	<entry>
		<id>https://firealarmpedia.org/index.php?title=Strathmore_District_Health_Services&amp;diff=13573&amp;oldid=prev</id>
		<title>TwentyThree33: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Edwards EST3&lt;br /&gt;FACP Location: Main Electrical Room&lt;br /&gt;System Type: Two-Stage Addressable&lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VDC&lt;br /&gt;System Coding: 20BPM (Alert)&lt;br&gt;120BPM (Alarm)&lt;br&gt;Strobes Synchronized: Yes, Genesis&lt;br /&gt;Date of last known Upgrade: 2015&lt;br /&gt;Most Recent Known Modification: N/A&lt;br /&gt;Year Opened: 1984, 1988 |}  &#039;&#039;&#039;Strathmore District Health Se...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Strathmore_District_Health_Services&amp;diff=13573&amp;oldid=prev"/>
		<updated>2026-03-06T21:26:26Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Edwards EST3&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Two-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: 20BPM (Alert)&amp;lt;br&amp;gt;120BPM (Alarm)&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Genesis&amp;lt;br /&amp;gt;Date of last known Upgrade: 2015&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 1984, 1988 |}  &amp;#039;&amp;#039;&amp;#039;Strathmore District Health Se...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Edwards EST3&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Two-Stage Addressable&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: 20BPM (Alert)&amp;lt;br&amp;gt;120BPM (Alarm)&amp;lt;br&amp;gt;Strobes Synchronized: Yes, Genesis&amp;lt;br /&amp;gt;Date of last known Upgrade: 2015&amp;lt;br /&amp;gt;Most Recent Known Modification: N/A&amp;lt;br /&amp;gt;Year Opened: 1984, 1988&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Strathmore District Health Services&amp;#039;&amp;#039;&amp;#039; is a hospital located at 200 Brent Blvd, in Strathmore, Alberta, Canada.  The hospital is owned and operated by Alberta Health Services.  The building was built in 1984, was expanded in 1988, and the fire alarm system was upgraded in 2015.&lt;br /&gt;
&lt;br /&gt;
==System Specifications (2015-present)==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by an Edwards EST3 addressable fire alarm system.  The panel is located in the main electrical room.  The system runs Edwards&amp;#039; Signature addressable protocol, and is configured for two-stage operation.  The alert signal is 20BPM, and the alarm signal is 120BPM.&lt;br /&gt;
&lt;br /&gt;
=====Annunciators=====&lt;br /&gt;
There are Edwards EST3-LCDANN annunciators at the nurse&amp;#039;s station, in one room, and in the main entrance vestibule.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
All notification appliances are Edwards &amp;quot;Genesis&amp;quot; G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are EST SIGA-PS addressable photoelectric smoke detectors throughout most areas, and at the top of each stairwell.  &amp;lt;br&amp;gt;There are EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in areas such as mechanical rooms and elevator shafts.  &amp;lt;br&amp;gt;All aforementioned detectors are mounted on EST SIGA-SB bases.  &amp;lt;br&amp;gt;There are EST &amp;quot;SuperDuct&amp;quot; SIGA-SD addressable photoelectric duct smoke detectors on all air handling units, with EST SIGA-LED remote indicators connected to each detector.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There are EST SIGA-CT1 addressable monitor modules supervising the kitchen suppression system, the generator&amp;#039;s run/trouble contacts, the fire pump&amp;#039;s run/trouble contacts, the pre-action system&amp;#039;s run/trouble contacts, and the sprinkler system&amp;#039;s tamper and flow switches.  &amp;lt;br&amp;gt;There are EST SIGA-CR addressable relay modules serving various purposes.  &amp;lt;br&amp;gt;There are EST SIGA-IM addressable isolator modules on all SLCs.  &amp;lt;br&amp;gt;There are EST SIGA-MCC1S addressable control modules serving as NACs.  &amp;lt;br&amp;gt;There are EST &amp;quot;Genesis SignalMaster&amp;quot; G1M-RM modules for 4-wire horn/strobe operation.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Edwards EOL-P1 end of line resistor plates on all circuits supervised by monitor modules, and on all signal circuits.&lt;br /&gt;
&lt;br /&gt;
==Former System Specifications (1984-2015)==&lt;br /&gt;
{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! Former System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Simplex 2001&amp;lt;br /&amp;gt;FACP Location: Main Electrical Room&amp;lt;br /&amp;gt;System Type: Two-Stage Conventional&amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VDC&amp;lt;br /&amp;gt;System Coding: 20BPM (Alert)&amp;lt;br&amp;gt;90BPM (Alarm)&amp;lt;br&amp;gt;Strobes Synchronized: N/A&amp;lt;br /&amp;gt; Most Recent Known Modification: N/A&amp;lt;br/&amp;gt;Year Installed: 1984&amp;lt;br /&amp;gt;Year + Reason Decommissioned: 2015, Lifecycle Upgrade&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
====FACP====&lt;br /&gt;
The building was protected by a Simplex 2001 conventional fire alarm system.  The panel was located in the main electrical room.  The system was configured for two-stage operation.  The alert signal was 20BPM, and the alarm signal was 90BPM.&lt;br /&gt;
&lt;br /&gt;
=====Annunciators=====&lt;br /&gt;
There were Simplex annunciators in some areas.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
All notification appliances were Simplex 4080-C5 vibrating bells (6&amp;quot; gong).&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations were Simplex 2099-9905 conventional two-stage single-action pull stations.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There were Simplex 2098-9544 conventional ionization smoke detectors throughout the building.  &amp;lt;br&amp;gt;There were Simplex 4255-51 conventional 135°F fixed-temperature/rate-of-rise heat detectors in some areas.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There were Simplex 2081-9018C end of line resistor plates on all circuits.&lt;br /&gt;
&lt;br /&gt;
[[Category:Strathmore]]&lt;br /&gt;
[[Category:Healthcare]]&lt;br /&gt;
[[Category:Edwards]]&lt;/div&gt;</summary>