| FACP: Edwards EST3X <br /> FACP Location: TBA <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2019 <br />Year Opened: 1967
| FACP: Edwards EST3X <br /> FACP Location: Boiler Room<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, Genesis<br />Date of last known Upgrade: 2019 <br />Year Opened: 1967
|}
|}
'''Centennial Planetarium''' was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of [[TELUS Spark]] in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant.
'''Centennial Planetarium''' was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of [[TELUS Spark]] in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant.
== System Specifications (2018-present) ==
== System Specifications (2018-present) ==
==== FACP ====
==== FACP ====
The planetarium is protected by an Edwards EST3X addressable fire alarm system. The panel is located (Nathan, please fill). The system runs EST's Signature-series addressable protocol, and the system coding is Temporal.
The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the boiler room. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.
 
===== Annunciators =====
There is an Edwards EST3-6ANN annunciator equipped with an LCDXL1 display at the main entrance.
 
==== Notification Appliances ====
==== Notification Appliances ====
The notification appliances are EST "Genesis" G1R-HDVM (red, wall, no FIRE) horn/strobes throughout the building. There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected.
All notification appliances are EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).  
 
There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
Line 20: Line 24:
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases.
The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases.
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
==== EOLs ====
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.
== Former System Specifications (East Wing) (2000s-2011) ==
== Former System Specifications (East Wing) (2000s-2011) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 27: Line 37:
|  
|  
|-
|-
| FACP: Notifier AFP-400 <br /> FACP Location: Unknown <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (first stage) <br> Temporal (GA) <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2005 <br />Year Decomissioned: 2011
| FACP: Notifier AFP-400 <br /> FACP Location: Unknown <br />System Type: Two-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (Alert) <br> Temporal (Alarm) <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2005 <br />Year Decomissioned: 2011
|}
|}
==== FACP ====
==== FACP ====
The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The system coding was 20BPM for first stage, and temporal for general alarm.
The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The alert coding was 20BPM, and the alarm coding was temporal.
==== Notification Appliances ====
==== Notification Appliances ====
The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd)
The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd)
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier MMX-101A addressable modules, behind each station.
The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier FMM-101A addressable modules, behind each station.
 
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
 
Not available.
Not available
== Former System Specifcations (West Wing) (Early 2000s-2011) ==
== Former System Specifcations (West Wing) (Early 2000s-2011) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 47: Line 55:
|  
|  
|-
|-
| FACP: Edwards EST2? <br /> FACP Location: Unknown <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (first stage) <br> Continuous (GA) <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2000s <br />Year Decomissioned: 2011
| FACP: Edwards EST2? <br /> FACP Location: Unknown <br />System Type: Two-Stage Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (first stage) <br> Continuous (GA) <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2000s <br />Year Decomissioned: 2011
|}
|}
==== FACP ====
==== FACP ====
The West Wing was most likely protected by an Edwards EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm.
The West Wing was most likely protected by an Edwards EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm.
==== Notification Appliances ====
==== Notification Appliances ====
The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd).  
The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd) and others mounted remotely.  
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations were all Edwards 270P-SPO conventional two-stage pull stations.
The pull stations were all Edwards 270P-SPO conventional two-stage pull stations.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
Not available.
Not available.
[[Category:Facilitie]
[[Category:Calgary]]
[[Category:Facilitie]
[[Category:Museums]]
[[Category:Iconic buildings in Calgary]]

Latest revision as of 16:21, 23 September 2024

System Specifications
FACP: Edwards EST3X
FACP Location: Boiler Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, Genesis
Date of last known Upgrade: 2019
Year Opened: 1967

Centennial Planetarium was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of TELUS Spark in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant.

System Specifications (2018-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the boiler room. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is an Edwards EST3-6ANN annunciator equipped with an LCDXL1 display at the main entrance.

Notification Appliances[edit | edit source]

All notification appliances are EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).

There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

The pull stations are EST SIGA-270 addressable pull stations.

Automatic Detection Devices[edit | edit source]

The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.

Former System Specifications (East Wing) (2000s-2011)[edit | edit source]

System Specifications
FACP: Notifier AFP-400
FACP Location: Unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: No
Date of last known Upgrade: 2005
Year Decomissioned: 2011

FACP[edit | edit source]

The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The alert coding was 20BPM, and the alarm coding was temporal.

Notification Appliances[edit | edit source]

The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd)

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier FMM-101A addressable modules, behind each station.

Automatic Detection Devices[edit | edit source]

Not available.

Former System Specifcations (West Wing) (Early 2000s-2011)[edit | edit source]

System Specifications
FACP: Edwards EST2?
FACP Location: Unknown
System Type: Two-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (first stage)
Continuous (GA)
Strobes Synchronized: Yes
Date of last known Upgrade: 2000s
Year Decomissioned: 2011

FACP[edit | edit source]

The West Wing was most likely protected by an Edwards EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm.

Notification Appliances[edit | edit source]

The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd) and others mounted remotely.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

The pull stations were all Edwards 270P-SPO conventional two-stage pull stations.

Automatic Detection Devices[edit | edit source]

Not available.