<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=John_J_Bowlen_Building</id>
	<title>John J Bowlen Building - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=John_J_Bowlen_Building"/>
	<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=John_J_Bowlen_Building&amp;action=history"/>
	<updated>2026-04-27T22:21:52Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.41.0</generator>
	<entry>
		<id>https://firealarmpedia.org/index.php?title=John_J_Bowlen_Building&amp;diff=11958&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Notifier NFS2-640C &lt;br /&gt;FACP Location: Various &lt;br /&gt;System Type: Two-Stage Networked Addressable &lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 70.7VRMS (Audible) &lt;br&gt;24VDC (Visual) &lt;br /&gt;System Coding: 20BPM Tone + Message (Alert) &lt;br&gt;Temporal Tone + Message (Alarm) &lt;br&gt;Strobes Synchronized: Yes, System Sensor &lt;br /&gt;Date of last known Upgrade: 2011 &lt;br /&gt;Year Opened: 1967 |}...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=John_J_Bowlen_Building&amp;diff=11958&amp;oldid=prev"/>
		<updated>2025-01-07T05:55:09Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Notifier NFS2-640C &amp;lt;br /&amp;gt;FACP Location: Various &amp;lt;br /&amp;gt;System Type: Two-Stage Networked Addressable &amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 70.7VRMS (Audible) &amp;lt;br&amp;gt;24VDC (Visual) &amp;lt;br /&amp;gt;System Coding: 20BPM Tone + Message (Alert) &amp;lt;br&amp;gt;Temporal Tone + Message (Alarm) &amp;lt;br&amp;gt;Strobes Synchronized: Yes, System Sensor &amp;lt;br /&amp;gt;Date of last known Upgrade: 2011 &amp;lt;br /&amp;gt;Year Opened: 1967 |}...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Notifier NFS2-640C &amp;lt;br /&amp;gt;FACP Location: Various &amp;lt;br /&amp;gt;System Type: Two-Stage Networked Addressable &amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 70.7VRMS (Audible) &amp;lt;br&amp;gt;24VDC (Visual) &amp;lt;br /&amp;gt;System Coding: 20BPM Tone + Message (Alert) &amp;lt;br&amp;gt;Temporal Tone + Message (Alarm) &amp;lt;br&amp;gt;Strobes Synchronized: Yes, System Sensor &amp;lt;br /&amp;gt;Date of last known Upgrade: 2011 &amp;lt;br /&amp;gt;Year Opened: 1967&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
The &amp;#039;&amp;#039;&amp;#039;John J Bowlen Building&amp;#039;&amp;#039;&amp;#039; is an Alberta government building located at 620 7 Ave SW, in Calgary, Alberta, Canada.  The building is operated by Edon management.  The building was built in 1967, and the fire alarm system was upgraded in 2011.&lt;br /&gt;
&lt;br /&gt;
==System Specifications (2011-present)==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by a Notifier NOTI-FIRE-NET networked fire alarm system.  There are 4 nodes on this system; all are Notifier NFS2-640C addressable fire alarm panels.  Node 1 is located in the CACF room on the main floor and is equipped with an NCA-2C display.  Nodes 2 through 4 are located in the north storage rooms on floors 3, 6 and 9 respectively.  The system runs Notifier’s FlashScan addressable protocol, is configured for two-stage operation, and is equipped with Notifier’s “Digital Voice Command” (DVC) voice evacuation system.  The alert signal is a 20BPM tone followed by a standby message, and the alarm signal is a temporal tone followed by an evacuation message.  See below for message scripts.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
Most notification appliances are System Sensor “SpectrAlert Advance” SPSCWA speaker/strobes (white, ceiling-mount, set to 70V/15cd).  &amp;lt;br&amp;gt;Some areas have System Sensor SPCWA remote speakers (white, ceiling-mount, set to 70V).  &amp;lt;br&amp;gt;Some areas, such as the parkade area, have System Sensor SPSRA speaker/strobes (red, wall-mount, set to 70V/15cd).  &amp;lt;br&amp;gt;The stairwells have System Sensor SPWA remote speakers (white, wall-mount, set to 70V).  &amp;lt;br&amp;gt;Some areas have System Sensor SWA remote strobes (white, wall-mount, set to 15cd).&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are Notifier N-MPS-2A addressable two-stage single-action pull stations.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are Notifier FSP-851A addressable photoelectric smoke detectors in most areas.  &amp;lt;br&amp;gt;There are Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detectors in some kitchens and storage rooms, and in the loading dock.  &amp;lt;br&amp;gt;There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in the mechanical room.  &amp;lt;br&amp;gt;All aforementioned detectors are mounted on System Sensor B210LPA bases.  &amp;lt;br&amp;gt;There are System Sensor DNRA duct smoke detector housings with Notifier FSP-851A addressable photoelectric heads on all air handling units.  &amp;lt;br&amp;gt;There is an FDD CR-135-EWP conventional explosion-proof 135°F fixed-temperature/rate-of-rise heat detector in the gas meter room, wired to a Notifier FMM-101A addressable monitor module.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.  &amp;lt;br&amp;gt;There are Notifier FRM-1A addressable relay modules serving various purposes.  &amp;lt;br&amp;gt;There are Notifier FTM-1A addressable control modules on all fire phones.  &amp;lt;br&amp;gt;There is a Notifier FCM-1A addressable control module controlling a pre-action solenoid.  &amp;lt;br&amp;gt;There are Notifier ISO-XA isolator modules on all SLCs.&lt;br /&gt;
&lt;br /&gt;
====Firefighter’s Telephones====&lt;br /&gt;
There are Notifier FT-300N firefighter’s telephones at each stairwell on each floor.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Notifier EOL-CR end of line resistor plates on all sprinkler, signal, fire phone and conventional circuits.&lt;br /&gt;