| Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Simplex 4100ES | | FACP: Simplex 4100ES <br /> FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage:24VDC <br />System Coding: Temporal <br />Strobes Synchronized: Yes, SmartSync<br />Date of last known Upgrade: 2020 | ||
Most Recent Known Modification: N/A<br />Year Opened: 1984, 1998 | |||
|} | |} | ||
'''Safeway''' is a chain of grocery stores. This | '''Safeway Canada''' is a chain of grocery stores. They are owned by Sobeys, and have locations across the country. This particular store is located at 99 Crowfoot Crescent NW Calgary, AB, and was built in 1984 as a Food For Less. It was re-opened in 1997 as Safeway and underwent major renovations in 2000 and 2020. The fire alarm system was installed during the renovation. | ||
==System Specifications (2020-present)== | |||
====FACP==== | |||
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with InfoAlarm Command Center. The CPU (4100-9212) was replaced in 2020, as the system was converted to be fully addressable when the renovations happened. The cabinet was kept, and was installed in 2015, as the system was conventional prior to renovations. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal. | |||
====Notification Appliances==== | |||
All of the notification appliances are from Simplex’s “TrueAlert” line of products. | |||
Most notification appliances are Simplex 4906-9127 horn/strobes (red, wall-mount, set to 15cd). | |||
In the low ceiling area, there is a Simplex 4906-9101 remote strobe (red, wall-mount, set to 15cd). | |||
For exterior notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount, set to 75cd) outside the main entrance. | |||
==== | All of these horn/strobes and strobes were installed in spring-summer 2020, replacing EST “PowerSaver Integrity” horn/strobes, see below for more information. | ||
===Initiating Devices=== | |||
====Pull Stations==== | |||
All of the pull stations are Simplex 4099-9004 addressable single-action pull stations. | |||
====Automatic Detection Devices==== | |||
There are most likely Simplex 4098-9734 addressable fixed/rate-of-rise heat detectors installed, mounted on Simplex 4098-9792 bases. The storefront is protected by waterflow. | |||
====Modules==== | |||
There are Simplex 4090-9001 addressable monitor modules monitoring the system's sprinkler flow switches and tamper switches. | |||
==== EOLs ==== | |||
There are Simplex 2081-9040C end-of-line resistors on all sprinkler and signal circuits. | |||
==Former System Specifications (1990-2020)== | |||
{| style="float:right;border:2px solid black" | |||
|- | |||
!System Specifications | |||
|- | |||
| | |||
|- | |||
|FACP: Simplex 4100ES | |||
FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage:24VDC <br> System Coding: Temporal <br /> Strobes Synchronized: Yes, Self-Sync <br />Year Installed: 1990 (FACP 2015) | |||
Most Recent Known Modification: 2018 (Pull Stations)<br /> Year Decomissioned: 2020 | |||
|} | |||
====FACP ==== | |||
The building was protected by a Simplex 4100ES conventional fire alarm system. The panel was located in the main entrance vestibule, and was equipped with InfoAlarm Command Center. The system coding was temporal. | |||
==== FACP ==== | |||
The | |||
=== Initiating Devices === | The 4100ES replaced an Edwards 6616 in 2015 after a main board failure. | ||
====Notification Appliances==== | |||
All notification appliances were EST “PowerSaver Integrity” 757H-15PS horn/strobes (red, wall-mount, 15cd). They were installed in 2000 following the conversion to Safeway. | |||
===Initiating Devices=== | |||
====Pull Stations==== | |||
Most pull stations were Tyco/Grinnell MS-401GR conventional pull stations. | |||
At the east entrance, there were two Edwards 275-C111 conventional pull stations, installed in 1990. | |||
The backroom had one Edwards 270-SPO conventional pull station. | |||
The following pull stations were installed as deficiency replacements: | |||
* Simplex MS-301C conventional pull station at main entrance | |||
*Mircom MS-401 conventional pull station at backroom doors near Aisle 6, replaced Tyco/Grinnell MS-401 in 2018 | |||
[[Category: | *Tyco/Grinnell MS-401GR by juice, replaced Notifier MPS-950B in 2018 | ||
====Automatic Detection Devices ==== | |||
There were Edwards 281C rate-of-rise/fixed-temperature heat detectors in some areas. There was also a sprinkler system with waterflow detection. | |||
==== EOLs ==== | |||
There were Simplex 2081-9040C end-of-line resistors on all circuits. | |||
[[Category:Simplex]] | |||
[[Category:Calgary]] | |||
[[Category:Retail Stores]] | |||
Latest revision as of 14:20, 21 December 2025
| System Specifications |
|---|
| FACP: Simplex 4100ES FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage:24VDC System Coding: Temporal Strobes Synchronized: Yes, SmartSync Date of last known Upgrade: 2020 Most Recent Known Modification: N/A |
Safeway Canada is a chain of grocery stores. They are owned by Sobeys, and have locations across the country. This particular store is located at 99 Crowfoot Crescent NW Calgary, AB, and was built in 1984 as a Food For Less. It was re-opened in 1997 as Safeway and underwent major renovations in 2000 and 2020. The fire alarm system was installed during the renovation.
