More actions
No edit summary |
No edit summary |
||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Simplex 4100ES <br /> FACP Location: CACF Room <br />System Type: | | FACP: Simplex 4100ES <br />FACP Location: CACF Room <br />System Type: Two-Stage Networked Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br>24VDC (Visual) <br />System Coding: 20BPM Tone (Alert) <br>Slow Whoop (Alarm) <br>Strobes Synchronized: Yes, Wheelock <br />Date of last known Upgrade: 2010s <br />Year Opened: 1981 | ||
|} | |} | ||
'''First Tower''' is a high-rise office building located at 411 1 Street Southeast, in Downtown Calgary, Alberta, Canada. The tower opened in 1981, and the fire alarm system was upgraded in the 2010s. | '''First Tower''' is a high-rise office building located at 411 1 Street Southeast, in Downtown Calgary, Alberta, Canada. The tower opened in 1981, and the fire alarm system was upgraded in the 2010s. | ||
==System Specifications (2010s-present)== | ==System Specifications (2010s-present)== | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Simplex 4100ES addressable fire alarm | The building is protected by a Simplex 4120 networked fire alarm system. There are several nodes, all are Simplex 4100ES addressable fire alarm panels. The main node is likely located in a CACF room. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is slow whoop. There are custom messages for each stage. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
=====Most Areas===== | =====Most Areas===== | ||
Line 20: | Line 20: | ||
All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations. | All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 addressable bases | There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 addressable bases. | ||
====Modules==== | ====Modules==== | ||
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. There are also Simplex 4090-9002 addressable relay modules controlling fire doors, dampers, fan shutdowns, and other systems. | There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
There are also Simplex 4090-9002 addressable relay modules controlling fire doors, dampers, fan shutdowns, and other systems. | |||
==== EOLs ==== | |||
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits. | |||
[[Category:Calgary]] | [[Category:Calgary]] | ||
[[Category:Commercial]] | [[Category:Commercial]] |
Latest revision as of 13:50, 27 September 2024
System Specifications |
---|
FACP: Simplex 4100ES FACP Location: CACF Room System Type: Two-Stage Networked Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VDC (Visual) System Coding: 20BPM Tone (Alert) Slow Whoop (Alarm) Strobes Synchronized: Yes, Wheelock Date of last known Upgrade: 2010s Year Opened: 1981 |
First Tower is a high-rise office building located at 411 1 Street Southeast, in Downtown Calgary, Alberta, Canada. The tower opened in 1981, and the fire alarm system was upgraded in the 2010s.
System Specifications (2010s-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Simplex 4120 networked fire alarm system. There are several nodes, all are Simplex 4100ES addressable fire alarm panels. The main node is likely located in a CACF room. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation. The alert signal is a 20BPM tone, and the alarm signal is slow whoop. There are custom messages for each stage.
Notification Appliances[edit | edit source]
Most Areas[edit | edit source]
All notification appliances are Wheelock E90-24MCC-FW speaker/strobes (white, ceiling-mount, set to 70V/15cd).
Terrace[edit | edit source]
All notification appliances are Wheelock ET-1080R weatherproof remote speakers (red, wall-mount, set to 70V), mounted next to Wheelock RSSWP-2475-FR remote strobes (red, wall-mount, 180cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 addressable bases.
Modules[edit | edit source]
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are also Simplex 4090-9002 addressable relay modules controlling fire doors, dampers, fan shutdowns, and other systems.
EOLs[edit | edit source]
There are Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.