Maple Ridge School: Difference between revisions

From FireAlarmPedia
(Added link to RTA.)
No edit summary
 
(11 intermediate revisions by 4 users not shown)
Line 1: Line 1:
""Maple Ridge School"" is an elementary school located in the Maple Ridge neighborhood of Southeast Calgary. The school has a capacity of approximately 600 students, and was built in 1967. The school received its most recent fire alarm upgrade in 2012.
{| style="float:right;border:2px solid black"
==System Specifications==
|-
! System Specifications
|-
|
|-
| FACP: Simplex 4010 <br>FACP Location: Unknown<br />System Type: Single-Stage Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br>System Coding: Temporal <br>Strobes Synchronized: Yes, Wheelock<br />Date of last known Upgrade: 2015 <br />Year Opened: 1976
|}
'''Maple Ridge School''' is an elementary school located at 10203 Maplemont Rd SE, Calgary, Alberta. The school has a capacity of approximately 600 students, and was built in 1967. The school received its most recent fire alarm upgrade in 2015.
==System Specifications (2015-present) ==
====FACP====
====FACP====
The building is protected by a Simplex 4010-9101C addressable fire alarm system. The panel is unconfirmed, as is the location.
The building is protected by a Simplex 4010 addressable fire alarm system. The panel location is unknown. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.  
====Notification Appliances====
====Notification Appliances====
All notification appliances are Wheelock MT-12/24-R multitone horns on Wheelock RSSP-24MCW-FR strobe plates. These notification appliances were selected due to the large footprint of the previous devices, and to mount on the existing backboxes. The horns are set to code 3 horn (electromechanical), and the strobes are likely set on 15 candela.  As with the panel, the locations of the devices are unknown.
All notification appliances are Wheelock MT-12/24R remote horns (red, wall-mount) on Wheelock RSSP-24MCW strobe plates. The horns are set to horn, and the strobes are set to 15cd.
===Initiating Devices===
=== Initiating Devices ===
====Pull Stations====
====Pull Stations====
All pull stations are Simplex 4099-9001 IDnet addressable pull stations.
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Simplex 4098-9714 IDnet addressable photoelectric smoke detectors located throughout the facility. They are likely set to 2% smoke/cubic foot.
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors located throughout the facility, mounted on Simplex 4098-9792 addressable bases.
==System Specifications (previous system)==
 
NOTE: This system is unconfirmed, as it is based off a non-user's memory, and the system at the neighboring [[R.T. Alderman School]].
==== EOLs ====
There are Simplex 2081-9040C end of line resistor plates on all signal circuits.
 
==System Specifications (previous system, late 1980s-2015)==
{| style="float:right;border:2px solid black"
|-
! System Specifications
|-
|
|-
| FACP: Simplex 4002 <br>FACP Location: Unknown<br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br>System Coding: Continuous <br>Strobes Synchronized: No<br />Date of last known Upgrade: N/A <br />Year Decomissioned: 2015
|}
NOTE: This system is unconfirmed, as it is based off ThePurpleMage's memory, and the system at the neighboring [[R.T. Alderman School]].
====FACP====
====FACP====
The previous panel was likely a 16-zone Simplex 4002-8001 conventional fire alarm panel.
The building was likely protected by a Simplex 4002 conventional fire alarm system. The system coding was likely continuous.
====Notification Appliances====
====Notification Appliances====
The previous notification appliances were Simplex 2901-9833 mechanical horns on Simplex 2903-9101 strobe plates. The system likely did continuous in alarm.
The notification appliances were Simplex 2901-9833 mechanical horns (red) on Simplex 2903-9101 strobe plates.  
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
The previous pull stations were likely Simplex 2099-9901 "T-bar" conventional pull stations.
The pull stations were likely Simplex 2099-9901 conventional pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There were Simplex 2098-9110 ionization smoke detectors throughout the school.
There were Simplex 2098-9110 ionization smoke detectors throughout the school.
==== EOLs ====
There were Simplex 2081-9040C end of line resistor plates on all circuits.
[[Category:Facilities]]
[[Category:Calgary]]
[[Category:Schools]]

Latest revision as of 14:07, 30 September 2024

System Specifications
FACP: Simplex 4010
FACP Location: Unknown
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, Wheelock
Date of last known Upgrade: 2015
Year Opened: 1976

Maple Ridge School is an elementary school located at 10203 Maplemont Rd SE, Calgary, Alberta. The school has a capacity of approximately 600 students, and was built in 1967. The school received its most recent fire alarm upgrade in 2015.

System Specifications (2015-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4010 addressable fire alarm system. The panel location is unknown. The system runs Simplex's IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All notification appliances are Wheelock MT-12/24R remote horns (red, wall-mount) on Wheelock RSSP-24MCW strobe plates. The horns are set to horn, and the strobes are set to 15cd.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors located throughout the facility, mounted on Simplex 4098-9792 addressable bases.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all signal circuits.

System Specifications (previous system, late 1980s-2015)[edit | edit source]

System Specifications
FACP: Simplex 4002
FACP Location: Unknown
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Continuous
Strobes Synchronized: No
Date of last known Upgrade: N/A
Year Decomissioned: 2015

NOTE: This system is unconfirmed, as it is based off ThePurpleMage's memory, and the system at the neighboring R.T. Alderman School.

FACP[edit | edit source]

The building was likely protected by a Simplex 4002 conventional fire alarm system. The system coding was likely continuous.

Notification Appliances[edit | edit source]

The notification appliances were Simplex 2901-9833 mechanical horns (red) on Simplex 2903-9101 strobe plates.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

The pull stations were likely Simplex 2099-9901 conventional pull stations.

Automatic Detection Devices[edit | edit source]

There were Simplex 2098-9110 ionization smoke detectors throughout the school.

EOLs[edit | edit source]

There were Simplex 2081-9040C end of line resistor plates on all circuits.