Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

St. Timothy High School: Difference between revisions

From FireAlarmPedia
 
(58 intermediate revisions by 3 users not shown)
Line 1: Line 1:
'''St. Timothy High School''' is a junior and senior high school in the neighborhood of Sunset Ridge in Cochrane, AB. It was built in 2004, and the current system is from 2020. Only the pull stations are original. The school is two floors. User Simplex NimrodES was been unable to obtain any alarms.
{| style="float:right;border:2px solid black"
 
|-
== System Specifications ==
! System Specifications
 
|-
|
|-
| FACP: Kidde VS4 <br /> FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes<br />Date of last known Upgrade: 2020 <br />Year Opened: 2004
|}
'''St. Timothy High School''' is a junior and senior high school located at 501 Sunset Drive, Cochrane, AB. It is operated by the Calgary Catholic School District. The school was built in 2004, and the fire alarm system was upgraded in 2020; only the pull stations are original.
== System Specifications (2020-present) ==
This system took two months to install, starting in May 2020 and ending that summer.
==== FACP ====
==== FACP ====
The building is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the caretaker's office. The system runs Kidde's GSA addressable protocol, and the system coding is temporal.
===== Annunciators =====
There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.
==== Notification Appliances ====
All notification appliances except for one are from Kidde's "Genesis" line of products.


The fire alarm control panel is a Kidde VS4. It was installed in April-June 2020, replacing an EST QuickStart QS1 from 2016. The main panel is not visible, it's in the caretaker's office. When the system goes into alarm, all horns and strobes (indoor and outdoor) are synchronized, and all horns do code-3. It took Altex Security two whole months to do this system. The annunciator is on a rectangular plate covering the QuickStart's space.
The main notification appliances are Kidde GC-HDVM horn/strobes (white, ceiling-mount, no lettering, set to 30 or 75cd). There is one horn/strobe per classroom, and the library contains three horn/strobes.  


===== Annunciators =====
Open ceiling areas (the top floor atrium, gymnasium, band/music room and the shop) have Kidde G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to either 15, 75, or 110cd). The gym has four; two of the horn/strobes where the bell/strobes were, but the other two are in new locations.


There is a Kidde K-RLCD-C annunciator and a K-RLED24 LED annunciator at the entrance.
All washrooms have an Kidde GC-VM remote strobe (white, ceiling-mount, no lettering, set to 75cd).  


==== Notification Appliances ====
For exterior notification, there is an Edwards WG4RN-HVMC weatherproof horn/strobe (red, no lettering, set to 60cd) by the tarmac, behind a wire grill.  
 
The notification appliance circuits were mostly re-wired when the VS4 was installed. The main notification appliances are EST "Genesis" GC-HDVM (white, ceiling, no FIRE marking) horn/strobes on the ceiling in the hallways and classrooms. There is one horn/strobe per classroom, and the library, there are three horn/strobes. The open ceiling areas, such as the atrium, gymnasium, band/music room and the shop have EST "Genesis" G1R-HDVM (red, wall, no FIRE marking) horn/strobes. The gym has two of the horn/strobes where the old bell/strobes were, but the other two are in new locations, having two per side. The shop has the horn/strobes moved to different locations as well. All horn/strobes are set to high volume, and random candelas (a few are at 110cd). These horn/strobes were installed in spring 2020. Plates are covering where the bell/strobes were. One of the three outdoor bells was replaced with an EST "Genesis" WG4RN-HVMC (red, no FIRE) horn/strobe by the tarmac, and it is now covered by a cage. Metal plates are covering the former outdoor bells' space. The EST "Integrity" CS405-8A-T weatherproof strobe by the bike rack that was replaced in February 2020 when the QuickStart was still in use, is still in use on the VS4.


There is also an Edwards "Integrity" CS405-8A-T weatherproof remote strobe (red, 110cd) by the bike rack that was installed in early 2020 when the QuickStart was still in service; the only notification appliance to remain from the previous system.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All pull stations are the original EST SIGA-270 addressable pull stations. These were kept from the previous system as they are compatible.
==== Automatic Detection Devices ====
There are Kidde KI-PD optical addressable smoke detectors throughout the building.


All of the pull stations are the original EST SIGA-270 from 2004.  
Certain rooms have Kidde KIR-HD addressable 135°F fixed-temperature/rate-of-rise heat detectors. All detectors installed on KI-SB bases.  
 
==== Automatic Detection Devices ====


The smoke detectors were replaced with Kidde KIR-PD optical addressable smoke detectors. Installed in spring 2020 when the new system was installed. The duct detectors in the air handling units are Kidde SD-2W two-wire photoelectric duct smoke detectors.
There are Kidde GSA-SD two-wire photoelectric duct smoke detectors on each air handling unit and behind ceilings. They are connected to Kidde GSA-LED LED indicators.
==== Modules ====
There are Kidde GSA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.  


