Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Kananaskis Mountain Lodge: Difference between revisions

From FireAlarmPedia
No edit summary
No edit summary
 
(One intermediate revision by the same user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Notifier NFS2-640C <br>FACP Location: Room Behind Front Desk<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br>System Coding: Temporal <br> Strobes Synchronized: Yes, SS <br />Date of last known Upgrade: 2018 <br />Year Opened: 1987
| FACP: Notifier NFS2-640C <br>FACP Location: Room Behind Front Desk<br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br>System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: 2018 <br />Year Opened: 1987
|}
|}
The '''Kananaskis Mountain Lodge''' is a 3-story hotel located at 1 Centennial Drive, Kananaskis, AB. It was built in 1987 as Delta Lodge, and became Pomeroy Kananaskis Mountain Lodge in 2018. The fire alarm system was installed after the renovation.
The '''Kananaskis Mountain Lodge''' is a 3-story hotel located at 1 Centennial Drive, Kananaskis, AB. It was built in 1987 as Delta Lodge, and became Pomeroy Kananaskis Mountain Lodge in 2018. The fire alarm system was installed after the renovation.
NOTE: This page may not be accurate as there is conflicting information from sources.  This page should not be used for official purposes.
== System Specifications (2018-present) ==
== System Specifications (2018-present) ==
==== FACP ====
==== FACP ====
Line 22: Line 24:
==== Modules ====
==== Modules ====
There are likely Notifier FMM-1A monitor modules supervising the sprinkler system's tamper and flow switches.
There are likely Notifier FMM-1A monitor modules supervising the sprinkler system's tamper and flow switches.
==== EOLs ====
==== EOLs ====
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.
==Former System Specifications (1987-2018)==
==Former System Specifications (1987-2018)==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"

Latest revision as of 19:33, 3 November 2024

System Specifications
FACP: Notifier NFS2-640C
FACP Location: Room Behind Front Desk
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2018
Year Opened: 1987

The Kananaskis Mountain Lodge is a 3-story hotel located at 1 Centennial Drive, Kananaskis, AB. It was built in 1987 as Delta Lodge, and became Pomeroy Kananaskis Mountain Lodge in 2018. The fire alarm system was installed after the renovation.

NOTE: This page may not be accurate as there is conflicting information from sources. This page should not be used for official purposes.

System Specifications (2018-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Notifier NFS2-640C addressable fire alarm system. The panel is located in a room behind the front desk. The panel is fitted with a Notifier NCA-2 display. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are from System Sensor's "SpectrAlert Advance" line of products. All common area notification appliances are System Sensor P2RA horn/strobes (red, wall-mount, set to 15cd). The guest rooms contain System Sensor MHW mini horns (white).

There are Edwards 439D-10AWC vibrating bells (10" gong) left over in the weight room and pool area, however it is unknown how that portion works.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations. However, the Edwards 275-C111 conventional pull stations still exist in the pool area and weight room, and it is unknown if these are still in use.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851A addressable photoelectric smoke detectors on B210LPA bases throughout the hotel.

Modules[edit | edit source]

There are likely Notifier FMM-1A monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.

Former System Specifications (1987-2018)[edit | edit source]

System Specifications
FACP: Edwards 6500

FACP Location: Room Behind Front Desk
System Type: Conventional (Two-Stage)
System Line Voltage: 120VAC
NAC Voltage: 24VDC

System Coding: 20BPM (first stage)

Continuous (GA)
Date of last known Upgrade: 2000s
Year Decomissioned: 2018

FACP[edit | edit source]

The building was protected by an Edwards 6500 conventional fire alarm system. The panel was located in a room behind the front desk. The system was configured for two-stage operation. First stage coding was 20BPM, followed by continuous in general alarm.

Notification Appliances[edit | edit source]

All notification appliances except for one were the original Edwards 439D-10AWC vibrating bells (10" gong). They were mounted behind grills in all common areas except for the parkade, pool area, basement and The Fireweed Grill. There was a Notifier KMS-6-24A motor bell (6" gong) on the third floor as a deficiency replacement.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were Edwards 275-C111 conventional pull stations. Despite being two-stage, two devices had to be activated to go into general alarm.

Automatic Detection Devices[edit | edit source]

The smoke detectors were a mix of System Sensor 1412A ionization smoke detectors and Edwards 6264B ionization smoke detectors.