EST SIGA-CR addressable relay modules serving various purposes.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.&lt;br /&gt;
&lt;br /&gt;
[[Category:Calgary]]&lt;br /&gt;
[[Category:Office Buildings]]&lt;br /&gt;
[[Category:Edwards]]&lt;/div&gt;</summary>