		<id>https://firealarmpedia.org/index.php?title=Riverview_Towers&amp;diff=12510&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: None &lt;br /&gt;System Type: 120V Hardwired &lt;br /&gt; System Line Voltage: 120VAC &lt;br /&gt; System Coding: Continuous &lt;br /&gt;Date of last known Upgrade: 2000s &lt;br /&gt;Year Opened: 1969 |}  &#039;&#039;&#039;Riverview Towers&#039;&#039;&#039; is an apartment building located at 10045 117 St NW, Edmonton, Alberta. The building was built in 1969, and the fire alarm system is mostly original, with parts replaced as deficiencies o...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Riverview_Towers&amp;diff=12510&amp;oldid=prev"/>
		<updated>2025-04-06T06:12:15Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: None &amp;lt;br /&amp;gt;System Type: 120V Hardwired &amp;lt;br /&amp;gt; System Line Voltage: 120VAC &amp;lt;br /&amp;gt; System Coding: Continuous &amp;lt;br /&amp;gt;Date of last known Upgrade: 2000s &amp;lt;br /&amp;gt;Year Opened: 1969 |}  &amp;#039;&amp;#039;&amp;#039;Riverview Towers&amp;#039;&amp;#039;&amp;#039; is an apartment building located at 10045 117 St NW, Edmonton, Alberta. The building was built in 1969, and the fire alarm system is mostly original, with parts replaced as deficiencies o...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: None &amp;lt;br /&amp;gt;System Type: 120V Hardwired &amp;lt;br /&amp;gt; System Line Voltage: 120VAC &amp;lt;br /&amp;gt; System Coding: Continuous &amp;lt;br /&amp;gt;Date of last known Upgrade: 2000s &amp;lt;br /&amp;gt;Year Opened: 1969&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Riverview Towers&amp;#039;&amp;#039;&amp;#039; is an apartment building located at 10045 117 St NW, Edmonton, Alberta. The building was built in 1969, and the fire alarm system is mostly original, with parts replaced as deficiencies occur.&lt;br /&gt;
&lt;br /&gt;
== System Specifications (1969-present) ==&lt;br /&gt;
&lt;br /&gt;
==== FACP ====&lt;br /&gt;
The building is protected by a 120V hardwired fire alarm system. There are multiple different initiating circuits corresponding to each zone, wired in series. The bells are wired in parallel, which are wired to a relay to sound when any device is activated. The system coding is continuous.&lt;br /&gt;
&lt;br /&gt;
===== Annunciators =====&lt;br /&gt;
There is an Edwards 456 annunciator in the lobby.&lt;br /&gt;
&lt;br /&gt;
==== Notification Appliances ====&lt;br /&gt;
&lt;br /&gt;
Most notification appliances are Edwards &amp;quot;Durabel&amp;quot; 6000D vibrating bells (6&amp;quot; gong), also installed in each suite. &amp;lt;br&amp;gt; There are Edwards 438D-6N5C vibrating bells (6&amp;quot; gong) as deficiency replacements. &amp;lt;br&amp;gt; There is a System Sensor SSV120-6A vibrating bell (6&amp;quot; gong) in the lobby as a deficiency replacement.&lt;br /&gt;
&lt;br /&gt;
=== Initiating Devices ===&lt;br /&gt;
&lt;br /&gt;
==== Pull Stations ====&lt;br /&gt;
&lt;br /&gt;
Most pull stations are Edwards CCS-642 conventional single-action pull stations. &amp;lt;br&amp;gt; There are Mircom MS-401 conventional single-action pull stations as deficiency replacements. &lt;br /&gt;
&lt;br /&gt;
==== Automatic Detection Devices ====&lt;br /&gt;
&lt;br /&gt;
There are American Sensors ESA5011 ionization smoke alarms throughout the building, wired to BRK relays. &amp;lt;br&amp;gt; There is a System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detector in the weight room.&lt;br /&gt;
&lt;br /&gt;
[[Category:Edmonton]]&lt;br /&gt;
[[Category:Residential]]&lt;/div&gt;</summary>