Toronto Pearson International Airport: Difference between revisions

From FireAlarmPedia
No edit summary
mNo edit summary
 
(2 intermediate revisions by the same user not shown)
Line 6: Line 6:
|-
|-
| FACP: Simplex 4100ES
| FACP: Simplex 4100ES
FACP Location: Multiple, unknown<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage: Directly to IED amp/70.7VRMS (audible) 24VDC (visual)
FACP Location: Multiple, unknown<br />System Type: Two-Stage Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage: Directly to IED amp/70.7VRMS (audible) 24VDC (visual)


System Coding: TBA
System Coding: TBA
Line 12: Line 12:
Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: 2021 <br />Year Opened: 2003
Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: 2021 <br />Year Opened: 2003
|}
|}
'''Toronto Pearson International Airport''' is the largest airport in Canada. It is located iat 6301 Silver Dart Drive in Mississauga, Ontario, and it serves the city of Toronto, along with most of Southern Ontario. Terminal 1 was built in 2003, but the fire alarm system was replaced in 2021.
'''Toronto Pearson International Airport''' is the largest airport in Canada. It is located iat 6301 Silver Dart Drive in Mississauga, Ontario, and it serves the city of Toronto, along with most of Southern Ontario. Terminal 1 was built in 2003, and Terminal 3 was built in 1991. The fire alarm system was upgraded in 2021.
==System Specifications (2021-present) ==
==System Specifications (2021-present) ==
====FACP====
====FACP====
The airport is protected by a Simplex 4100ES addressable fire alarm system. The panel locations are unknown. The system runs Simplex’s IDNet addressable protocol, is two-stage, and likely does temporal and a custom message in alarm.
The airport is protected by a Simplex 4100ES addressable fire alarm system. The panel locations are unknown, and are part of an airport-wide network. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the tones and/or messages are unknown at this time.
====Notification Appliances====
====Notification Appliances====
The main notification appliances are Simplex “TrueAlert” 4906-9103 remote strobes (white, wall-mount, multi-candela, SmartSync), likely set to 75 candela. Areas with lower ceilings have Simplex “TrueAlert” 4906-9104 remote strobes (white, ceiling-mount, multi-candela, SmartSync), likely set to 75 candela. Some of the strobes have bilingual lettering on them. The restrooms and some other areas have Siemens SET-CW speakers (white, ceiling-mount), left over. In the main terminal, the audio for the system goes through the PA system. The PA speakers consist of Arnscott C81-708-11 8" coaxial ceiling speakers (round baffle) in the main terminal, Arnscott C41-704-15 5" coaxial ceiling speakers in low ceilings (round baffle), and GAP-15T 15 watt paging horn speakers. There is also one Arnscott 4HV-870 vandal-resistant horn speaker.
The main notification appliances are Simplex “TrueAlert” 4906-9103 remote strobes (white, wall-mount, multi-candela, SmartSync), likely set to 75 candela.  
 
Areas with lower ceilings have Simplex “TrueAlert” 4906-9104 remote strobes (white, ceiling-mount, multi-candela, SmartSync), likely set to 75 candela.
 
Some of the strobes have bilingual lettering on them.  
 
The restrooms and some other areas have Siemens SET-CW speakers (white, ceiling-mount), left over.  
 
In the main terminal, the audio for the system goes through the PA system.  
 
The PA speakers consist of Arnscott C81-708-11 8" coaxial ceiling speakers (round baffle) in the main terminal, Arnscott C41-704-15 5" coaxial ceiling speakers in low ceilings (round baffle), and GAP-15T 15 watt paging horn speakers.  
 
There is also one Arnscott 4HV-870 vandal-resistant horn speaker.
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Simplex 4099-9008CAB IDNet addressable two-stage single-action pull stations. These have a MagLock button, and have an additional set of normally closed contacts.
All pull stations are Simplex 4099-9008CAB IDNet addressable two-stage single-action pull stations. These have a MagLock button, and have an additional set of normally closed contacts.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Simplex 4098-9714 IDNet addressable photoelectric smoke detectors throughout the facility.
There are Simplex 4098-9714 IDNet addressable photoelectric smoke detectors throughout the facility, mounted on Simplex 4098-9792 bases.
==System Specifications (former system) (2003-2021) ==
==== Modules ====
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
There are Simplex 4090-9002 addressable relay modules serving various purposes.
 
