	<entry>
		<id>https://firealarmpedia.org/index.php?title=Willow_Lodge_S2&amp;diff=12746&amp;oldid=prev</id>
		<title>Alberta Fire Alarms: Created page with &quot;{| style=&quot;float:right;border:2px solid black&quot; |- ! System Specifications |- |  |- | FACP: Mircom FA-1000 &lt;br /&gt;FACP Location: Centre Hallway Exit &lt;br /&gt;System Type: Single-Stage Conventional &lt;br /&gt;System Line Voltage: 120VAC&lt;br /&gt;NAC Voltage: 24VFWR &lt;br /&gt;System Coding: Temporal &lt;br&gt;Strobes Synchronized: Yes, Mircom &lt;br /&gt;Date of last known Upgrade: N/A &lt;br /&gt;Most Recent Known Modification: 2023, FACP&lt;br /&gt; Year Opened: Mid 2010s |}  &#039;&#039;&#039;Willow Lodge&#039;&#039;&#039; is a Suncor camp l...&quot;</title>
		<link rel="alternate" type="text/html" href="https://firealarmpedia.org/index.php?title=Willow_Lodge_S2&amp;diff=12746&amp;oldid=prev"/>
		<updated>2025-05-13T05:05:03Z</updated>

		<summary type="html">&lt;p&gt;Created page with &amp;quot;{| style=&amp;quot;float:right;border:2px solid black&amp;quot; |- ! System Specifications |- |  |- | FACP: Mircom FA-1000 &amp;lt;br /&amp;gt;FACP Location: Centre Hallway Exit &amp;lt;br /&amp;gt;System Type: Single-Stage Conventional &amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VFWR &amp;lt;br /&amp;gt;System Coding: Temporal &amp;lt;br&amp;gt;Strobes Synchronized: Yes, Mircom &amp;lt;br /&amp;gt;Date of last known Upgrade: N/A &amp;lt;br /&amp;gt;Most Recent Known Modification: 2023, FACP&amp;lt;br /&amp;gt; Year Opened: Mid 2010s |}  &amp;#039;&amp;#039;&amp;#039;Willow Lodge&amp;#039;&amp;#039;&amp;#039; is a Suncor camp l...&amp;quot;&lt;/p&gt;
&lt;p&gt;&lt;b&gt;New page&lt;/b&gt;&lt;/p&gt;&lt;div&gt;{| style=&amp;quot;float:right;border:2px solid black&amp;quot;&lt;br /&gt;
|-&lt;br /&gt;
! System Specifications&lt;br /&gt;
|-&lt;br /&gt;
| &lt;br /&gt;
|-&lt;br /&gt;
| FACP: Mircom FA-1000 &amp;lt;br /&amp;gt;FACP Location: Centre Hallway Exit &amp;lt;br /&amp;gt;System Type: Single-Stage Conventional &amp;lt;br /&amp;gt;System Line Voltage: 120VAC&amp;lt;br /&amp;gt;NAC Voltage: 24VFWR &amp;lt;br /&amp;gt;System Coding: Temporal &amp;lt;br&amp;gt;Strobes Synchronized: Yes, Mircom &amp;lt;br /&amp;gt;Date of last known Upgrade: N/A &amp;lt;br /&amp;gt;Most Recent Known Modification: 2023, FACP&amp;lt;br /&amp;gt; Year Opened: Mid 2010s&lt;br /&gt;
|}&lt;br /&gt;
&lt;br /&gt;
&amp;#039;&amp;#039;&amp;#039;Willow Lodge&amp;#039;&amp;#039;&amp;#039; is a Suncor camp located in Wood Buffalo, Alberta, Canada.  This page will cover Building S2, which is a dormitory building built in the mid 2010s.  The fire alarm system is mostly original, with an FACP replacement occurring in 2023.&lt;br /&gt;
&lt;br /&gt;
==System Specifications==&lt;br /&gt;
====FACP====&lt;br /&gt;
The building is protected by a Mircom FA-1000 conventional fire alarm system.  The panel is located at the centre hallway exit.  The system coding is temporal.  &amp;lt;br&amp;gt;This panel replaced a Mircom FA-101T.&lt;br /&gt;
&lt;br /&gt;
====Notification Appliances====&lt;br /&gt;
All common areas have Mircom &amp;quot;Select-A-Horn/Strobe&amp;quot; FHS-340R horn/strobes (red, wall-mount, set to electromechanical/15cd).  &amp;lt;br&amp;gt;All dorm rooms have Mircom FS-400-RR remote strobes (red, wall-mount, set to 15cd) paired with Mircom MH-S25WA silenceable mini-horns (white).&lt;br /&gt;
&lt;br /&gt;
===Initiating Devices===&lt;br /&gt;
====Pull Stations====&lt;br /&gt;
All pull stations are Mircom MS-401 conventional single-action pull stations.&lt;br /&gt;
&lt;br /&gt;
====Automatic Detection Devices====&lt;br /&gt;
There are Mircom TD-135 conventional 135°F fixed-temperature heat detectors in all service and dorm rooms.  &amp;lt;br&amp;gt;There are Mircom TD-200 conventional 200°F fixed-temperature heat detectors in all water heater and laundry rooms.  &amp;lt;br&amp;gt;There are System Sensor C2W-BA conventional photoelectric smoke detectors throughout all corridors.&lt;br /&gt;
&lt;br /&gt;
====Modules====&lt;br /&gt;
There is a Mircom MIX-4050 sync module synchronizing all strobes.&lt;br /&gt;
&lt;br /&gt;
====EOLs====&lt;br /&gt;
There are Mircom MP-300 end of line resistor plates on all circuits.&lt;br /&gt;
&lt;br /&gt;
[[Category:Alberta]]&lt;br /&gt;