Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

École Secondaire Beaumont Composite High School: Difference between revisions

From FireAlarmPedia
(New system being added!)
(AND THAT IS ALL! Normal activity may resume.)
 
(2 intermediate revisions by the same user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Notifier NFS2-3030C <br />FACP Location: Custodian's Office <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST & Wheelock <br />Date of last known Upgrade: 2021 <br />Year Opened: 1988
| FACP: Notifier NFS2-3030C <br />FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC<br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST & Wheelock <br />Date of last known Upgrade: 2021 <br />Year Opened: 1988
|}
|}
'''École Secondaire Beaumont Composite High School''' is a high school located at 5417 43 Ave, Beaumont, AB. It teaches grades 10 to 12, is a bilingual school and has an enrollment of 980 students. It is part of Black Gold Regional Schools district. It was built in 1988, and had a major renovation in 2003. A new wing was constructed in 2021, and the fire alarm system was upgraded following that extension.
== System Specifications (2021-present) ==
==== FACP ====
The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the custodian's office. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
===== Annunciators =====
There is a Notifier LCD-160 LCD annunciator in the main entrance vestibule.
==== Notification Appliances ====
All notification appliances in the main school are Edwards MB10-24 motor bells (10" gong) on EST "Integrity" 403-5A-R strobe plates (15cd), leftover from the previous system.
The 2021 expansion has Notifier KMS-10-24A motor bells (10" gong) mounted on Wheelock RSSP-24MCW strobe plates (red, set to 15cd).
There are System Sensor "L-Series" SCRLA-E remote strobes (red, ceiling-mount, English only, set to 15cd) in the annex to the main school and in each expansion washroom.
=== Initiating Devices ===
==== Pull Stations ====
All pull stations except for the gymnasium are Notifier NBG-12LX addressable dual-action pull stations.
The gymnasium has Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.
==== Automatic Detection Devices ====
There are Notifier FSP-951A addressable photoelectric smoke detectors in all stairwells and by each set of fire doors.
All offices, storage rooms and other rooms have Notifier FST-951RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.
All detectors are mounted on System Sensor B300A-6 bases.
==== Modules ====
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules for fire door closing and HVAC shutdown.
==== EOLs ====
There are Notifier EOL-CR end-of-line resistors on all sprinkler and signal circuits in the expansion.


'''École Secondaire Beaumont Composite High School''' is a high school located at 5417 43 Ave, Beaumont, AB. It teaches grades 10 to 12, is a bilingual school and has an enrollment of 980 students. It is part of Black Gold Regional Schools district. It was built in 1988, and had a major renovation in 2003. A new wing was constructed in 2021, and the fire alarm system was upgraded following that extension.
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits for the main school.
== Former System Specifications (2003-2021) ==
== Former System Specifications (2003-2021) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 18: Line 47:
| FACP: EST QuickStart QS4 <br />FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br/> Year Installed: 2003 <br />Year Decommissioned: 2021
| FACP: EST QuickStart QS4 <br />FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br/> Year Installed: 2003 <br />Year Decommissioned: 2021
|}
|}
==== FACP ====
==== FACP ====
The building was protected by an EST QuickStart QS4 addressable fire alarm system. The panel was located in the custodian's office The system ran EST’s Signature addressable protocol, and the system coding is temporal.  
The building was protected by an EST QuickStart QS4 addressable fire alarm system. The panel was located in the custodian's office The system ran EST’s Signature addressable protocol, and the system coding is temporal.  
===== Annunciators =====
There was an EST QSA-2-S annunciator with a QS4-CPU-2 CPU and two SL30 zone cards in the main entrance vestibule.
==== Notification Appliances ====
==== Notification Appliances ====
All notification appliances are Edwards MB10-24 motor bells (10” gong) on EST “Integrity” 403-5A-R strobe plates (15cd). These are still in service in the main school.  
All notification appliances are Edwards MB10-24 motor bells (10” gong) on EST “Integrity” 403-5A-R strobe plates (15cd). These are still in service in the main school.  
Line 27: Line 57:
All pull stations were EST SIGA-270 addressable single-action pull stations.
All pull stations were EST SIGA-270 addressable single-action pull stations.
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
There were EST SIGA-PS addressable photoelectric smoke detectors in parts of the school.
There were EST SIGA-PS addressable photoelectric smoke detectors by each stairwell and sets of fire doors.


