'''Southland Leisure Centre''' is an indoor leisure centre in the Palliser neighborhood of SW Calgary. It is known for its wave pool and big indoor water park. The facility was built in 1983, but the fire alarm system is not original. The facility was renovated in 2008, and the system is from then.
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Edwards EST4 <br>FACP Location: Behind Customer Service<br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (Alert) <br>Temporal (Alarm) <br />Date of Last Known Upgrade: 2023<br />Year Opened: 1983, 2008
|}
'''Southland Leisure Centre''' is an indoor leisure centre located at 2000 Southland Drive Southwest, in Calgary, Alberta, Canada. The facility is owned and operated by the City of Calgary. The building opened in 1983, and was renovated in 2008. The fire alarm system was upgraded in 2008, and again in May of 2023.
==System Specifications (May 2023-present)==
====FACP====
The building is protected by an Edwards EST4 addressable fire alarm system. The panel is located behind the customer service desk. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. Alert signal coding is 20BPM, followed by temporal for the evacuation signal.
=====Annunciators=====
There is an Edwards EST4-4ANN annunciator in the main entrance vestibule.
====Notification Appliances====
The notification appliances were left untouched during the upgrade.


== System Specifications ==
Most notification appliances are Siemens MBDC-6 motor bells (6" gong). <br>Areas with higher ambient noise levels, such as the pool area, have Siemens MBDC-10 motor bells (10” gong). <br>There is one Wheelock MB-G6-24 motor bell (6” gong) in the men’s locker room, which was not replaced during the 2008 upgrade. <br>There is a Siemens SFM24-10 motor bell (10" gong) by the play structure in the pool area as a deficiency replacement.
===Initiating Devices===
====Pull Stations====
All pull stations are Edwards SIGA-270P addressable two-stage single-action pull stations.
====Automatic Detection Devices====
There are Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors in the elevator shaft, around the perimeter of the main lobby, and in some mechanical rooms. <br>There is an Edwards SIGA-OSD addressable optical smoke detector in the elevator machine room. <br>All detectors are mounted on Edwards SIGA-SB bases. <br>There are Edwards SIGA-SD addressable photoelectric duct smoke detectors on several air handling units. <br>The building is equipped with a sprinkler system.
====Modules====
There are Edwards SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.


==== FACP ====
There are Edwards SIGA-CR addressable relays for elevator recall.
 
There are Edwards SIGA-IM addressable isolator modules on the SLC.


The fire alarm panel is a Siemens MXL. It was installed in 2008 after renovations. The fire panel is not visible, but the annunciator is at the entrance.
==== EOLs ====
There are Siemens EL-300C end-of-line resistor plates on all sprinkler and signal circuits.


==== Notification Appliances ====


The notification appliances mainly consist of Siemens MBDC-10 motor bells throughout the facility, and a few Siemens MBDC-6 motor bells in the changerooms and some areas. There is one in the pool area, near the for additional sound on the water park, for additional sound coverage (which has lost its label). These bells were installed in 2008. There is one Wheelock MB-G6-24 motor bell in the men's changeroom, left over from the previous fire alarm system (it has the pre-2007 logo). There is a Siemens SFM24-10A motor bell by the splash area in the pool area, as a replacement for an MBDC-10 that stopped working.


==System Specifications (2008-May 2023)==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Siemens MXL-IQ<br>FACP Location: Behind Customer Service<br />System Type: Two-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br>System Coding: 20BPM (Alert) <br>Temporal (Alarm)<br />Year Installed: 2008
Year of last known upgrade: 2015<br>Year Decommissioned: 2023
|}
==== FACP ====
The building was protected by a Siemens MXL-IQ addressable fire alarm system. The panel was located behind the customer service desk. The system ran Siemens' FirePrint addressable protocol, and was configured for two-stage operation. Alert signal coding was 20BPM, followed by temporal in evacuation signal. This panel was replaced due to an issue with the alarm relay contacts.
===== Annunciators =====
There was a Siemens RCC-3 annunciator in the main entrance vestibule.
==== Notification Appliances ====
Most notification appliances were Siemens MBDC-6 motor bells (6" gong). <br>Areas with higher ambient noise levels, such as the pool area, had Siemens MBDC-10 motor bells (10” gong). <br>There was one Wheelock MB-G6-24 motor bell (6” gong) in the men’s locker room, which was not replaced during the 2008 upgrade. <br>There was a Siemens SFM24-10 motor bell (10" gong) by the play structure in the pool area as a deficiency replacement. <br>All devices remain in use on the current fire alarm system.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
All pull stations were Siemens MSI-30B addressable two-stage single-action pull stations.
==== Automatic Detection Devices ====
There was a Siemens “FirePrint” FP-11 addressable multisensor smoke/heat detector in the elevator machine room.


