| System Specifications |
|---|
| FACP: Notifier NFS-320SYS FACP Location: Basement Hallway System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: 1986 Most Recent Known Modification: 2022, FACP Year Opened: 1932 |
The Camrose Federal Building is a commercial building located at 4901 50 Ave, in Camrose, Alberta, Canada. The building is anchored by Canada Post. The building was built in 1932, and extensive electrical upgrades were performed in 1986. The fire alarm system was upgraded as part of the electrical upgrades, with an FACP replacement occurring in 2022.
System Specifications (1986-present)
FACP
The building is protected by a Notifier NFS-320SYS conventional fire alarm system. The panel is located in the basement hallway. The system utilizes several Notifier XP6-MAA zone cards to accommodate the system's conventional devices, and the system coding is continuous.
Annunciators
There is a Notifier LCD2-80 annunciator paired with a Notifier ACM-24AT annunciator in the elevator lobby.
Notification Appliances
Most notification appliances are Edwards 439D-6AWC vibrating bells (6" gong).
Some office areas have Mircom BL-6A motor bells (6" gong) mounted on Amseco RSB24-153075 strobe plates (set to 15cd).
Initiating Devices
Pull Stations
All pull stations are Edwards 270-SPO conventional single-action pull stations.
Automatic Detection Devices
There are a mix of Edwards 6250C and System Sensor 1400A conventional ionization and System Sensor C2W-BA conventional photoelectric smoke detectors throughout all corridors, at the top of each stairwell, and in some storage rooms.
There are a mix of Edwards 281C, Edwards 281A and System Sensor 5601A conventional 135°F fixed-temperature/rate-of-rise heat detectors in all washrooms, janitor rooms, storage rooms and some other rooms.
There is an Edwards 284C conventional 194°F fixed-temperature heat detector in the basement kitchen.
There is an Edwards 245A conventional 135°F fixed-temperature heat detector in the boiler room.
There are Edwards 6265B-001 duct smoke detector housings equipped with Edwards 6264C-001 conventional ionization heads on all air handling units but two.
There are Edwards "SuperDuct" SD-2W conventional photoelectric smoke detectors on all upgraded air handling units.
EOLs
There are Notifier EOL-CW end of line resistor plates on all circuits.