There are Simplex 4090-9116 isolator modules on each SLC.
==== EOLs ====
There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and strobe circuits.
 
== System Specifications (Terminal 3) ==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Simplex 4100ES
FACP Location: Multiple, unknown<br />System Type: Two-Stage Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage: Directly to IED amp/70.7VRMS (audible) 24VDC (visual) <br> System Coding: TBA  <br />Date of last known Upgrade: 2021 <br />Year Opened: 1991
|}
 
==== FACP ====
The airport is protected by a Simplex 4100ES addressable fire alarm system. The panel locations are unknown, and are part of an airport-wide network. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the tones and/or messages are unknown at this time.
====Notification Appliances====
All notification appliances are Arnscott ASAL81G11W 8" speakers (white, ceiling-mount, square, 8").
 
=== Initiating Devices ===
 
====Pull Stations====
All pull stations are Simplex 4099-9004CA addressable two-stage pull stations.
 
====Automatic Detection Devices====
There are Simplex 4098-9714 IDNet addressable photoelectric smoke detectors throughout the facility, mounted on Simplex 4098-9792 bases.
==== Modules ====
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
There are Simplex 4090-9002 addressable relay modules serving various purposes.
 
There are Simplex 4090-9116 isolator modules on each SLC.
==== EOLs ====
There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler circuits.
==System Specifications (former system, Main Terminal) (2003-2021) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 34: Line 86:
|}
|}
====FACP====
====FACP====
The airport was protected by a Siemens MXLV addressable fire alarm system. The panel locations are unknown, but the size and age of the terminal suggest it was an MXLV. The system ran Siemens' FirePrint addressable protocol. This system was replaced in 2021.
The airport was protected by a Siemens MXLV addressable fire alarm system. The panel locations are unknown, but the size and age of the terminal suggest it was an MXLV. The system ran Siemens' FirePrint addressable protocol, and was equipped with voice-evacuation. The system was configured for two-stage operation. There were messages for both stages.
====Notification Appliances====
====Notification Appliances====
There were Siemens CU-MCS bilingual strobes throughout the terminal. The restrooms had Siemens SET-CW speakers (white, 70V). These speakers are still in use on the Simplex system. In the main terminal, the audio for the system went through the Arnscott PA speakers.
There were Siemens CU-MCS bilingual strobes throughout the terminal.  
 
The restrooms had Siemens SET-CW speakers (white, 70V). These speakers are still in use on the Simplex system.  
 
In the main terminal, the audio for the system went through the Arnscott PA speakers.
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations were Siemens MSI-30BC addressable two-stage single-action pull stations. Most of these were replaced during the upgrade, but some can still be found in the gate hallways, however they are likely decommissioned, as the Simplex panel cannot operate them. Thus, it may confuse people.
All pull stations were Siemens MSI-30BC addressable two-stage single-action pull stations. Most of these were replaced during the upgrade, but some can still be found in the gate hallways, however they are likely decommissioned, as the Simplex panel cannot operate them.  
====Automatic Detection Devices====
====Automatic Detection Devices====
There were Siemens FirePrint FP11 multisensor smoke/heat detectors throughout the terminal. All were replaced due to not being compatible with the new Simplex system.
There were Siemens FP-11 multisensor smoke/heat detectors throughout the terminal.  
==== Modules ====
There were Siemens TRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches.
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Ontario]]
[[Category:Ontario]]
[[Category:Airports]]
[[Category:Airports]]

Latest revision as of 21:15, 29 July 2024

System Specifications
FACP: Simplex 4100ES

FACP Location: Multiple, unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: Directly to IED amp/70.7VRMS (audible) 24VDC (visual)

System Coding: TBA

Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2021
Year Opened: 2003

Toronto Pearson International Airport is the largest airport in Canada. It is located iat 6301 Silver Dart Drive in Mississauga, Ontario, and it serves the city of Toronto, along with most of Southern Ontario. Terminal 1 was built in 2003, and Terminal 3 was built in 1991. The fire alarm system was upgraded in 2021.

