Walmart Supercentre (Royal Oak): Difference between revisions

From FireAlarmPedia
m (This is NOT an arena.)
No edit summary
 
(12 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Simplex 4007ES <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: 2021<br />Year Opened: 2003
| FACP: Simplex 4007ES <br /> FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, SignalMaster<br />Date of last known Upgrade: 2021 <br />Year Opened: 2003
|}
|}
'''Walmart''' is a retail outlet chain. This specific location is in Royal Oak in NW calgary. It was built in 2003, but the fire alarm system is not original, it was upgraded in January 2021. Most of the notification appliances are original.
'''Walmart''' is an American chain of supermarkets. They are headquartered in Bentonville, Arkansas, USA. This particular store is located at 8888 Country Hills Boulevard Northwest, in Calgary, Alberta, Canada. The store opened in 2003, and the fire alarm system was upgraded in 2021; only the notification appliances remain original.
==System Specifications (2021-present)==
====FACP====
The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
====Notification Appliances====
The notification appliances are mostly EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount).  


== System Specifications ==
There are also EST G1R-V15 remote strobes (red, wall-mount, 15cd) in the main store area. Throughout the store, the notification appliances are mounted on poles, with two horn/strobes and two remote strobes facing opposite directions.


==== FACP ====
In the McDonald's there is a G1R-HDVM installed in 2019, mounted upside down.
===Initiating Devices===
====Pull Stations====
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
====Automatic Detection Devices====
None noticed, waterflow present.
==== Modules ====
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.


The fire alarm panel is a brand new Simplex 4007ES (4007-9202, platinum cabinet). It was installed in 2021 as the replacement panel for the original EST QuickStart QS1. The cause of the replacement is unknown, but the permit issued for this was "fire alarm upgrades". The panel is located right at the entrance. The system is serviced by Johnson Controls.
==== EOLs ====
There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits.


==== Notification Appliances ====


The notification appliances were kept from the original fire alarm system. They are a mix of EST "Genesis" G1R-HDVM (red, wall, no FIRE) horn/strobes and EST "Genesis" G1R-V75 (red, wall, no FIRE) remote strobes.  Usually there are two horn/strobes and two remote strobes on each opposite side of a pole, though some are on walls. Some have the EST logo and some do not. The McDonald's has a G1R-HDVM installed in 2019 after the remodel, but it's upside down. Most of the notification appliances are original to the store from 2003.
[[File:Royal Oak MCD fail.jpg|thumb|The specific Edwards G1R-HDVM in Question]]


=== Initiating Devices ===
== Former System Specifications (2003-2021) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: EST QuickStart QS1
FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage:24VFWR


==== Pull Stations ====
System Coding: Temporal


The pull stations are all brand new Simplex 4099-9004 addressable single-action T-Bar pull stations with an LED. They were installed in 2021 after the system upgrade.
Strobes Synchronized: Yes, EST<br />Date of last known Upgrade: Early 2010s <br />Year Decommissioned: 2021
|}
====FACP====
The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran EST’s Signature addressable protocol, and the system coding is temporal.
====Notification Appliances====
The notification appliances were mostly EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount).  


==== Automatic Detection Devices ====
There are also EST G1R-V15 remote strobes (red, wall-mount, 15cd) in the main store area.


None noticed so far.
Throughout the store, the notification appliances are mounted on poles, with two horn/strobes and two remote strobes facing opposite directions. These remain in use on the Simplex system.
===Initiating Devices===
====Pull Stations====
All pull stations were EST SIGA-270 addressable single-action pull stations.
====Automatic Detection Devices====
None noticed, waterflow present
==== Modules ====
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.


== Former System Specifications ==
==== EOLs ====
There were Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.


==== FACP ====
== Bonus Information ==
Permit issued for system overhaul on January 21, 2021.
"Fire Alarm Upgade"
== Gallery ==
<gallery>
Royal Oak MCD fail.jpg|The horn/strobe in McDonald's.


The original fire alarm panel was an EST QuickStart QS1, installed in 2003 when the store was built. It had many troubles during the remodel of the McDonald's in 2019. The system got upgraded in 2021 to a Simplex 4007ES.
</gallery>
 
[[Category:Facilities]]
==== Notification Appliances ====
 
The notification appliances were the EST Genesis G1R-HDVM (red, wall, no FIRE) horn/strobes and EST "Genesis" G1R-V75 (red, wall, no FIRE) remote strobes that are still installed today, despite the system upgrade.
 
=== Initiating Devices ===
 
==== Pull Stations ====
 
The pull stations were all EST SIGA-270 addressable pull stations. Most were original from 2003, but there were two from 2011-2013 (EST/GE). These pull stations were replaced when the system was upgraded due to not being compatible with the 4007ES.
 
==== Automatic Detection Devices ====
 
The smoke detectors were EST SIGA-PS photoelectric addressable smoke detectors, original from 2003. These were replaced due to not being compatible with Simplex.
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Calgary]]
[[Category:Retail Stores]]

Latest revision as of 21:16, 14 October 2024

System Specifications
FACP: Simplex 4007ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SignalMaster
Date of last known Upgrade: 2021
Year Opened: 2003

Walmart is an American chain of supermarkets. They are headquartered in Bentonville, Arkansas, USA. This particular store is located at 8888 Country Hills Boulevard Northwest, in Calgary, Alberta, Canada. The store opened in 2003, and the fire alarm system was upgraded in 2021; only the notification appliances remain original.

System Specifications (2021-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

The notification appliances are mostly EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount).

There are also EST G1R-V15 remote strobes (red, wall-mount, 15cd) in the main store area. Throughout the store, the notification appliances are mounted on poles, with two horn/strobes and two remote strobes facing opposite directions.

In the McDonald's there is a G1R-HDVM installed in 2019, mounted upside down.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed, waterflow present.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and signal circuits.


Former System Specifications (2003-2021)[edit | edit source]

System Specifications
FACP: EST QuickStart QS1

FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage:24VFWR

System Coding: Temporal

Strobes Synchronized: Yes, EST
Date of last known Upgrade: Early 2010s
Year Decommissioned: 2021

FACP[edit | edit source]

The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the main entrance vestibule. The system ran EST’s Signature addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

The notification appliances were mostly EST “Genesis” G1R-HDVM horn/strobes (red, wall-mount).

There are also EST G1R-V15 remote strobes (red, wall-mount, 15cd) in the main store area.

Throughout the store, the notification appliances are mounted on poles, with two horn/strobes and two remote strobes facing opposite directions. These remain in use on the Simplex system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed, waterflow present

Modules[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There were Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.

Bonus Information[edit | edit source]

Permit issued for system overhaul on January 21, 2021. "Fire Alarm Upgade"