== Former System Specifications ==
There are also Kidde GSA-CR addressable control modules for shutting down the HVAC system and releasing the fire doors, wired to EST 1508-AQN5 magnetic door holders.


There are Kidde GSA-IM isolator modules on the SLC.
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.
== Former System Specifications (2004-2020) ==
{| style="float:right;border:2px solid black"
|-
! Former System Specifications
|-
|
|-
| FACP: EST QuickStart QS1 <br /> FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: Feb 2020
Year Installed: 2004<br />Year Decomissioned: 2020
|}
==== FACP ====
==== FACP ====
The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. The system ran EST's Signature addressable protocol, and the system coding was temporal.


The school had an EST QuickStart QS1 from 2016. The original fire alarm panel was also an EST Quickstart QS1, but it failed. It rarely has troubles at all, but usually when the power is out. The panel had an SL30 card. There is an annunciator at the entrance, but the panel itself is in the caretaker's office. The original QuickStart did continuous, and the second one did code-3 with all strobes synchronized. The system is managed by Altex Security.  
This panel was installed in 2016 as an emergency replacement for the original variant, which suffered a CPU failure.
===== Annunciators =====
There was a QSA-1-S cabinet in the main entrance vestibule, with an EST QS1-CPU-1 CPU and an SL30 card in it.
==== Notification Appliances ====
Most notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R strobe plates (15cd). These could also be found in the library, the music room, and the changerooms.  


===== Annunciators =====
The gym and shop had Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates due to higher ambient noise levels. There were three in the gym, and two in the shop.


There was an  EST QS1-CPU-1 annunciator at the entrance, and an SL30 card in it.
For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the front near the hill, one by the staff parking lot, and one at the tarmac.  


==== Notification Appliances ====
There was also an Edwards CS405-8A-T weatherproof remote strobe (red, 110cd) above the bike rack; this was installed in February 2020 as a deficiency replacement for the original EST one, and is still in use on the current system.
=== Initiating Devices ===
==== Pull Stations ====
All pull stations were EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.
==== Automatic Detection Devices ====
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building.


The main notification appliances seen throughout the school are Edwards MB6-24 motor bells on EST 403-5A-R (15cd) Integrity strobe plates. They can also be found in the library, the music room, and even the changerooms! The gym and shop have louder ambient noise levels, so they have Edwards MB10-24 motor bells on EST 403-5A-R strobe plates. There are 3 in the gym, and they are very loud. For outdoor notification, there are three Edwards MB6-24 motor bells. One by the hill where stairs to the basement are, one in the staff parking lot, and one in the tarmac. There is also an EST CS405-8A-T (110cd) weatherproof Integrity strobe installed in February 2020, after an older one stopped flashing in September 2019. The strobe is above the bike rack, close to the main entrance.
Certain rooms such as the electrical room had EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.  


=== Initiating Devices ===
All detectors were mounted on SIGA-SB bases. Most were original, and some were deficiency replacements over the years.


==== Pull Stations ====
There were EST SIGA-DH duct detector housings, on the air handling units and above some ceilings, with SIGA-PS addressable photoelectric heads inside them. These were connected to EST SIGA-LED LED indicators.
==== Modules ====
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.


All of the pull stations were EST SIGA-270, original to the school in 2004. The gym one is missing its glass rod. These are still in use on the Kidde system.
There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.


==== Automatic Detection Devices ====
There were EST SIGA-IM isolator modules on the SLC.
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.


The smoke detectors are EST SIGA-PS, most are original from 2004, but some are newer.
== List of known activations ==
September 21, 2020 - alarm at around 9:45 AM, activated by duct detector in air handling unit in gymnasium. Scent of smoke reported in gym and nearby areas prior to alarm. School was evacuated, Cochrane Fire Services responded and the cause was found to be a motor overheating, burning red hot and smoking from the electrical panel outputting 4x the rated current, due to FORTIS working on power. Alarm shut off after 30 minutes.
== Gallery ==
<gallery>
StTimothyBellStrobe.jpeg|An Edwards MB6-24 bell/strobe combo in the basement. (This alarm does not exist anymore)
StTimothyBellStrobe2.jpeg|This one was located by Room 209. Note the sticker on the bell. (This alarm does not exist anymore)
StTimothyBandRoomBellStrobe.jpeg|This bell/strobe was in the band room. Note the Incredibles logo on it, which was vandalized by the band teacher. This was a code violation, as the strobe flashes are not visible. (This alarm does not exist anymore)
StTimothySmoke.jpeg|An original EST SIGA-PS smoke detector in the stairwell. Also pictured is an Enforcer ceiling speaker. (This smoke detector does not exist anymore)
StTimothyOriginalAnnunciator.jpeg|The QuickStart annunciator in the entrance. Note the new EST logo. (System has been replaced)
StTimothyPull.jpeg|A pull station by the stairwell in the basement. This pull station is still installed on the Kidde system.
</gallery>
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Cochrane]]
[[Category:Schools - Secondary]]

Latest revision as of 23:05, 13 October 2024

System Specifications
FACP: Kidde VS4
FACP Location: Custodian's Office
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2020
Year Opened: 2004

St. Timothy High School is a junior and senior high school located at 501 Sunset Drive, Cochrane, AB. It is operated by the Calgary Catholic School District. The school was built in 2004, and the fire alarm system was upgraded in 2020; only the pull stations are original.