==== Pull Stations ====
There were Siemens FPT-11 addressable fixed-temperature/rate-of-rise heat detectors in the elevator shaft, around the perimeter of the main lobby, and in some mechanical rooms.
==== Modules ====
There were Siemens TRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
There were Siemens LIM-1 addressable isolator modules on the SLC.


The pull stations are Siemens HMS-2S/MSI-30B two-stage addressable pull stations installed in 2008.
==== EOLs ====
There are Siemens EL-300C end-of-line resistor plates on all sprinkler and signal circuits.


==== Automatic Detection Devices ====
==System Specifications (1983-2008)==
Please note that these details are unconfirmed.
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Edwards Custom 6500 <br />FACP Location: Behind Reception <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (Alert) <br>120BPM (Evac) <br>Strobes Synchronized: N/A <br />Year Installed: 1983 <br />Year Decommissioned: 2008
|}
====FACP====
The building was protected by an Edwards Custom 6500 conventional fire alarm system. The panel was located behind the reception desk. The system was configured for two-stage operation. The alert signal was 20BPM, followed by 120BPM march time for the evacuation signal.
====Notification Appliances====
All notification appliances were Edwards “Durabel” 6100D vibrating bells (6’ gong).


None noticed.
There was one Wheelock MB-G6-24 motor bell (6" gong) in the mens' locker room as a deficiency replacement. This bell is still in service.
===Initiating Devices===
====Pull Stations====
All pull stations were Edwards 270-GAO conventional two-stage single-action pull stations.
====Automatic Detection Devices====
There were likely Edwards 281C conventional 135°F fixed-temperature/rate-of-rise heat detectors in some areas.


==== EOLs ====
There were Edwards EOL-P1 end-of-line resistor plates on circuits.


== Bonus Information ==
== Bonus Information ==
For the wave pool warning system, there is an Edwards "Adaptahorn" 874-N5 horn and an Edwards "Adaptabeacon" 110FINB-N5 blue strobe at the back of the pool. The horn is set to a very loud volume, and there's a sign above the two saying "WARNING! Light and buzzer activate. Waves will be on in 10 seconds"
For the wave pool warning system, there is an Edwards "Adaptahorn" 874-N5 horn and an Edwards "Adaptabeacon" 110FINB-N5 blue strobe at the back of the pool. The horn is set to a very loud volume, and there's a sign above the two saying "WARNING! Light and buzzer activate. Waves will be on in 10 seconds"
There is a bell gong mounted on a water motor on the play structure water bucket in the pool area. The bell rings when the bucket is about to dump, and increases in speed until the dump occurs.
==Permit Information==
Commercial / Multi Family Project is Issued Permit. Permit issued on 2023-05-25. Project scope was Fire Alarm Repair. <br> Source: Calgary MyProperty
[[Category:Facilities]]
[[Category:Calgary]]
[[Category:Recreation Centres]]
[[Category:Swimming Pools]]

Latest revision as of 00:29, 13 October 2024

System Specifications
FACP: Edwards EST4
FACP Location: Behind Customer Service
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
Temporal (Alarm)
Date of Last Known Upgrade: 2023
Year Opened: 1983, 2008

Southland Leisure Centre is an indoor leisure centre located at 2000 Southland Drive Southwest, in Calgary, Alberta, Canada. The facility is owned and operated by the City of Calgary. The building opened in 1983, and was renovated in 2008. The fire alarm system was upgraded in 2008, and again in May of 2023.

System Specifications (May 2023-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST4 addressable fire alarm system. The panel is located behind the customer service desk. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. Alert signal coding is 20BPM, followed by temporal for the evacuation signal.

Annunciators[edit | edit source]

There is an Edwards EST4-4ANN annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

The notification appliances were left untouched during the upgrade.

