Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

The River Condos: Difference between revisions

From FireAlarmPedia
(NO STROBES IN A 2015 BUILDING!?!?!)
 
No edit summary
 
(One intermediate revision by the same user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST3 <br />FACP Location: Maintenance Office (Main Node) <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS <br />System Coding: Temporal Tone <br>Strobes Synchronized: N/A <br />Date of last known Upgrade: N/A <br />Year Opened: 2015
| FACP: Edwards EST3 <br />FACP Location: Maintenance Office (Main Node) <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS <br />System Coding: Temporal Tone <br>Strobes Synchronized: N/A <br />Date of last known Upgrade: N/A <br />Year Opened: 2015
|}
|}
 
'''The River Condos''' is a condo building located at 135 26 Avenue SW, in Calgary, Alberta, Canada. This page also covers RiverHomes, which is part of the same system. The building was built in 2015, and the fire alarm system is original.
'''The River Condos''' is a condo building located at 135 26 Avenue SW, in Calgary, Alberta, Canada. This page also covers RiverHomes, which is part of the same system. The building was built in 2015, and the fire alarm system is original.
 
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with 4 nodes; Nodes 1 & 2 are located in the maintenance office; nodes 3 and 4 are located in the 16th floor electrical room. Node 5 is located in the main electrical room in RiverHomes. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The evacuation signal is a temporal tone; there is no automated message.
The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with 4 nodes; Nodes 1 & 2 are located in the maintenance office; nodes 3 and 4 are located in the 16th floor electrical room. Node 5 is located in the main electrical room in RiverHomes. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The evacuation signal is a temporal tone; there is no automated message.
 
=====Annunciators=====
=====Annunciators=====
There is an Edwards EST3-6ANN annunciator with an LCDXL1 display in the main entrance vestibule of RiverHomes.
There is an Edwards EST3-6ANN annunciator with an LCDXL1 display in the main entrance vestibule of RiverHomes.
====Notification Appliances====
====Notification Appliances====
Most units and common areas have Edwards “Genesis” GCRF-S7 remote speakers (red, ceiling-mount, FIRE marking, 70V). <br>Some units have Edwards G4R-S7 remote speakers (red, wall-mount, no marking, 70V). <br>Higher-end units have Edwards GC-S7 remote speakers (white, ceiling-mount, no marking, 70V).
Most units and common areas have Edwards “Genesis” GCRF-S7 remote speakers (red, ceiling-mount, FIRE marking, 70V). <br>Some units have Edwards G4R-S7 remote speakers (red, wall-mount, no marking, 70V). <br>Higher-end units have Edwards GC-S7 remote speakers (white, ceiling-mount, no marking, 70V).  
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are EST SIGA-270 addressable single-action pull stations.
All pull stations are EST SIGA-270 addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA2-PS addressable photoelectric smoke detectors throughout most corridors and in all elevator lobbies. <br>There are EST SIGA2-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical rooms and at the top of all elevator shafts. <br>There is an EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detector on the second floor air handling unit. <br>There is an EST SIGA-PS addressable photoelectric smoke detector in one area, likely NOS. <br>All detectors are mounted on EST SIGA-SB bases.
There are EST SIGA2-PS addressable photoelectric smoke detectors throughout most corridors and in all elevator lobbies. <br>There are EST SIGA2-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical rooms and at the top of all elevator shafts. <br>There is an EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detector on the second floor air handling unit. <br>There is an EST SIGA-PS addressable photoelectric smoke detector in one area, likely NOS. <br>All detectors are mounted on EST SIGA-SB bases.
====Modules====
There are EST SIGA-CT2 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br>There are EST SIGA-CR addressable relay modules serving various purposes. <br>There are EST SIGA-IM isolator modules on all SLCs. <br>All in-suite speakers are connected to Edwards 684-1C silence switches.


====Modules====
==== EOLs ====
There are EST SIGA-CT2 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.  <br>There are EST SIGA-CR addressable relay modules serving various purposes.  <br>There are EST SIGA-IM isolator modules on all SLCs.  <br>All in-suite speakers are connected to Edwards 684-1C silence switches.
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.
[[Category:Calgary]]
[[Category:Residential]]

Latest revision as of 16:21, 14 October 2024

System Specifications
FACP: Edwards EST3
FACP Location: Maintenance Office (Main Node)
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS
System Coding: Temporal Tone
Strobes Synchronized: N/A
Date of last known Upgrade: N/A
Year Opened: 2015

The River Condos is a condo building located at 135 26 Avenue SW, in Calgary, Alberta, Canada. This page also covers RiverHomes, which is part of the same system. The building was built in 2015, and the fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with 4 nodes; Nodes 1 & 2 are located in the maintenance office; nodes 3 and 4 are located in the 16th floor electrical room. Node 5 is located in the main electrical room in RiverHomes. The system runs Edwards’ Signature addressable protocol, and is equipped with voice evacuation. The evacuation signal is a temporal tone; there is no automated message.

Annunciators[edit | edit source]

There is an Edwards EST3-6ANN annunciator with an LCDXL1 display in the main entrance vestibule of RiverHomes.

Notification Appliances[edit | edit source]

Most units and common areas have Edwards “Genesis” GCRF-S7 remote speakers (red, ceiling-mount, FIRE marking, 70V).
Some units have Edwards G4R-S7 remote speakers (red, wall-mount, no marking, 70V).
Higher-end units have Edwards GC-S7 remote speakers (white, ceiling-mount, no marking, 70V).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA2-PS addressable photoelectric smoke detectors throughout most corridors and in all elevator lobbies.
There are EST SIGA2-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors in all mechanical rooms and at the top of all elevator shafts.
There is an EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detector on the second floor air handling unit.
There is an EST SIGA-PS addressable photoelectric smoke detector in one area, likely NOS.
All detectors are mounted on EST SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT2 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM isolator modules on all SLCs.
All in-suite speakers are connected to Edwards 684-1C silence switches.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.