(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Notifier NFS-320C <br />FACP Location: West Foyer <br />System Type: Two-Stage Addressablae <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: N/A <br />Year Opened: 2014 |} '''New Brighton Child Care''' is a daycare located at 6 New Brighton Heath SE, Calgary, Albert...") |
(I'm an idiot. I added the wrong pull station model to the notes. Corrected and is now accurate!) |
||
| Line 24: | Line 24: | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are Notifier | All pull stations are Notifier N-MPS-2A addressable two-stage single-action pull stations. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
Latest revision as of 17:49, 26 May 2025
| System Specifications |
|---|
| FACP: Notifier NFS-320C FACP Location: West Foyer System Type: Two-Stage Addressablae System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2014 |
New Brighton Child Care is a daycare located at 6 New Brighton Heath SE, Calgary, Alberta. The centre opened in 2014, and the fire alarm system is original.
System Specifications (2014-present)
FACP
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the west foyer. The system runs Notifier's FlashScan addressable protocol, and is configured for two-stage operation. The alert signal is 20BPM, followed by temporal as the alarm signal.
Notification Appliances
All notification appliances are System Sensor "SpectrAlert Advance" P4RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Notifier N-MPS-2A addressable two-stage single-action pull stations.
Automatic Detection Devices
There are Notifier FSP-851A addressable photoelectric smoke detectors in all corridors, stairwells and some rooms.
There are Notifier FST-851A addressable 135°F fixed-temperature heat detectors in the mechanical room, washrooms and kitchen.
All aforementioned detectors but one are mounted on System Sensor B210LPA bases, while the upstairs washroom heat detector is on a System Sensor B224BIA isolator base.
The attic has System Sensor 5604A conventional 190°F fixed-temperature heat detectors, all wired to a single Notifier FMM-1A addressable monitor module.
Modules
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs
There are Notifier EOL-CR end-of-line resistor plates on all signal circuits.