More actions
(Revamping the page a little bit.) |
No edit summary |
||
(10 intermediate revisions by 3 users not shown) | |||
Line 1: | Line 1: | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 6: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: | | FACP: Edwards EST3X <br /> FACP Location: Boiler Room<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, Genesis<br />Date of last known Upgrade: 2019 <br />Year Opened: 1967 | ||
|}''' | |} | ||
== System Specifications == | '''Centennial Planetarium''' was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of [[TELUS Spark]] in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant. | ||
== System Specifications (2018-present) == | |||
==== FACP ==== | ==== FACP ==== | ||
The fire alarm panel is | The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the boiler room. The system runs Edwards' Signature addressable protocol, and the system coding is temporal. | ||
===== Annunciators ===== | |||
There is an Edwards EST3-6ANN annunciator equipped with an LCDXL1 display at the main entrance. | |||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances are EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd). | |||
There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected. | |||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
The pull stations are | The pull stations are EST SIGA-270 addressable pull stations. | ||
==== | ==== Automatic Detection Devices ==== | ||
The smoke detectors are | The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases. | ||
== | ==== Modules ==== | ||
==== | There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches. | ||
==== EOLs ==== | |||
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits. | |||
== Former System Specifications (East Wing) (2000s-2011) == | |||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 26: | Line 37: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier | | FACP: Notifier AFP-400 <br /> FACP Location: Unknown <br />System Type: Two-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (Alert) <br> Temporal (Alarm) <br> Strobes Synchronized: No <br />Date of last known Upgrade: 2005 <br />Year Decomissioned: 2011 | ||
|} | |} | ||
The fire alarm panel was | ==== FACP ==== | ||
The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The alert coding was 20BPM, and the alarm coding was temporal. | |||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd) | |||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
The pull stations were Notifier | The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier FMM-101A addressable modules, behind each station. | ||
== | ==== Automatic Detection Devices ==== | ||
==== | Not available. | ||
== Former System Specifcations (West Wing) (Early 2000s-2011) == | |||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 42: | Line 55: | ||
| | | | ||
|- | |- | ||
| FACP: Unknown | | FACP: Edwards EST2? <br /> FACP Location: Unknown <br />System Type: Two-Stage Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br /> System Coding: 20BPM (first stage) <br> Continuous (GA) <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2000s <br />Year Decomissioned: 2011 | ||
|} | |} | ||
The fire alarm | ==== FACP ==== | ||
The West Wing was most likely protected by an Edwards EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm. | |||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
The notification appliances were Edwards 439D-6AWC vibrating bells on EST 403-5A-R "Integrity" strobe plates | The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd) and others mounted remotely. | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
The pull stations | The pull stations were all Edwards 270P-SPO conventional two-stage pull stations. | ||
[[Category: | ==== Automatic Detection Devices ==== | ||
Not available. | |||
[[Category:Calgary]] | |||
[[Category:Museums]] | |||
[[Category:Iconic buildings in Calgary]] |
Latest revision as of 16:21, 23 September 2024
System Specifications |
---|
FACP: Edwards EST3X FACP Location: Boiler Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, Genesis Date of last known Upgrade: 2019 Year Opened: 1967 |
Centennial Planetarium was a planetarium in Calgary. It is in Downtown Calgary, at 701 11 St SW. It is one of Calgary's best examples of Brutalist architecture. The TELUS World of Science moved in in 1984, and was renovated in 2011. Following the opening of TELUS Spark in 2011, Telus World of Science closed its doors. In 2018, an art museum known as Contemporary Calgary moved into the space. The system was installed following the new tenant.
System Specifications (2018-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by an Edwards EST3X addressable fire alarm system. The panel is located in the boiler room. The system runs Edwards' Signature addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There is an Edwards EST3-6ANN annunciator equipped with an LCDXL1 display at the main entrance.
Notification Appliances[edit | edit source]
All notification appliances are EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no marking, set to 15cd).
There is one Edwards 439D-6AWC vibrating bell (6" gong) on an EST 403-5A-R (15cd) strobe plate left over, but it is disconnected.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
The pull stations are EST SIGA-270 addressable pull stations.
Automatic Detection Devices[edit | edit source]
The smoke detectors are EST SIGA2-PS addressable photoelectric smoke detectors, mounted on SIGA-SB bases.
Modules[edit | edit source]
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
EOLs[edit | edit source]
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.
Former System Specifications (East Wing) (2000s-2011)[edit | edit source]
System Specifications |
---|
FACP: Notifier AFP-400 FACP Location: Unknown System Type: Two-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (Alert) Temporal (Alarm) Strobes Synchronized: No Date of last known Upgrade: 2005 Year Decomissioned: 2011 |
FACP[edit | edit source]
The East Wing was protected by a Notifier AFP-400 addressable fire alarm system. The panel location was unknown. The system ran Notifier's CLIP addressable protocol, and was configured for two-stage operation. The alert coding was 20BPM, and the alarm coding was temporal.
Notification Appliances[edit | edit source]
The notification appliances were Notifier KMS-10-24A motor bells (10" gong) on Wheelock RSSP-2415W-FR strobe plates (15cd)
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
The pull stations were Notifier MPS-950KB conventional two-stage pull stations. They were directly wired to Notifier FMM-101A addressable modules, behind each station.
Automatic Detection Devices[edit | edit source]
Not available.
Former System Specifcations (West Wing) (Early 2000s-2011)[edit | edit source]
System Specifications |
---|
FACP: Edwards EST2? FACP Location: Unknown System Type: Two-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: 20BPM (first stage) Continuous (GA) Strobes Synchronized: Yes Date of last known Upgrade: 2000s Year Decomissioned: 2011 |
FACP[edit | edit source]
The West Wing was most likely protected by an Edwards EST2 conventional fire alarm system. The panel location was unknown. The system was configured for two-stage operation; first stage coding was 20BPM, with continuous in general alarm.
Notification Appliances[edit | edit source]
The notification appliances were Edwards 439D-6AWC vibrating bells (6" gong), mostly on EST 403-5A-R "Integrity" strobe plates (15cd) and others mounted remotely.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
The pull stations were all Edwards 270P-SPO conventional two-stage pull stations.
Automatic Detection Devices[edit | edit source]
Not available.