System Specifications (2020-present)[edit | edit source]

This system took two months to install, starting in May 2020 and ending that summer.

FACP[edit | edit source]

The building is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the caretaker's office. The system runs Kidde's GSA addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.

Notification Appliances[edit | edit source]

All notification appliances except for one are from Kidde's "Genesis" line of products.

The main notification appliances are Kidde GC-HDVM horn/strobes (white, ceiling-mount, no lettering, set to 30 or 75cd). There is one horn/strobe per classroom, and the library contains three horn/strobes.

Open ceiling areas (the top floor atrium, gymnasium, band/music room and the shop) have Kidde G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to either 15, 75, or 110cd). The gym has four; two of the horn/strobes where the bell/strobes were, but the other two are in new locations.

All washrooms have an Kidde GC-VM remote strobe (white, ceiling-mount, no lettering, set to 75cd).

For exterior notification, there is an Edwards WG4RN-HVMC weatherproof horn/strobe (red, no lettering, set to 60cd) by the tarmac, behind a wire grill.

There is also an Edwards "Integrity" CS405-8A-T weatherproof remote strobe (red, 110cd) by the bike rack that was installed in early 2020 when the QuickStart was still in service; the only notification appliance to remain from the previous system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are the original EST SIGA-270 addressable pull stations. These were kept from the previous system as they are compatible.

Automatic Detection Devices[edit | edit source]

There are Kidde KI-PD optical addressable smoke detectors throughout the building.

Certain rooms have Kidde KIR-HD addressable 135°F fixed-temperature/rate-of-rise heat detectors. All detectors installed on KI-SB bases.

There are Kidde GSA-SD two-wire photoelectric duct smoke detectors on each air handling unit and behind ceilings. They are connected to Kidde GSA-LED LED indicators.

Modules[edit | edit source]

There are Kidde GSA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.

There are also Kidde GSA-CR addressable control modules for shutting down the HVAC system and releasing the fire doors, wired to EST 1508-AQN5 magnetic door holders.

There are Kidde GSA-IM isolator modules on the SLC.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.

Former System Specifications (2004-2020)[edit | edit source]

Former System Specifications
FACP: EST QuickStart QS1
FACP Location: Custodian's Office
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: Feb 2020

Year Installed: 2004
Year Decomissioned: 2020

FACP[edit | edit source]

The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. The system ran EST's Signature addressable protocol, and the system coding was temporal.

This panel was installed in 2016 as an emergency replacement for the original variant, which suffered a CPU failure.

Annunciators[edit | edit source]

There was a QSA-1-S cabinet in the main entrance vestibule, with an EST QS1-CPU-1 CPU and an SL30 card in it.

Notification Appliances[edit | edit source]

Most notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R strobe plates (15cd). These could also be found in the library, the music room, and the changerooms.

The gym and shop had Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates due to higher ambient noise levels. There were three in the gym, and two in the shop.

For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the front near the hill, one by the staff parking lot, and one at the tarmac.

There was also an Edwards CS405-8A-T weatherproof remote strobe (red, 110cd) above the bike rack; this was installed in February 2020 as a deficiency replacement for the original EST one, and is still in use on the current system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.

Automatic Detection Devices[edit | edit source]

There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building.

Certain rooms such as the electrical room had EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.

All detectors were mounted on SIGA-SB bases. Most were original, and some were deficiency replacements over the years.

There were EST SIGA-DH duct detector housings, on the air handling units and above some ceilings, with SIGA-PS addressable photoelectric heads inside them. These were connected to EST SIGA-LED LED indicators.

Modules[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.

There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.

There were EST SIGA-IM isolator modules on the SLC.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.

List of known activations[edit | edit source]

September 21, 2020 - alarm at around 9:45 AM, activated by duct detector in air handling unit in gymnasium. Scent of smoke reported in gym and nearby areas prior to alarm. School was evacuated, Cochrane Fire Services responded and the cause was found to be a motor overheating, burning red hot and smoking from the electrical panel outputting 4x the rated current, due to FORTIS working on power. Alarm shut off after 30 minutes.

Gallery[edit | edit source]