More actions
(Corrected page with info gathered during the annual inspection. Confirmed system is fully addressable as each device annunciates separately.) |
|||
(2 intermediate revisions by the same user not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Mircom FX-2000 <br />FACP Location: Main Entrance <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: | | FACP: Mircom FX-2000 <br />FACP Location: Main Entrance <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: N/A <br />Date of last known Upgrade: 2010s <br />Year Opened: Mid 1980s | ||
|} | |} | ||
'''McCall Lake Golf Course''' is a golf course owned and operated by the City of Calgary. This page will cover the clubhouse building, located at 1600 32 Avenue Northeast, in Calgary, Alberta, Canada. The building opened in the mid-1980s, and the fire alarm system was upgraded in 1996, with a panel replacement occurring in the late 2000s. | '''McCall Lake Golf Course''' is a golf course owned and operated by the City of Calgary. This page will cover the clubhouse building, located at 1600 32 Avenue Northeast, in Calgary, Alberta, Canada. The building opened in the mid-1980s, and the fire alarm system was upgraded in 1996, with a panel replacement occurring in the late 2000s. | ||
Line 15: | Line 15: | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Simplex MS-301C conventional single-action pull stations | All pull stations are Simplex MS-301C conventional single-action pull stations, wired to Mircom MIX-M501MA addressable monitor modules. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There are Mircom MIX-5251RBA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchen, some washrooms and all mechanical rooms. | There are Mircom MIX-5251RBA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchen, some washrooms and all mechanical rooms. | ||
There is a Mircom MIX-2251BA addressable photoelectric smoke detector at the top of the stairwell. | There is a Mircom MIX-2251BA addressable photoelectric smoke detector at the top of the stairwell. | ||
All detectors are mounted on System Sensor B210LPA bases. | |||
==== EOLs ==== | |||
There are Mircom MP-300 end of line resistor plates on all signal circuits. | |||
[[Category:Calgary]] | |||
[[Category:Golf Courses]] |
Revision as of 12:40, 24 October 2024
System Specifications |
---|
FACP: Mircom FX-2000 FACP Location: Main Entrance System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: N/A Date of last known Upgrade: 2010s Year Opened: Mid 1980s |
McCall Lake Golf Course is a golf course owned and operated by the City of Calgary. This page will cover the clubhouse building, located at 1600 32 Avenue Northeast, in Calgary, Alberta, Canada. The building opened in the mid-1980s, and the fire alarm system was upgraded in 1996, with a panel replacement occurring in the late 2000s.
System Specifications (2000s-present)
FACP
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located at the main entrance. The system runs Mircom’s CLIP addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are Wheelock MB-G6-24 motor bells (6” gong).
Initiating Devices
Pull Stations
All pull stations are Simplex MS-301C conventional single-action pull stations, wired to Mircom MIX-M501MA addressable monitor modules.
Automatic Detection Devices
There are Mircom MIX-5251RBA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the kitchen, some washrooms and all mechanical rooms.
There is a Mircom MIX-2251BA addressable photoelectric smoke detector at the top of the stairwell.
All detectors are mounted on System Sensor B210LPA bases.
EOLs
There are Mircom MP-300 end of line resistor plates on all signal circuits.