Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Foothills Medical Centre: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3 <br />FACP Location: Various <br />System Type: Hybrid-Addressable <br /...")
 
mNo edit summary
 
(One intermediate revision by the same user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST3 <br />FACP Location: Various <br />System Type: Hybrid-Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70VRMS (audible) <br> 24VDC (visual) <br />System Coding: Strobes Only (Alert) <br> TBA (Alarm) <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2021 <br />Year Opened: 1966
| FACP: Edwards EST3 <br />FACP Location: Various <br />System Type: Two-Stage Hybrid-Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70VRMS (audible) <br> 24VDC (visual) <br />System Coding: Strobes Only (Alert) <br> TBA (Alarm) <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2021 <br />Year Opened: 1966
|}
|}
'''Foothills Medical Centre''' is the largest hospital in Alberta. It is located at 1403 29 St NW, Calgary, Alberta. It serves southern Alberta, British Columbia and Saskatchewan. The hospital opened in 1966, and was expanded in 2006 and 2010. The fire alarm system was upgraded in 1997, and has been networked as the building expanded.
'''Foothills Medical Centre''' is the largest hospital in Alberta. It is located at 1403 29 St NW, Calgary, Alberta. It serves southern Alberta, British Columbia and Saskatchewan. The hospital opened in 1966, and was expanded in 2006 and 2010. The fire alarm system was upgraded in 1997, and has been networked as the building expanded.
== System Specifications (1997-present) ==
== System Specifications (1997-present) ==
*Please note that these system specifications are from the main building only.
*Please note that these system specifications are from the main building only.
==== FACP ====
==== FACP ====
The buildings are protected by an Edwards EST3 hybrid-addressable fire alarm system. There are many nodes, and they are located in electrical rooms throughout the building. The main node is located in the security office. The system runs Edwards’ Signature addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The alert signal is strobes only (no audible alarm), followed by the alarm signal, to be confirmed.  
The buildings are protected by an Edwards EST3 hybrid-addressable fire alarm system. There are many nodes, and they are located in electrical rooms throughout the building. The main node is located in the security office. The system runs Edwards’ Signature addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The alert signal is strobes only (no audible alarm), followed by the alarm signal, to be confirmed.  
===== Booster Panels =====
===== Booster Panels =====
There are Edwards booster panels in each electrical room, model to be confirmed.
There are Edwards booster panels in each electrical room, model to be confirmed.
===== Annunciators =====
===== Annunciators =====
There are Edwards EST 3-LCDANN annunciators at each nurse’s station.
There are Edwards EST 3-LCDANN annunciators at each nurse’s station.
==== Notification Appliances ====
==== Notification Appliances ====
Most notification appliances are EST “Integrity” 965-1A-8SW speakers (white, ceiling-mount, 70V, 8”), also installed in units. <br> Areas requiring more audible coverage have EST 965-3A-8SW speaker/strobes (white, ceiling-mount, 30cd, 70V, 8”). <br> Some floors have EST “Genesis” GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, set to 30cd). <br> The units on the aforementioned floors have EST GCF-S7 speakers (white, ceiling-mount, FIRE marking).
Most notification appliances are EST “Integrity” 965-1A-8SW speakers (white, ceiling-mount, 70V, 8”), also installed in units. <br> Areas requiring more audible coverage have EST 965-3A-8SW speaker/strobes (white, ceiling-mount, 30cd, 70V, 8”). <br> Some floors have EST “Genesis” GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, set to 30cd). <br> The units on the aforementioned floors have EST GCF-S7 speakers (white, ceiling-mount, FIRE marking).
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
Most pull stations are EST SIGA-270P addressable two-stage pull stations. <br> The sixth floor has Edwards 270-GAO conventional two-stage pull stations.
Most pull stations are EST SIGA-270P addressable two-stage pull stations. <br> The sixth floor has Edwards 270-GAO conventional two-stage pull stations.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There are EST SIGA-PS addressable photoelectric smoke detectors throughout. <br> Certain areas have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors. <br> The following detectors were installed as deficiency replacements:
* EST SIGA2-PS addressable photoelectric smoke detectors


