(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4007ES <br />FACP Location: Main Entrance <br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 29VDC <br />System Coding: 60BPM (alert) <br> 120BPM March Time (alarm) <br>Strobes Synchronized: Yes, IDNAC <br />Date of last known Upgrade: N/A <br />Year Opened: 2018 |} '''Kids' Stop''' is a daycare and early childhood education program...") |
(Chase you need to drink your own piss.) |
||
| Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Simplex 4007ES <br />FACP Location: Main Entrance <br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 29VDC <br />System Coding: 60BPM (alert) <br> 120BPM March Time (alarm) <br>Strobes Synchronized: Yes, IDNAC <br />Date of last known Upgrade: N/A <br />Year Opened: 2018 | | FACP: Simplex 4007ES<br />FACP Location: Main Entrance<br />System Type: Two-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 29VDC<br />System Coding: 60BPM (alert)<br>120BPM March Time (alarm)<br>Strobes Synchronized: Yes, IDNAC<br />Date of last known Upgrade: N/A<br />Year Opened: 2018 | ||
|} | |} | ||
| Line 14: | Line 14: | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex's IDNet addressable initiating and IDNAC addressable | The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex's IDNet addressable initiating and IDNAC addressable indicating protocols, and is configured for two-stage operation. The alert signal coding is 60BPM, and the alarm signal coding is 120BPM. General alarm timer length is 5 minutes. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
| Line 24: | Line 24: | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are Simplex 4099-9004CA addressable two-stage pull stations. | All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Simplex 4098-9714 addressable photoelectric smoke detectors throughout the building. <br> There is a Simplex 4098-9734 addressable 190°F fixed temperature/rate-of-rise heat detector in the kitchen. <br> All detectors are mounted on Simplex 4098-9792 bases. | There are Simplex "TrueAlarm"4098-9714 addressable photoelectric smoke detectors throughout the building. <br>There is a Simplex 4098-9734 addressable 190°F fixed temperature/rate-of-rise heat detector in the kitchen. <br>All detectors are mounted on Simplex 4098-9792 bases. | ||
==== Modules ==== | ==== Modules ==== | ||
There are Simplex 4090-9002 addressable relay modules for releasing the door holders. <br> There are Simplex 4090-9116 isolator modules on the SLC. | There are Simplex 4090-9002 addressable relay modules for releasing the door holders. <br>There are Simplex 4090-9116 addressable isolator modules on the SLC. | ||
[[Category:Alberta]] | [[Category:Alberta]] | ||
[[Category:Childcare]] | [[Category:Childcare]] | ||
Latest revision as of 16:10, 25 May 2025
| System Specifications |
|---|
| FACP: Simplex 4007ES FACP Location: Main Entrance System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 29VDC System Coding: 60BPM (alert) 120BPM March Time (alarm) Strobes Synchronized: Yes, IDNAC Date of last known Upgrade: N/A Year Opened: 2018 |
Kids' Stop is a daycare and early childhood education program with centres in Okotoks and Calgary. This particular daycare is located at 702 Drake Landing St, Okotoks, Alberta. The centre opened in 2018, and the fire alarm system is original.
System Specifications (2018-present)
FACP
The building is protected by a Simplex 4007ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex's IDNet addressable initiating and IDNAC addressable indicating protocols, and is configured for two-stage operation. The alert signal coding is 60BPM, and the alarm signal coding is 120BPM. General alarm timer length is 5 minutes.
Notification Appliances
All notification appliances are Simplex "TrueAlert ES" 49AV-WRF addressable horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Simplex 4099-9004CA addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Simplex "TrueAlarm"4098-9714 addressable photoelectric smoke detectors throughout the building.
There is a Simplex 4098-9734 addressable 190°F fixed temperature/rate-of-rise heat detector in the kitchen.
All detectors are mounted on Simplex 4098-9792 bases.
Modules
There are Simplex 4090-9002 addressable relay modules for releasing the door holders.
There are Simplex 4090-9116 addressable isolator modules on the SLC.