LOCAL Public Eatery 8th Avenue: Difference between revisions

From FireAlarmPedia
No edit summary
No edit summary
 
(One intermediate revision by one other user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Simplex 4010ES <br />FACP Location: Main Entrance <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: 2010s <br />Year Opened: 1974
| FACP: Simplex 4010ES <br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: 2013 <br />Year Opened: 1974
|}
|}
'''Local Public Eatery''' is a chain of upscale bars. This particular bar is located at 310 8 Avenue Southwest, in Calgary, Alberta, Canada. The building was built in 1974, and became LOCAL Public Eatery in the 2010s. The fire alarm system was upgraded in the 2010s.
'''Local Public Eatery''' is a chain of upscale bars. This particular bar is located at 310 8 Avenue Southwest, in Calgary, Alberta, Canada. The building was built in 1974, and became LOCAL Public Eatery in 2013. The fire alarm system was upgraded in 2013.
==System Specifications (2010s-present)==
==System Specifications (2013-present)==
====FACP====
====FACP====
The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal. This panel replaced a Mirtone 7800.
The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal. This panel replaced a Mirtone 7800.

Latest revision as of 13:01, 30 September 2024

System Specifications
FACP: Simplex 4010ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2013
Year Opened: 1974

Local Public Eatery is a chain of upscale bars. This particular bar is located at 310 8 Avenue Southwest, in Calgary, Alberta, Canada. The building was built in 1974, and became LOCAL Public Eatery in 2013. The fire alarm system was upgraded in 2013.

System Specifications (2013-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal. This panel replaced a Mirtone 7800.

Notification Appliances[edit | edit source]

All notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors throughout the building, mounted on Simplex 4098-9792 bases.