Some areas, such as offices, had EST SIGA-HRS addressable fixed-temperature/rate-of-rise heat detectors.
All offices, storage rooms and some other rooms had EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.


All detectors were mounted on SIGA-SB bases.  
All detectors were mounted on SIGA-SB bases.  
Line 38: Line 68:


There were EST SIGA-CR addressable relays for fire-door closing and HVAC shutdown.
There were EST SIGA-CR addressable relays for fire-door closing and HVAC shutdown.
 
==== EOLs ====
There were Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.
There were Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits. These are still in the main school.
[[Category:Alberta]]
[[Category:Alberta]]
[[Category:Schools - Secondary]]
[[Category:Schools - Secondary]]

Latest revision as of 21:48, 14 October 2024

System Specifications
FACP: Notifier NFS2-3030C
FACP Location: Custodian's Office
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, EST & Wheelock
Date of last known Upgrade: 2021
Year Opened: 1988

École Secondaire Beaumont Composite High School is a high school located at 5417 43 Ave, Beaumont, AB. It teaches grades 10 to 12, is a bilingual school and has an enrollment of 980 students. It is part of Black Gold Regional Schools district. It was built in 1988, and had a major renovation in 2003. A new wing was constructed in 2021, and the fire alarm system was upgraded following that extension.

System Specifications (2021-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-3030C addressable fire alarm system. The panel is located in the custodian's office. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Notifier LCD-160 LCD annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

All notification appliances in the main school are Edwards MB10-24 motor bells (10" gong) on EST "Integrity" 403-5A-R strobe plates (15cd), leftover from the previous system.

The 2021 expansion has Notifier KMS-10-24A motor bells (10" gong) mounted on Wheelock RSSP-24MCW strobe plates (red, set to 15cd).

There are System Sensor "L-Series" SCRLA-E remote strobes (red, ceiling-mount, English only, set to 15cd) in the annex to the main school and in each expansion washroom.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations except for the gymnasium are Notifier NBG-12LX addressable dual-action pull stations.

The gymnasium has Notifier MPS-950B conventional single-action pull stations, wired to Notifier FMM-101A addressable monitor modules.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-951A addressable photoelectric smoke detectors in all stairwells and by each set of fire doors.

All offices, storage rooms and other rooms have Notifier FST-951RA addressable 135°F fixed-temperature/rate-of-rise heat detectors.

All detectors are mounted on System Sensor B300A-6 bases.

Modules[edit | edit source]

There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Notifier FRM-1A addressable relay modules for fire door closing and HVAC shutdown.

EOLs[edit | edit source]

There are Notifier EOL-CR end-of-line resistors on all sprinkler and signal circuits in the expansion.

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits for the main school.

Former System Specifications (2003-2021)[edit | edit source]

Former System Specifications
FACP: EST QuickStart QS4
FACP Location: Custodian's Office
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, EST
Date of last known Upgrade: N/A
Year Installed: 2003
Year Decommissioned: 2021

FACP[edit | edit source]

The building was protected by an EST QuickStart QS4 addressable fire alarm system. The panel was located in the custodian's office The system ran EST’s Signature addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There was an EST QSA-2-S annunciator with a QS4-CPU-2 CPU and two SL30 zone cards in the main entrance vestibule.

Notification Appliances[edit | edit source]

All notification appliances are Edwards MB10-24 motor bells (10” gong) on EST “Integrity” 403-5A-R strobe plates (15cd). These are still in service in the main school.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There were EST SIGA-PS addressable photoelectric smoke detectors by each stairwell and sets of fire doors.

All offices, storage rooms and some other rooms had EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.

All detectors were mounted on SIGA-SB bases.

There is also a sprinkler system with waterflow detection.

Modules[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.

There were EST SIGA-CR addressable relays for fire-door closing and HVAC shutdown.

EOLs[edit | edit source]

There were Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits. These are still in the main school.