(Created page with " {| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Edwards EST3 <br />FACP Location: Various (Networked) <br />System Type: Two-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: 20BPM (alert) <br> Temporal (alarm) <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: 2012 <br />Year Opened: 2003 |} '''Genesis Place''' is a recreation centre located at 800 East Lake Blv...") |
(Some tweaks.) |
||
| (One intermediate revision by one other user not shown) | |||
| Line 15: | Line 15: | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by an Edwards EST3 addressable fire alarm system. The system is a network of two nodes: | The building is protected by an Edwards EST3 addressable fire alarm system. The system is a network of two nodes: | ||
* Node 1: Aquatics Entrance Vestibule | |||
* Node 2: Arena Electrical Room | |||
The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is temporal. | |||
===== Annunciators ===== | ===== Annunciators ===== | ||
| Line 31: | Line 36: | ||
=== Initiating Devices === | === Initiating Devices === | ||
===Pull Stations === | |||
All pull stations are EST SIGA-270P addressable two-stage pull stations. | All pull stations are EST SIGA-270P addressable two-stage pull stations. | ||
| Line 37: | Line 42: | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are EST SIGA2-PS addressable photoelectric smoke detectors in | There are EST SIGA2-PS addressable photoelectric smoke detectors in some areas. <br> Some mechanical rooms have EST SIGA2-HRS addressable 135°F fixed-temperature/rate of rise heat detectors. <br> There are EST SIGA2-HFS addressable 135°F fixed temperature heat detectors in some rooms such as the concession, communications room, electrical rooms, as well as the elevator shafts. <br> All aforementioned detectors are mounted on EST SIGA-SB bases. <br> Some air handling units have EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors. | ||
==== Modules ==== | ==== Modules ==== | ||
Latest revision as of 13:03, 27 May 2025
| System Specifications |
|---|
| FACP: Edwards EST3 FACP Location: Various (Networked) System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (alert) Temporal (alarm) Strobes Synchronized: Yes, EST Date of last known Upgrade: 2012 Year Opened: 2003 |
Genesis Place is a recreation centre located at 800 East Lake Blvd NE, Airdrie, Alberta. The facility features a wave pool, two NHL sized arenas and various other attractions. The facility was built in 2003, was expanded in 2009 to add a soccer complex and gymnasium, and finally expanded in 2012 to add the arenas. The fire alarm system is original, with a network expansion in 2012.
System Specifications (2003-present)
FACP
The building is protected by an Edwards EST3 addressable fire alarm system. The system is a network of two nodes:
- Node 1: Aquatics Entrance Vestibule
- Node 2: Arena Electrical Room
The system runs Edwards’ Signature addressable protocol, and is configured for two-stage operation. The alert signal coding is 20BPM, and the alarm signal coding is temporal.
Annunciators
There are two Edwards EST3-LCDANN annunciators fitted with the LCDXL1 displays in the arena entrance vestibule and behind the main desk.
Booster Panels
There are a total of 10 Edwards BPS10A 10-amp power supplies throughout the building.
Notification Appliances
Most notification appliances are Edwards MB6-24 motor bells (6” gong) mounted on EST 403-5A-R strobe plates (15cd).
Areas with higher ambient noise levels have Edwards MB10-24 motor bells (10” gong) mounted on EST 403-5A-R strobe plates.
Initiating Devices
Pull Stations
All pull stations are EST SIGA-270P addressable two-stage pull stations.
Automatic Detection Devices
There are EST SIGA2-PS addressable photoelectric smoke detectors in some areas.
Some mechanical rooms have EST SIGA2-HRS addressable 135°F fixed-temperature/rate of rise heat detectors.
There are EST SIGA2-HFS addressable 135°F fixed temperature heat detectors in some rooms such as the concession, communications room, electrical rooms, as well as the elevator shafts.
All aforementioned detectors are mounted on EST SIGA-SB bases.
Some air handling units have EST “SuperDuct” SIGA-SD addressable photoelectric duct smoke detectors.
Modules
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM isolator modules on each SLC.
EOLs
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.