More actions
mNo edit summary |
|||
(8 intermediate revisions by 3 users not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier NFS-320C <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: 2014 <br />Year Opened: 2004 | | FACP: Notifier NFS-320C <br /> FACP Location: Main Entrance <br> System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br> Date of last known Upgrade: 2014 <br />Year Opened: 2004 | ||
|} | |} | ||
The '''Crowfoot Library''' is a public library located at 8665 Nose Hill Drive Northwest, in Calgary, Alberta, Canada. It is part of the Calgary Public Library. The building opened in 2004, and the fire alarm system is mostly from 2014. All of the notification appliances are original. | |||
The '''Crowfoot Library''' is a public library in | |||
== System Specifications (2014-present) == | == System Specifications (2014-present) == | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule, between two book return slots. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal. | |||
The | |||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances are the original System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). These are mounted on the ceiling throughout the library. | |||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are Notifier NBG-12LX addressable dual-action pull stations. | |||
All | |||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the library, mounted on System Sensor B210LPA low-profile bases. There is also a sprinkler system with waterflow detection. | |||
==== Modules ==== | |||
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches. | |||
==== EOLs ==== | |||
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits. | |||
== Former System Specifications == | == Former System Specifications (2004-2014) == | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
! System Specifications | ! Former System Specifications | ||
|- | |- | ||
| | | | ||
|- | |- | ||
| FACP: Simplex 4010 <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2014 | | FACP: Simplex 4010 <br /> FACP Location: Main Entrance <br> System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: No <br> Date of last known Upgrade: N/A <br />Year Decommissioned: 2014 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building was protected by a Simplex 4010 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Simplex's IDNet addressable protocol, and the system coding was temporal. | |||
The | |||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances were System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). These are still in use on the Notifier system, and were likely installed due to customer preference. | |||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations were Simplex 4099-9001 addressable single-action pull stations. | |||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There were Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors throughout the library, mounted on Simplex 4098-9792 addressable bases. There is also a sprinkler system with waterflow detection. | |||
==== Modules ==== | |||
There were Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches. | |||
==== EOLs ==== | |||
There were Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits. | |||
[[Category:Calgary]] | |||
[[Category:Libraries]] |
Latest revision as of 10:01, 24 September 2024
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes Date of last known Upgrade: 2014 Year Opened: 2004 |
The Crowfoot Library is a public library located at 8665 Nose Hill Drive Northwest, in Calgary, Alberta, Canada. It is part of the Calgary Public Library. The building opened in 2004, and the fire alarm system is mostly from 2014. All of the notification appliances are original.
System Specifications (2014-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the main entrance vestibule, between two book return slots. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All notification appliances are the original System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). These are mounted on the ceiling throughout the library.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the library, mounted on System Sensor B210LPA low-profile bases. There is also a sprinkler system with waterflow detection.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs[edit | edit source]
There are Notifier EOL-CR end-of-line resistor plates on all sprinkler and signal circuits.
Former System Specifications (2004-2014)[edit | edit source]
Former System Specifications |
---|
FACP: Simplex 4010 FACP Location: Main Entrance System Type: Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: No Date of last known Upgrade: N/A Year Decommissioned: 2014 |
FACP[edit | edit source]
The building was protected by a Simplex 4010 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran Simplex's IDNet addressable protocol, and the system coding was temporal.
Notification Appliances[edit | edit source]
All notification appliances were System Sensor "SpectrAlert" P2415A horn/strobes (red, wall-mount, 15cd). These are still in use on the Notifier system, and were likely installed due to customer preference.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Simplex 4099-9001 addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
There were Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors throughout the library, mounted on Simplex 4098-9792 addressable bases. There is also a sprinkler system with waterflow detection.
Modules[edit | edit source]
There were Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs[edit | edit source]
There were Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits.