| FACP: Simplex 4100+ <br />FACP Location: Main Electrical Room <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: N/A <br />Date of last known Upgrade: N/A <br />Year Opened: 1996 | | FACP: Simplex 4100+ <br />FACP Location: Main Electrical Room <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Continuous <br>Strobes Synchronized: N/A <br />Date of last known Upgrade: N/A <br />Year Opened: 1996 | ||
|} | |} | ||
'''Edward Milne Community School''' is a school located at 6218 Sooke Road, in Sooke, British Columbia, Canada. The school opened in 1996, and the fire alarm system is mostly original. The theatre has a separate fire alarm system from the rest of the building. | |||
'''Edward Milne Community School''' is a school located at 6218 Sooke Road, in Sooke, British Columbia, Canada. | |||
==System Specifications (Main Building)== | ==System Specifications (Main Building)== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Simplex 4100+ conventional fire alarm system. | The building is protected by a Simplex 4100+ conventional fire alarm system. The panel is located in the main electrical room. The system coding is continuous. | ||
=====Annunciators===== | =====Annunciators===== | ||
There is a Simplex 4602-9102 annunciator paired with three Simplex 4602-9101 annunciators outside the main entrance. | There is a Simplex 4602-9102 annunciator paired with three Simplex 4602-9101 annunciators outside the main entrance. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All notification appliances are Simplex 2901-9722 motor bells (10” gong). | All notification appliances are Simplex 2901-9722 motor bells (10” gong). | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations but one are Simplex MS-301C conventional single-action pull stations. | All pull stations but one are Simplex MS-301C conventional single-action pull stations. There is a Mircom MS-401 conventional single-action pull station near one exit as a deficiency replacement. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Simplex 2098-9110 conventional ionization smoke detectors throughout the building. | There are Simplex 2098-9110 conventional ionization smoke detectors throughout the building. There are Simplex 2098-9465 duct smoke detectors on all air handling units. The building is equipped with a sprinkler system. | ||
==System Specifications (Theatre)== | ==System Specifications (Theatre)== | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 38: | Line 30: | ||
|} | |} | ||
====FACP==== | ====FACP==== | ||
The theatre is protected by an EST FireShield FS302G conventional fire alarm system. | The theatre is protected by an EST FireShield FS302G conventional fire alarm system. The panel is located in the main electrical room. The system coding is likely temporal. | ||
=====Annunciators===== | =====Annunciators===== | ||
There is an EST FSRSI annunciator paired with an EST FSRZI annunciator outside the building, mounted on an EST FSAT-2 chassis. | There is an EST FSRSI annunciator paired with an EST FSRZI annunciator outside the building, mounted on an EST FSAT-2 chassis. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All notification appliances are Edwards 439D-6AWC vibrating bells (6” gong) mounted on Edwards 403-5A-R strobe plates (15cd). | All notification appliances are Edwards 439D-6AWC vibrating bells (6” gong) mounted on Edwards 403-5A-R strobe plates (15cd). | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Edwards 270-SPO conventional single-action pull stations. | All pull stations are Edwards 270-SPO conventional single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Edwards 281B-PL conventional 135°F fixed/rate-of-rise heat detectors mounted on the walls. | There are Edwards 281B-PL conventional 135°F fixed/rate-of-rise heat detectors mounted on the walls. There is an FDD CR135 conventional 135°F fixed/rate-of-rise heat detector mounted at the top of the theatre. | ||
[[Category:British Columbia]] | |||
[[Category:Schools]] |
Latest revision as of 13:23, 26 September 2024
System Specifications |
---|
FACP: Simplex 4100+ FACP Location: Main Electrical Room System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: N/A Date of last known Upgrade: N/A Year Opened: 1996 |
Edward Milne Community School is a school located at 6218 Sooke Road, in Sooke, British Columbia, Canada. The school opened in 1996, and the fire alarm system is mostly original. The theatre has a separate fire alarm system from the rest of the building.
System Specifications (Main Building)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Simplex 4100+ conventional fire alarm system. The panel is located in the main electrical room. The system coding is continuous.
Annunciators[edit | edit source]
There is a Simplex 4602-9102 annunciator paired with three Simplex 4602-9101 annunciators outside the main entrance.
Notification Appliances[edit | edit source]
All notification appliances are Simplex 2901-9722 motor bells (10” gong).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations but one are Simplex MS-301C conventional single-action pull stations. There is a Mircom MS-401 conventional single-action pull station near one exit as a deficiency replacement.
Automatic Detection Devices[edit | edit source]
There are Simplex 2098-9110 conventional ionization smoke detectors throughout the building. There are Simplex 2098-9465 duct smoke detectors on all air handling units. The building is equipped with a sprinkler system.
System Specifications (Theatre)[edit | edit source]
System Specifications |
---|
FACP: EST FireShield FACP Location: Main Electrical Room System Type: Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal? Strobes Synchronized: No Date of last known Upgrade: N/A Year Opened: 1996 |
FACP[edit | edit source]
The theatre is protected by an EST FireShield FS302G conventional fire alarm system. The panel is located in the main electrical room. The system coding is likely temporal.
Annunciators[edit | edit source]
There is an EST FSRSI annunciator paired with an EST FSRZI annunciator outside the building, mounted on an EST FSAT-2 chassis.
Notification Appliances[edit | edit source]
All notification appliances are Edwards 439D-6AWC vibrating bells (6” gong) mounted on Edwards 403-5A-R strobe plates (15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Edwards 281B-PL conventional 135°F fixed/rate-of-rise heat detectors mounted on the walls. There is an FDD CR135 conventional 135°F fixed/rate-of-rise heat detector mounted at the top of the theatre.