| FACP: Simplex 4100ES <br /> FACP Location: Main Entrance Vestibule<br>System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Unknown <br>Strobes Synchronized: No <br>Date of last known Upgrade: | | FACP: Simplex 4100ES <br /> FACP Location: Main Entrance Vestibule<br>System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Unknown <br>Strobes Synchronized: No <br>Date of last known Upgrade: 2022 <br />Year Opened: 1995 | ||
|} | |} | ||
'''Don Hartman | '''NESS: Don Hartman North East Sportsplex''' is a sports facility located at 5206 68 Street Northeast, in Calgary, Alberta, Canada. It houses two 150-seat, NHL-sized arenas, as well as a large gymnasium. The building was built in 1995, and the fire alarm system was partially upgraded in 2022; most notification appliances remain original. | ||
==System Specifications (2021-present) == | ==System Specifications (2021-present) == | ||
====FACP==== | ====FACP==== | ||
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule. This panel is equipped with the Simplex ES touchscreen interface. The system runs Simplex's IDNet addressable protocol, but the coding of the system is unknown. | The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule. This panel is equipped with the Simplex Color ES touchscreen interface. The system runs Simplex's IDNet addressable protocol, but the coding of the system is unknown. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
Most notification appliances are Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5 candela). The dressing room hallway has a Simplex 2901-9724 motor bell (10" gong) and a Potter MBA-10-24 motor bell (10" gong) on the original strobe plates as deficiency replacements. The second floor corridor has a Potter MBA-6-24 motor bell (6" gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd) as a deficiency replacement. | Most notification appliances are Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5 candela). | ||
The dressing room hallway has a Simplex 2901-9724 motor bell (10" gong) and a Potter MBA-10-24 motor bell (10" gong) on the original strobe plates as deficiency replacements. | |||
The second floor corridor has a Potter MBA-6-24 motor bell (6" gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd) as a deficiency replacement. | |||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
Line 20: | Line 24: | ||
==== Modules ==== | ==== Modules ==== | ||
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler's tamper and flow switches. | There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler's tamper and flow switches. | ||
There are Simplex 4090-9002 addressable relay modules serving various purposes. | |||
There are Simplex 4090-9116 addressable isolator modules on the SLC. | |||
==== EOLs ==== | |||
There are a mix of Notifier EOL-CR and Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits. | |||
==System Specifications (original system) (1995-2021)== | ==System Specifications (original system) (1995-2021)== | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
Line 27: | Line 39: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier System 500<br /> FACP Location: Main Entrance Vestibule <br> System Type: Single-Stage Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Continuous <br> Strobes Synchronized: No <br> Date of last known Upgrade: 2000s <br />Final year in service: 2021 | | FACP: Notifier System 500<br />FACP Location: Main Entrance Vestibule <br>System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No <br>Date of last known Upgrade: 2000s <br />Final year in service: 2021 | ||
|} | |} | ||
====FACP==== | ====FACP==== | ||
The building was protected by a Notifier System 500 conventional fire alarm system. The panel was located in the main entrance vestibule. The system coding was continuous. | The building was protected by a Notifier System 500 conventional fire alarm system. The panel was located in the main entrance vestibule. The system coding was continuous. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
Most notification appliances are Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5 candela). The dressing room hallway has a Simplex 2901-9724 motor bell (10" gong) and a Potter MBA-10-24 motor bell (10" gong) on the original strobe plates as deficiency replacements. The second floor corridor has a Potter MBA-6-24 motor bell (6" gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd) as a deficiency replacement. All of these notification appliances are still in service on the current system. | Most notification appliances are Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5 candela). | ||
The dressing room hallway has a Simplex 2901-9724 motor bell (10" gong) and a Potter MBA-10-24 motor bell (10" gong) on the original strobe plates as deficiency replacements. | |||
The second floor corridor has a Potter MBA-6-24 motor bell (6" gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd) as a deficiency replacement. | |||
All of these notification appliances are still in service on the current system. | |||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations were Notifier NFM-950B conventional single-action pull stations. | All pull stations were Notifier NFM-950B conventional single-action pull stations. | ||
====Automatic Detection Devices==== | ====Automatic Detection Devices==== | ||
There were likely System Sensor 1400A conventional ionization smoke detectors at the top of each stairwell, however this is unconfirmed. | |||
==== EOLs ==== | |||
There were Notifier EOL-CR end of line resistor plates on all circuits. | |||
[[Category:Calgary]] | [[Category:Calgary]] | ||
[[Category:Recreation Centres]] | [[Category:Recreation Centres]] | ||
[[Category:Arenas]] | [[Category:Arenas]] |
Latest revision as of 17:10, 24 November 2024
System Specifications |
---|
FACP: Simplex 4100ES FACP Location: Main Entrance Vestibule System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Unknown Strobes Synchronized: No Date of last known Upgrade: 2022 Year Opened: 1995 |
NESS: Don Hartman North East Sportsplex is a sports facility located at 5206 68 Street Northeast, in Calgary, Alberta, Canada. It houses two 150-seat, NHL-sized arenas, as well as a large gymnasium. The building was built in 1995, and the fire alarm system was partially upgraded in 2022; most notification appliances remain original.
System Specifications (2021-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located in the main entrance vestibule. This panel is equipped with the Simplex Color ES touchscreen interface. The system runs Simplex's IDNet addressable protocol, but the coding of the system is unknown.
Notification Appliances[edit | edit source]
Most notification appliances are Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5 candela).
The dressing room hallway has a Simplex 2901-9724 motor bell (10" gong) and a Potter MBA-10-24 motor bell (10" gong) on the original strobe plates as deficiency replacements.
The second floor corridor has a Potter MBA-6-24 motor bell (6" gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd) as a deficiency replacement.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors at the top of each stairwell, mounted on Simplex 4098-9792 bases.
Modules[edit | edit source]
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler's tamper and flow switches.
There are Simplex 4090-9002 addressable relay modules serving various purposes.
There are Simplex 4090-9116 addressable isolator modules on the SLC.
EOLs[edit | edit source]
There are a mix of Notifier EOL-CR and Simplex 2081-9040C end of line resistor plates on all sprinkler and signal circuits.
System Specifications (original system) (1995-2021)[edit | edit source]
System Specifications |
---|
FACP: Notifier System 500 FACP Location: Main Entrance Vestibule System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 2000s Final year in service: 2021 |
FACP[edit | edit source]
The building was protected by a Notifier System 500 conventional fire alarm system. The panel was located in the main entrance vestibule. The system coding was continuous.
Notification Appliances[edit | edit source]
Most notification appliances are Wheelock MBS-G10-24 motor bell/strobes (10" gong, 1.5 candela).
The dressing room hallway has a Simplex 2901-9724 motor bell (10" gong) and a Potter MBA-10-24 motor bell (10" gong) on the original strobe plates as deficiency replacements.
The second floor corridor has a Potter MBA-6-24 motor bell (6" gong) mounted on a Wheelock RSSP-24MCW strobe plate (set to 15cd) as a deficiency replacement.
All of these notification appliances are still in service on the current system.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Notifier NFM-950B conventional single-action pull stations.
Automatic Detection Devices[edit | edit source]
There were likely System Sensor 1400A conventional ionization smoke detectors at the top of each stairwell, however this is unconfirmed.
EOLs[edit | edit source]
There were Notifier EOL-CR end of line resistor plates on all circuits.