System Specifications (2020-present)
FACP
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule, and is equipped with InfoAlarm Command Center. The CPU (4100-9212) was replaced in 2020, as the system was converted to be fully addressable when the renovations happened. The cabinet was kept, and was installed in 2015, as the system was conventional prior to renovations. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
Notification Appliances
All of the notification appliances are from Simplex’s “TrueAlert” line of products.
Most notification appliances are Simplex 4906-9127 horn/strobes (red, wall-mount, set to 15cd).
In the low ceiling area, there is a Simplex 4906-9101 remote strobe (red, wall-mount, set to 15cd).
For exterior notification, there is a Simplex 4906-9105 weatherproof remote strobe (red, wall-mount, set to 75cd) outside the main entrance.
All of these horn/strobes and strobes were installed in spring-summer 2020, replacing EST “PowerSaver Integrity” horn/strobes, see below for more information.
Initiating Devices
Pull Stations
All of the pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices
There are most likely Simplex 4098-9734 addressable fixed/rate-of-rise heat detectors installed, mounted on Simplex 4098-9792 bases. The storefront is protected by waterflow.
Modules
There are Simplex 4090-9001 addressable monitor modules monitoring the system's sprinkler flow switches and tamper switches.
EOLs
There are Simplex 2081-9040C end-of-line resistors on all sprinkler and signal circuits.
Former System Specifications (1990-2020)
| System Specifications |
|---|
| FACP: Simplex 4100ES
FACP Location: Main Entrance Vestibule Most Recent Known Modification: 2018 (Pull Stations) |
FACP
The building was protected by a Simplex 4100ES conventional fire alarm system. The panel was located in the main entrance vestibule, and was equipped with InfoAlarm Command Center. The system coding was temporal.
The 4100ES replaced an Edwards 6616 in 2015 after a main board failure.
Notification Appliances
All notification appliances were EST “PowerSaver Integrity” 757H-15PS horn/strobes (red, wall-mount, 15cd). They were installed in 2000 following the conversion to Safeway.
Initiating Devices
Pull Stations
Most pull stations were Tyco/Grinnell MS-401GR conventional pull stations.
At the east entrance, there were two Edwards 275-C111 conventional pull stations, installed in 1990.
The backroom had one Edwards 270-SPO conventional pull station.
The following pull stations were installed as deficiency replacements:
- Simplex MS-301C conventional pull station at main entrance
- Mircom MS-401 conventional pull station at backroom doors near Aisle 6, replaced Tyco/Grinnell MS-401 in 2018
- Tyco/Grinnell MS-401GR by juice, replaced Notifier MPS-950B in 2018
Automatic Detection Devices
There were Edwards 281C rate-of-rise/fixed-temperature heat detectors in some areas. There was also a sprinkler system with waterflow detection.
EOLs
There were Simplex 2081-9040C end-of-line resistors on all circuits.