| FACP: Mircom QX-5000 <br /> FACP Location: Main Entrance <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> | | FACP: Mircom FX-2000 w/QX-5000 <br /> FACP Location: Main Entrance <br />System Type: Two-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VFWR (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized: Yes, SS <br />Date of last known Upgrade: N/A <br />Year Opened: 2015 | ||
|} | |} | ||
'''The Rec Room''' is a Canadian chain of entertainment restaurants owned by Cineplex. This particular restaurant is located at 1725 99 Street Northwest, in Edmonton, Alberta, Canada. This was the very first location; it opened in 2015, and the fire alarm system is original. | |||
'''The Rec Room''' is a Canadian chain of entertainment restaurants owned by Cineplex. | ==System Specifications (2015-present)== | ||
==System Specifications== | |||
====FACP==== | ====FACP==== | ||
The building is protected by a Mircom | The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom’s CLIP addressable protocol, and is equipped with the QX-5000 voice evacuation system. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All notification appliances are from System Sensor's "SpectrAlert Advance" line of products. | |||
=====First Floor===== | =====First Floor===== | ||
The notification appliances on the first floor are a mix of System Sensor | The notification appliances on the first floor are a mix of System Sensor SPSWA speaker/strobes (white, wall-mount, set to 70V/15cd) and System Sensor SPWA remote speakers (white, wall-mount, set to 70V). | ||
=====Second Floor/Low Ceilings===== | =====Second Floor/Low Ceilings===== | ||
The notification appliances on the second floor are a mix of System Sensor | The notification appliances on the second floor are a mix of System Sensor SPSCWA speaker/strobes (white, ceiling-mount, set to 70V/15cd) and System Sensor SPCWA remote speakers (white, ceiling-mount, set to 70V). These are also found in low ceiling areas on the first floor. | ||
=====Outdoors===== | =====Outdoors===== | ||
There are a mix of System Sensor | There are a mix of System Sensor SPSCWKA weatherproof speaker/strobes (white, ceiling-mount, set to 70V) and System Sensor SPCWKA weatherproof remote speakers (white, ceiling-mount, set to 70V) outdoors. | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Mircom MS-402AD addressable two-stage single-action pull stations. | All pull stations are Mircom MS-402AD addressable two-stage single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
None noticed. | None noticed. The building is equipped with a sprinkler system. | ||
====Modules==== | ====Modules==== | ||
There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
==== EOLs ==== | |||
There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits. | |||
[[Category:Facilities]] | |||
[[Category:Edmonton]] | |||
[[Category:Entertainment Centres]] |
Latest revision as of 16:20, 14 October 2024
System Specifications |
---|
FACP: Mircom FX-2000 w/QX-5000 FACP Location: Main Entrance System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 70.7VRMS (Audible) 24VFWR (Visual) System Coding: Unknown Strobes Synchronized: Yes, SS Date of last known Upgrade: N/A Year Opened: 2015 |
The Rec Room is a Canadian chain of entertainment restaurants owned by Cineplex. This particular restaurant is located at 1725 99 Street Northwest, in Edmonton, Alberta, Canada. This was the very first location; it opened in 2015, and the fire alarm system is original.
System Specifications (2015-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Mircom’s CLIP addressable protocol, and is equipped with the QX-5000 voice evacuation system. The system is configured for two-stage operation, however the messages and/or tones are unknown at this time.
Notification Appliances[edit | edit source]
All notification appliances are from System Sensor's "SpectrAlert Advance" line of products.
First Floor[edit | edit source]
The notification appliances on the first floor are a mix of System Sensor SPSWA speaker/strobes (white, wall-mount, set to 70V/15cd) and System Sensor SPWA remote speakers (white, wall-mount, set to 70V).
Second Floor/Low Ceilings[edit | edit source]
The notification appliances on the second floor are a mix of System Sensor SPSCWA speaker/strobes (white, ceiling-mount, set to 70V/15cd) and System Sensor SPCWA remote speakers (white, ceiling-mount, set to 70V). These are also found in low ceiling areas on the first floor.
Outdoors[edit | edit source]
There are a mix of System Sensor SPSCWKA weatherproof speaker/strobes (white, ceiling-mount, set to 70V) and System Sensor SPCWKA weatherproof remote speakers (white, ceiling-mount, set to 70V) outdoors.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Mircom MS-402AD addressable two-stage single-action pull stations.
Automatic Detection Devices[edit | edit source]
None noticed. The building is equipped with a sprinkler system.
Modules[edit | edit source]
There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits.