Line 5: Line 5:
|  
|  
|-
|-
| FACP: Siemens FireFinder XLS <br /> FACP Location: Behind Front Desk <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: 20BPM (First Stage) <br> Temporal (GA) <br> Strobes Synchronized: Yes, Siemens <br />Date of last known Upgrade: 2009 <br />Year Opened: 1980
| FACP: Siemens FireFinder XLS <br /> FACP Location: Behind Front Desk <br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br>24VDC (Visual) <br />System Coding: 20BPM (Alert) <br>Temporal (Alarm)<br>Strobes Synchronized: Yes, Siemens <br />Date of last known Upgrade: 2009 <br />Year Opened: 1980
|}
|}
 
'''Delta''' is a Canadian chain of hotels owned by Marriott. The chain is headquartered in Rockville, Maryland, USA, and has locations across Canada. This particular hotel is located at 209 4 Avenue Southeast, in Downtown Calgary, Alberta, Canada. The hotel opened in 1980, and was extensively renovated in 2009. The fire alarm system was upgraded in 2009.
'''Delta''' is a Canadian chain of hotels owned by Marriott. The chain is headquartered in Rockville, Maryland, USA, and has locations across Canada. This particular hotel is located at 209 4 Avenue Southeast, in Downtown Calgary, Alberta, Canada. The hotel opened in 1980, and was extensively renovated in 2009. The fire alarm system was upgraded in 2009.
 
==System Specifications (2009-present)==
==System Specifications (2009-present)==
====FACP====
====FACP====
The building is protected by a Siemens FireFinder XLS addressable fire alarm system. The panel is located behind the front desk. The system runs Siemens’ FirePrint addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. First stage coding is 20BPM, followed by temporal in general alarm.  Live announcements are made over the fire alarm system in lieu of pre-recorded messages.
The building is protected by a Siemens FireFinder XLS addressable fire alarm system. The panel is located behind the front desk. The system runs Siemens’ FirePrint addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is a temporal tone.  Live announcements are made over the fire alarm system in lieu of pre-recorded messages.
 
=====Annunciators=====
=====Annunciators=====
There is a Siemens SSD annunciator in the main entrance vestibule.
There is a Siemens SSD annunciator in the main entrance vestibule.
====Notification Appliances====
====Notification Appliances====
=====Common Areas=====
=====Common Areas=====
Most notification appliances are Siemens SE-MC-CW-B speaker/strobes (white, wall-mount, set to 70V/15cd). Some areas have Siemens SEC-W remote speakers (white, ceiling-mount) for additional sound coverage.
Most notification appliances are Siemens SE-MC-CW-B speaker/strobes (white, wall-mount, set to 70V/15cd). Some areas have Siemens SEC-W remote speakers (white, ceiling-mount) for additional sound coverage.
=====Guest Rooms=====
=====Guest Rooms=====
All guest rooms have Siemens SE-W remote speakers (white, wall-mount, set to 70V).
All guest rooms have Siemens SE-W remote speakers (white, wall-mount, set to 70V).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Siemens HMS-2S addressable two-stage single-action pull stations.
All pull stations are Siemens HMS-2S addressable two-stage single-action pull stations.
====Automatic Detection Devices====
There are Siemens HFP-11 addressable multisensor smoke/heat detectors in all guest rooms. There is also a sprinkler system protecting the entire hotel.
====Modules====
There are Siemens HTRI-S addressable monitor modules supervising the sprinkler system’s tamper and flow switches.


====Automatic Detection Devices====
There are Siemens HTRI-R addressable relay modules serving various purposes.
There are Siemens FP-11 addressable multisensor smoke/heat detectors in all guest rooms.  There is also a sprinkler system protecting the entire hotel.


====Modules====
==== EOLs ====
There are Siemens TRI-S addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are Siemens EL-300C end of line resistor plates on all sprinkler and signal circuits.
[[Category:Facilities]]

Latest revision as of 16:20, 25 September 2024

System Specifications
FACP: Siemens FireFinder XLS
FACP Location: Behind Front Desk
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM (Alert)
Temporal (Alarm)
Strobes Synchronized: Yes, Siemens
Date of last known Upgrade: 2009
Year Opened: 1980

Delta is a Canadian chain of hotels owned by Marriott. The chain is headquartered in Rockville, Maryland, USA, and has locations across Canada. This particular hotel is located at 209 4 Avenue Southeast, in Downtown Calgary, Alberta, Canada. The hotel opened in 1980, and was extensively renovated in 2009. The fire alarm system was upgraded in 2009.

System Specifications (2009-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Siemens FireFinder XLS addressable fire alarm system. The panel is located behind the front desk. The system runs Siemens’ FirePrint addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is a temporal tone. Live announcements are made over the fire alarm system in lieu of pre-recorded messages.

Annunciators[edit | edit source]

There is a Siemens SSD annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

Common Areas[edit | edit source]

Most notification appliances are Siemens SE-MC-CW-B speaker/strobes (white, wall-mount, set to 70V/15cd). Some areas have Siemens SEC-W remote speakers (white, ceiling-mount) for additional sound coverage.

Guest Rooms[edit | edit source]

All guest rooms have Siemens SE-W remote speakers (white, wall-mount, set to 70V).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Siemens HMS-2S addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Siemens HFP-11 addressable multisensor smoke/heat detectors in all guest rooms. There is also a sprinkler system protecting the entire hotel.

Modules[edit | edit source]

There are Siemens HTRI-S addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

There are Siemens HTRI-R addressable relay modules serving various purposes.

EOLs[edit | edit source]

There are Siemens EL-300C end of line resistor plates on all sprinkler and signal circuits.