Most notification appliances are Siemens MBDC-6 motor bells (6" gong).
Areas with higher ambient noise levels, such as the pool area, have Siemens MBDC-10 motor bells (10” gong).
There is one Wheelock MB-G6-24 motor bell (6” gong) in the men’s locker room, which was not replaced during the 2008 upgrade.
There is a Siemens SFM24-10 motor bell (10" gong) by the play structure in the pool area as a deficiency replacement.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Edwards SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors in the elevator shaft, around the perimeter of the main lobby, and in some mechanical rooms.
There is an Edwards SIGA-OSD addressable optical smoke detector in the elevator machine room.
All detectors are mounted on Edwards SIGA-SB bases.
There are Edwards SIGA-SD addressable photoelectric duct smoke detectors on several air handling units.
The building is equipped with a sprinkler system.

Modules[edit | edit source]

There are Edwards SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Edwards SIGA-CR addressable relays for elevator recall.

There are Edwards SIGA-IM addressable isolator modules on the SLC.

EOLs[edit | edit source]

There are Siemens EL-300C end-of-line resistor plates on all sprinkler and signal circuits.


System Specifications (2008-May 2023)[edit | edit source]

System Specifications
FACP: Siemens MXL-IQ
FACP Location: Behind Customer Service
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: 20BPM (Alert)
Temporal (Alarm)
Year Installed: 2008

Year of last known upgrade: 2015
Year Decommissioned: 2023

FACP[edit | edit source]

The building was protected by a Siemens MXL-IQ addressable fire alarm system. The panel was located behind the customer service desk. The system ran Siemens' FirePrint addressable protocol, and was configured for two-stage operation. Alert signal coding was 20BPM, followed by temporal in evacuation signal. This panel was replaced due to an issue with the alarm relay contacts.

Annunciators[edit | edit source]

There was a Siemens RCC-3 annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

Most notification appliances were Siemens MBDC-6 motor bells (6" gong).
Areas with higher ambient noise levels, such as the pool area, had Siemens MBDC-10 motor bells (10” gong).
There was one Wheelock MB-G6-24 motor bell (6” gong) in the men’s locker room, which was not replaced during the 2008 upgrade.
There was a Siemens SFM24-10 motor bell (10" gong) by the play structure in the pool area as a deficiency replacement.
All devices remain in use on the current fire alarm system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Siemens MSI-30B addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There was a Siemens “FirePrint” FP-11 addressable multisensor smoke/heat detector in the elevator machine room.

There were Siemens FPT-11 addressable fixed-temperature/rate-of-rise heat detectors in the elevator shaft, around the perimeter of the main lobby, and in some mechanical rooms.

Modules[edit | edit source]

There were Siemens TRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There were Siemens LIM-1 addressable isolator modules on the SLC.

EOLs[edit | edit source]

There are Siemens EL-300C end-of-line resistor plates on all sprinkler and signal circuits.

System Specifications (1983-2008)[edit | edit source]

Please note that these details are unconfirmed.

System Specifications
FACP: Edwards Custom 6500
FACP Location: Behind Reception
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: 20BPM (Alert)
120BPM (Evac)
Strobes Synchronized: N/A
Year Installed: 1983
Year Decommissioned: 2008

FACP[edit | edit source]

The building was protected by an Edwards Custom 6500 conventional fire alarm system. The panel was located behind the reception desk. The system was configured for two-stage operation. The alert signal was 20BPM, followed by 120BPM march time for the evacuation signal.

Notification Appliances[edit | edit source]

All notification appliances were Edwards “Durabel” 6100D vibrating bells (6’ gong).

There was one Wheelock MB-G6-24 motor bell (6" gong) in the mens' locker room as a deficiency replacement. This bell is still in service.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Edwards 270-GAO conventional two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There were likely Edwards 281C conventional 135°F fixed-temperature/rate-of-rise heat detectors in some areas.

EOLs[edit | edit source]

There were Edwards EOL-P1 end-of-line resistor plates on circuits.

Bonus Information[edit | edit source]

For the wave pool warning system, there is an Edwards "Adaptahorn" 874-N5 horn and an Edwards "Adaptabeacon" 110FINB-N5 blue strobe at the back of the pool. The horn is set to a very loud volume, and there's a sign above the two saying "WARNING! Light and buzzer activate. Waves will be on in 10 seconds"

There is a bell gong mounted on a water motor on the play structure water bucket in the pool area. The bell rings when the bucket is about to dump, and increases in speed until the dump occurs.

Permit Information[edit | edit source]

Commercial / Multi Family Project is Issued Permit. Permit issued on 2023-05-25. Project scope was Fire Alarm Repair.