<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=Excite_Lethbridge</id>
	<title>Excite Lethbridge - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=Excite_Lethbridge"/>
	<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Excite_Lethbridge&amp;action=history"/>
	<updated>2026-05-18T06:50:05Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.41.0</generator>
	<entry>
		<id>https://firealarmpedia.org/index.php?title=Excite_Lethbridge&amp;diff=13751&amp;oldid=prev</id>
		<title>TwentyThree33: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Siemens Cerberus Pro Modular&lt;br /&gt;FACP Location: Main Electrical Room&lt;br /&gt;System Type: Single-Stage Addressable&lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 70.7VRMS (Audible)&lt;br&gt;24VDC (Visual)&lt;br /&gt;System Coding: Temporal Tone + Message?&lt;br&gt;Strobes Synchronized: Yes, Siemens&lt;br /&gt;Date of last known Upgrade: N/A&lt;br /&gt;Most Recent Known Modification: N/A&lt;br /&gt;Year Opened: 2023...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Excite_Lethbridge&amp;diff=13751&amp;oldid=prev"/>
		<updated>2026-05-03T22:38:50Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Siemens Cerberus Pro Modular&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Single-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 70.7VRMS (Audible)&amp;lt;br&amp;gt;24VDC (Visual)&amp;lt;br /&amp;gt;System Coding: Temporal Tone + Message?&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Siemens&amp;lt;br /&amp;gt;Date of last known Upgrade: N/A&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 2023...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Siemens Cerberus Pro Modular&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Single-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 70.7VRMS (Audible)&amp;lt;br&amp;gt;24VDC (Visual)&amp;lt;br /&amp;gt;System Coding: Temporal Tone + Message?&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Siemens&amp;lt;br /&amp;gt;Date of last known Upgrade: N/A&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 2023&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Excite Lethbridge&amp;#039;&amp;#039;&amp;#039; is a convention centre located at 101 Exhibition Way S, in Lethbridge, Alberta, Canada.  The building was built in 2023, and the fire alarm system is original.&lt;br /&gt;
&lt;br /&gt;
==System Specifications==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by a Siemens Cerberus Pro Modular addressable fire alarm system.  The panel is located in the main electrical room.  The system runs Siemens&amp;#039; FirePrint addressable protocol, and is equipped with voice evacuation.  The evacuation signal is likely a temporal tone with a pre-recorded message.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
Most notification appliances are Siemens SE-MC-W-B speaker/strobes (white, wall-mount, bilingual lettering, set to 15cd).  &amp;lt;br&amp;gt;Some areas have Siemens SE-MC-CW-B speaker/strobes (white, ceiling-mount, bilingual lettering, set to 15cd).  &amp;lt;br&amp;gt;For outdoor notification, there is a Siemens ST-HMC-R-WP-B weatherproof remote strobe (red, bilingual lettering) outside the main electrical room.&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are Siemens M61-B conventional single-action pull stations, wired to Siemens XTRI-M addressable monitor modules.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are Siemens OP921 addressable photoelectric smoke detectors in some areas.  &amp;lt;br&amp;gt;There are Siemens OH921 addressable 135°F fixed-temperature/rate-of-rise heat detectors in some areas.  &amp;lt;br&amp;gt;All aforementioned detectors are mounted on Siemens DB-11 bases.  &amp;lt;br&amp;gt;There are Siemens FDBZ492-HR duct smoke detector housings equipped with Siemens OP921 addressable photoelectric heads on all air handling units.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are Siemens XTRI-D addressable monitor modules supervising the generator&amp;#039;s run/trouble contacts, the fire pump&amp;#039;s run/trouble/not in auto contacts, and the sprinkler system&amp;#039;s tamper and flow switches.  &amp;lt;br&amp;gt;There are Siemens XTRI-R addressable relay modules serving various purposes.  &amp;lt;br&amp;gt;All modules on this system have built-in isolators.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Siemens EL-300C end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.&lt;br /&gt;
&lt;br /&gt;
[[Category:Lethbridge]]&lt;br /&gt;
[[Category:Event Centres]]&lt;br /&gt;