System Specifications (2021-present)[edit | edit source]

FACP[edit | edit source]

The airport is protected by a Simplex 4100ES addressable fire alarm system. The panel locations are unknown, and are part of an airport-wide network. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the tones and/or messages are unknown at this time.

Notification Appliances[edit | edit source]

The main notification appliances are Simplex “TrueAlert” 4906-9103 remote strobes (white, wall-mount, multi-candela, SmartSync), likely set to 75 candela.

Areas with lower ceilings have Simplex “TrueAlert” 4906-9104 remote strobes (white, ceiling-mount, multi-candela, SmartSync), likely set to 75 candela.

Some of the strobes have bilingual lettering on them.

The restrooms and some other areas have Siemens SET-CW speakers (white, ceiling-mount), left over.

In the main terminal, the audio for the system goes through the PA system.

The PA speakers consist of Arnscott C81-708-11 8" coaxial ceiling speakers (round baffle) in the main terminal, Arnscott C41-704-15 5" coaxial ceiling speakers in low ceilings (round baffle), and GAP-15T 15 watt paging horn speakers.

There is also one Arnscott 4HV-870 vandal-resistant horn speaker.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9008CAB IDNet addressable two-stage single-action pull stations. These have a MagLock button, and have an additional set of normally closed contacts.

Automatic Detection Devices[edit | edit source]

There are Simplex 4098-9714 IDNet addressable photoelectric smoke detectors throughout the facility, mounted on Simplex 4098-9792 bases.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Simplex 4090-9002 addressable relay modules serving various purposes.

There are Simplex 4090-9116 isolator modules on each SLC.

EOLs[edit | edit source]

There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler and strobe circuits.

System Specifications (Terminal 3)[edit | edit source]

System Specifications
FACP: Simplex 4100ES

FACP Location: Multiple, unknown
System Type: Two-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: Directly to IED amp/70.7VRMS (audible) 24VDC (visual)
System Coding: TBA
Date of last known Upgrade: 2021
Year Opened: 1991

FACP[edit | edit source]

The airport is protected by a Simplex 4100ES addressable fire alarm system. The panel locations are unknown, and are part of an airport-wide network. The system runs Simplex’s IDNet addressable protocol, and is equipped with voice evacuation. The system is configured for two-stage operation, however the tones and/or messages are unknown at this time.

Notification Appliances[edit | edit source]

All notification appliances are Arnscott ASAL81G11W 8" speakers (white, ceiling-mount, square, 8").

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9004CA addressable two-stage pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex 4098-9714 IDNet addressable photoelectric smoke detectors throughout the facility, mounted on Simplex 4098-9792 bases.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Simplex 4090-9002 addressable relay modules serving various purposes.

There are Simplex 4090-9116 isolator modules on each SLC.

EOLs[edit | edit source]

There are Simplex 2081-9040C end-of-line resistor plates on all sprinkler circuits.

System Specifications (former system, Main Terminal) (2003-2021)[edit | edit source]

System Specifications
FACP: Siemens MXLV

FACP Location: Unknown
System Type:Addressable
System Line Voltage: 120VAC
NAC Voltage:70.7VRMS/IED amp (audible) 24VDC(visual)
Date of last known Upgrade: 2003?
Year Decomissioned: 2021

FACP[edit | edit source]

The airport was protected by a Siemens MXLV addressable fire alarm system. The panel locations are unknown, but the size and age of the terminal suggest it was an MXLV. The system ran Siemens' FirePrint addressable protocol, and was equipped with voice-evacuation. The system was configured for two-stage operation. There were messages for both stages.

Notification Appliances[edit | edit source]

There were Siemens CU-MCS bilingual strobes throughout the terminal.

The restrooms had Siemens SET-CW speakers (white, 70V). These speakers are still in use on the Simplex system.

In the main terminal, the audio for the system went through the Arnscott PA speakers.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Siemens MSI-30BC addressable two-stage single-action pull stations. Most of these were replaced during the upgrade, but some can still be found in the gate hallways, however they are likely decommissioned, as the Simplex panel cannot operate them.

Automatic Detection Devices[edit | edit source]

There were Siemens FP-11 multisensor smoke/heat detectors throughout the terminal.

Modules[edit | edit source]

There were Siemens TRI-M addressable monitor modules supervising the sprinkler system's tamper and flow switches.