Riverwest Condominiums: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- !System Specifications |- | |- |FACP: EST EST3 FACP Location: CACF Room System Type: Addressable System Line Voltage: 12...")
 
No edit summary
 
(4 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|
|
|-
|-
|FACP: EST EST3
|FACP: Edwards EST3 <br> FACP Location: CACF Room <br> System Type: Single-Stage Addressable <br> System Line Voltage: 120VAC <br> NAC Voltage: 70.7Vrms/24VDC (strobe) <br> System Coding: Temporal 3 (1200Hz) <br> Strobes Synchronized: Yes <br> Date of last known Upgrade: 2022 <br> Year Opened: 2005 (West) / 2006 (East)
 
|}'''Riverwest Condominums''' is pair of condo towers located at 1078 6 Ave SW, Calgary, Alberta. It was built in 2005 and the system is mostly original.
 
FACP Location: CACF Room  
 
System Type: Addressable  
 
System Line Voltage: 120VAC
 
NAC Voltage: 70.7Vrms/24VDC (strobe)  
 
System Coding: Temporal 3 (1200Hz)
 
Strobes Synchronized: Yes
 
Date of last known Upgrade: 2022
 
Year Opened: 2005 (West) / 2006 (East)
|}'''Buiding Name'''(General Building and System Description Goes Here)
==System Specifications==
==System Specifications==
===FACP===
===FACP===
The building is protected by a network of four CPU's all located in the West tower CACF room, two of which have control cards. (1/2) Nodes 4 and 5 are dedicated amplifier cabinets for both the East and West tower.  
The building is protected by an Edwards EST3 addressable fire alarm system. It is a network of four CPU's all located in the West tower CACF room, two of which have control cards. (1/2) Nodes 4 and 5 are dedicated amplifier cabinets for both the East and West tower. The system runs Edwards' Signature addressable protocol, and is equipped with voice-evacuation. The system coding is temporal.
=====Annunciators=====
=====Annunciators=====
There is an EST 3LCD-ANN in the East Tower "Fire Alarm Room"
There is an EST 3LCD-ANN in the East Tower "Fire Alarm Room"
Line 37: Line 20:
All pull stations are EST SIGA-270. Most are original with a few deficiency replacements noticed.
All pull stations are EST SIGA-270. Most are original with a few deficiency replacements noticed.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA-PS detectors located throughout with a few SIGA2-PS and SIGA-OSD replacements.
There are EST SIGA-PS detectors located throughout with a few SIGA2-PS and SIGA-OSD replacements. These are mounted to SIGA-SB bases.
 
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.
[[Category:Facilities]]
[[Category:Residential]]
[[Category:Calgary]]

Latest revision as of 22:13, 11 October 2024

System Specifications
FACP: Edwards EST3
FACP Location: CACF Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7Vrms/24VDC (strobe)
System Coding: Temporal 3 (1200Hz)
Strobes Synchronized: Yes
Date of last known Upgrade: 2022
Year Opened: 2005 (West) / 2006 (East)

Riverwest Condominums is pair of condo towers located at 1078 6 Ave SW, Calgary, Alberta. It was built in 2005 and the system is mostly original.

System Specifications

FACP

The building is protected by an Edwards EST3 addressable fire alarm system. It is a network of four CPU's all located in the West tower CACF room, two of which have control cards. (1/2) Nodes 4 and 5 are dedicated amplifier cabinets for both the East and West tower. The system runs Edwards' Signature addressable protocol, and is equipped with voice-evacuation. The system coding is temporal.

Annunciators

There is an EST 3LCD-ANN in the East Tower "Fire Alarm Room"

Notification Appliances

Public Notification Appliances on Consist of mostly Edwards 965-7A-4RW 4-inch speaker strobes. With 757-7A-SS70 "Integrity" Speaker strobes installed in the parkade. EST 757S2-15PS are oddly installed on only the Third Floor. There was a few EST "Genesis" GCAVRF LED Ceiling mount strobes installed as deficiency replacements in 2022.

In the suites there are all Edwards 965-1C-4RW ceiling speakers with Edwards 965-7A-4RW ceiling speaker/strobes in sleeping areas. Edwards 684-1C Silence switches are provided in each unit. One GCAVRF LED Ceiling mount strobe was installed a deficiency replacement in 2022.

Initiating Devices

Pull Stations

All pull stations are EST SIGA-270. Most are original with a few deficiency replacements noticed.

Automatic Detection Devices

There are EST SIGA-PS detectors located throughout with a few SIGA2-PS and SIGA-OSD replacements. These are mounted to SIGA-SB bases.

Modules

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.