<?xml version="1.0"?>
<feed xmlns="http://www.w3.org/2005/Atom" xml:lang="en">
	<id>https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=KBL_Projects_%28Main_Building%29</id>
	<title>KBL Projects (Main Building) - Revision history</title>
	<link rel="self" type="application/atom+xml" href="https://firealarmpedia.org/index.php?action=history&amp;feed=atom&amp;title=KBL_Projects_%28Main_Building%29"/>
	<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=KBL_Projects_(Main_Building)&amp;action=history"/>
	<updated>2026-05-18T12:44:18Z</updated>
	<subtitle>Revision history for this page on the wiki</subtitle>
	<generator>MediaWiki 1.41.0</generator>
	<entry>
		<id>https://firealarmpedia.org/index.php?title=KBL_Projects_(Main_Building)&amp;diff=12827&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Notifier NFS2-640C&lt;br /&gt;FACP Location: Main Entrance Vestibule&lt;br /&gt;System Type: Single-Stage Addressable&lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VDC&lt;br /&gt;System Coding: Temporal&lt;br&gt;Strobes Synchronized: Yes, System Sensor&lt;br /&gt;Date of last known Upgrade: N/A&lt;br /&gt;Most Recent Known Modification: 2010s, Some smokes&lt;br /&gt; Year Opened: 2008 |}  &#039;&#039;&#039;KBL Projects&#039;&#039;&#039; is an env...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=KBL_Projects_(Main_Building)&amp;diff=12827&amp;oldid=prev"/>
		<updated>2025-06-01T06:12:23Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Notifier NFS2-640C&amp;lt;br /&amp;gt;FACP Location: Main Entrance Vestibule&amp;lt;br /&amp;gt;System Type: Single-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: Temporal&amp;lt;br&amp;gt;Strobes Synchronized: Yes, System Sensor&amp;lt;br /&amp;gt;Date of last known Upgrade: N/A&amp;lt;br /&amp;gt;Most Recent Known Modification: 2010s, Some smokes&amp;lt;br /&amp;gt; Year Opened: 2008 |}  &amp;#039;&amp;#039;&amp;#039;KBL Projects&amp;#039;&amp;#039;&amp;#039; is an env...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Notifier NFS2-640C&amp;lt;br /&amp;gt;FACP Location: Main Entrance Vestibule&amp;lt;br /&amp;gt;System Type: Single-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: Temporal&amp;lt;br&amp;gt;Strobes Synchronized: Yes, System Sensor&amp;lt;br /&amp;gt;Date of last known Upgrade: N/A&amp;lt;br /&amp;gt;Most Recent Known Modification: 2010s, Some smokes&amp;lt;br /&amp;gt; Year Opened: 2008&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;KBL Projects&amp;#039;&amp;#039;&amp;#039; is an environmental health service located at 10501 Barlow Tr SE, Calgary, Alberta. This page will cover the main building. It was built in 2008, and the fire alarm system is original.&lt;br /&gt;
&lt;br /&gt;
==System Specifications==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by a Notifier NFS2-640C addressable fire alarm system.  The panel is located in the main entrance vestibule.  The system runs Notifier&amp;#039;s FlashScan addressable protocol, and the system coding is temporal.  &amp;lt;br&amp;gt;This panel is part of KBL&amp;#039;s NOTI-FIRE-NET network, and is networked to the other two buildings on site; this panel is equipped with an NCA-2 display.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
All notification appliances are System Sensor &amp;quot;SpectrAlert Advance&amp;quot; P2RA horn/strobes (red, wall-mount, set to 15cd).&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are Notifier FSI-851A addressable ionization smoke detectors at the top of most stairwells.  &amp;lt;br&amp;gt;There are Notifier FSP-851A addressable photoelectric smoke detectors at the top of all other stairwells as deficiency replacements.  &amp;lt;br&amp;gt;There is a Notifier FST-851RA addressable 135°F fixed-temperature/rate-of-rise heat detector in the electrical room.  &amp;lt;br&amp;gt;All detectors are mounted on Notifier B710LPA bases.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system&amp;#039;s tamper and flow switches.  &amp;lt;br&amp;gt;There are Notifier FRM-1A addressable relay modules serving various purposes.  &amp;lt;br&amp;gt;There are Notifier ISO-XA isolator modules on the SLC.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits but one; the remaining signal circuit is equipped with a Simplex 2081-9040C end of line resistor plate.&lt;br /&gt;