There are EST SIGA-PS addressable photoelectric smoke detectors throughout. <br> Certain areas have EST SIGA-HRS addressable  135°F fixed-temperature/rate-of-rise heat detectors. <br> The following detectors were installed as deficiency replacements:
*EST SIGA2-PS addressable photoelectric smoke detectors
*Edwards SIGA-OSD addressable optical smoke detectors
*Edwards SIGA-OSD addressable optical smoke detectors
*Edwards SIGA-PD addressable photoelectric smoke detectors
*Edwards SIGA-PD addressable photoelectric smoke detectors
*Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors
*Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors
<br> All above detectors are mounted on EST SIGA-SB4 bases. <br> The 6th floor has Edwards EC30U-3 conventional photoelectric smoke detectors.
All above detectors are mounted on EST SIGA-SB4 bases.


The 6th floor has Edwards EC30U-3 conventional photoelectric smoke detectors.
==== Modules ====
==== Modules ====
There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There are EST SIGA-CR addressable relays serving various purposes.
There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches. <br> There are EST SIGA-CR addressable relays serving various purposes.
==== EOLs ====
==== EOLs ====
 
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits, and 6th floor conventional zones.
There are Edwards EOL-P1 end-of-line resistors on the NACs and 6th floor conventional zones.
 
[[Category:Healthcare]]
[[Category:Healthcare]]
[[Category:Calgary]]
[[Category:Calgary]]

Latest revision as of 00:49, 26 July 2024

System Specifications
FACP: Edwards EST3
FACP Location: Various
System Type: Two-Stage Hybrid-Addressable
System Line Voltage: 120VAC
NAC Voltage: 70VRMS (audible)
24VDC (visual)
System Coding: Strobes Only (Alert)
TBA (Alarm)
Strobes Synchronized: Yes, EST
Date of last known Upgrade: 2021
Year Opened: 1966

Foothills Medical Centre is the largest hospital in Alberta. It is located at 1403 29 St NW, Calgary, Alberta. It serves southern Alberta, British Columbia and Saskatchewan. The hospital opened in 1966, and was expanded in 2006 and 2010. The fire alarm system was upgraded in 1997, and has been networked as the building expanded.

System Specifications (1997-present)[edit | edit source]

  • Please note that these system specifications are from the main building only.

FACP[edit | edit source]

The buildings are protected by an Edwards EST3 hybrid-addressable fire alarm system. There are many nodes, and they are located in electrical rooms throughout the building. The main node is located in the security office. The system runs Edwards’ Signature addressable protocol, and is equipped with voice-evacuation. The system is configured for two-stage operation. The alert signal is strobes only (no audible alarm), followed by the alarm signal, to be confirmed.

Booster Panels[edit | edit source]

There are Edwards booster panels in each electrical room, model to be confirmed.

Annunciators[edit | edit source]

There are Edwards EST 3-LCDANN annunciators at each nurse’s station.

Notification Appliances[edit | edit source]

Most notification appliances are EST “Integrity” 965-1A-8SW speakers (white, ceiling-mount, 70V, 8”), also installed in units.
Areas requiring more audible coverage have EST 965-3A-8SW speaker/strobes (white, ceiling-mount, 30cd, 70V, 8”).
Some floors have EST “Genesis” GCF-S7VM speaker/strobes (white, ceiling-mount, FIRE marking, set to 30cd).
The units on the aforementioned floors have EST GCF-S7 speakers (white, ceiling-mount, FIRE marking).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

Most pull stations are EST SIGA-270P addressable two-stage pull stations.
The sixth floor has Edwards 270-GAO conventional two-stage pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS addressable photoelectric smoke detectors throughout.
Certain areas have EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.
The following detectors were installed as deficiency replacements:

  • EST SIGA2-PS addressable photoelectric smoke detectors
  • Edwards SIGA-OSD addressable optical smoke detectors
  • Edwards SIGA-PD addressable photoelectric smoke detectors
  • Edwards SIGA-HRD addressable 135°F fixed-temperature/rate-of-rise heat detectors

All above detectors are mounted on EST SIGA-SB4 bases.

The 6th floor has Edwards EC30U-3 conventional photoelectric smoke detectors.

Modules[edit | edit source]

There are EST SIGA-CT2 addressable dual-input monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relays serving various purposes.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits, and 6th floor conventional zones.