University of Central Florida (Student Union): Difference between revisions

From FireAlarmPedia
No edit summary
No edit summary
 
Line 7: Line 7:
| FACP: Simplex 4100U <br /> FACP Location: Behind Front Desk <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized: Partially <br />Date of last known Upgrade: 2000s <br />Year Opened: 1993, 1997
| FACP: Simplex 4100U <br /> FACP Location: Behind Front Desk <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized: Partially <br />Date of last known Upgrade: 2000s <br />Year Opened: 1993, 1997
|}
|}
 
The '''University of Central Florida''' is a large private university in Orlando, Florida, USA. This page will cover the Student Union building. The building opened in 1993, and was expanded in 1997. The fire alarm system is partially original.
The '''University of Central Florida''' is a large private university in Orlando, Florida, USA. This page will cover the Student Union building. The building opened in 1993, and was expanded in 1997. The fire alarm system is partially original.
 
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located behind the main desk. The system runs Simplex’s MAPNET II addressable protocol, and is equipped with voice evacuation. The evac messages and/or tones are unknown at this time.
The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located behind the main desk. The system runs Simplex’s MAPNET II addressable protocol, and is equipped with voice evacuation. The evac messages and/or tones are unknown at this time.
 
====Notification Appliances====
====Notification Appliances====
=====1993 Portion=====
=====1993 Portion=====
Line 19: Line 16:
=====1997 Portion=====
=====1997 Portion=====
All notification appliances are Simplex “TrueAlert” 4906-9151 speaker/strobes (red, wall-mount, set to 110cd).
All notification appliances are Simplex “TrueAlert” 4906-9151 speaker/strobes (red, wall-mount, set to 110cd).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
Line 26: Line 22:
=====1997 Portion=====
=====1997 Portion=====
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
The 1993 portion of the building has Simplex “TrueAlarm” 4098-9716 addressable ionization smoke detectors mounted on Simplex 4098-9781 bases. The 1996 portion and some areas of the 1993 portion have Simplex 4098-9714 addressable photoelectric smoke detectors mounted on Simplex 4098-9792 addressable bases. There is a Simplex 4098-9733 addressable fixed/rate-of-rise heat detector above the restaurant, mounted on a Simplex 4098-9792 addressable base.
The 1993 portion of the building has Simplex “TrueAlarm” 4098-9716 addressable ionization smoke detectors mounted on Simplex 4098-9781 bases. The 1996 portion and some areas of the 1993 portion have Simplex 4098-9714 addressable photoelectric smoke detectors mounted on Simplex 4098-9792 addressable bases. There is a Simplex 4098-9733 addressable fixed/rate-of-rise heat detector above the restaurant, mounted on a Simplex 4098-9792 addressable base.
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Florida]]
[[Category:Post-Secondary]]

Latest revision as of 10:28, 28 May 2024

System Specifications
FACP: Simplex 4100U
FACP Location: Behind Front Desk
System Type: Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Unknown
Strobes Synchronized: Partially
Date of last known Upgrade: 2000s
Year Opened: 1993, 1997

The University of Central Florida is a large private university in Orlando, Florida, USA. This page will cover the Student Union building. The building opened in 1993, and was expanded in 1997. The fire alarm system is partially original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4100U addressable fire alarm system. The panel is located behind the main desk. The system runs Simplex’s MAPNET II addressable protocol, and is equipped with voice evacuation. The evac messages and/or tones are unknown at this time.

Notification Appliances[edit | edit source]

1993 Portion[edit | edit source]

All notification appliances are Simplex 4903-9254 speaker/strobes (red, wall-mount, 110cd).

1997 Portion[edit | edit source]

All notification appliances are Simplex “TrueAlert” 4906-9151 speaker/strobes (red, wall-mount, set to 110cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

1993 Portion[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

1997 Portion[edit | edit source]

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

The 1993 portion of the building has Simplex “TrueAlarm” 4098-9716 addressable ionization smoke detectors mounted on Simplex 4098-9781 bases. The 1996 portion and some areas of the 1993 portion have Simplex 4098-9714 addressable photoelectric smoke detectors mounted on Simplex 4098-9792 addressable bases. There is a Simplex 4098-9733 addressable fixed/rate-of-rise heat detector above the restaurant, mounted on a Simplex 4098-9792 addressable base.