More actions
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: EST QuickStart QS1<br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Temporal<br>Strobes Synchronized: Yes, Genesis Self-Sync<br />Date of last known Upgrade: 2006<br />Most Recent Known Modification: N/A<br />Year Opened: 1981 |} '''4903 50th Ave''' is the address of...") |
No edit summary |
||
| Line 29: | Line 29: | ||
====EOLs==== | ====EOLs==== | ||
There are Edwards EOL-P1 end of line resistor plates on all signal circuits. | There are Edwards EOL-P1 end of line resistor plates on all signal circuits. | ||
[[Category:Office Buildings]] | [[Category:Office Buildings]] | ||
[[Category:Red Deer]] | |||
Latest revision as of 15:06, 24 August 2025
| System Specifications |
|---|
| FACP: EST QuickStart QS1 FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, Genesis Self-Sync Date of last known Upgrade: 2006 Most Recent Known Modification: N/A Year Opened: 1981 |
4903 50th Ave is the address of a professional building in Red Deer, Alberta, Canada. The building was built in 1981, and housed a BMO bank until 2021. The fire alarm system was upgraded in 2006.
System Specifications (2006-present)
FACP
The building is protected by an EST QuickStart QS1 addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs EST's Signature addressable protocol, and the system coding is temporal.
Notification Appliances
All notification appliances are Edwards "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270 addressable single-action pull stations.
Automatic Detection Devices
There are EST SIGA-PS addressable photoelectric smoke detectors at the top of each stairwell, mounted on EST SIGA-SB bases.
Modules
There are EST SIGA-CR addressable relay modules serving various purposes.
EOLs
There are Edwards EOL-P1 end of line resistor plates on all signal circuits.