'''George Bush Intercontinental Airport''' is an international airport located in Houston, Texas, USA. This airport serves the Houston area, and is the second largest airport in the state of Texas. The airport has 5 terminals, each with their own system. All systems, however, are wired to trip each other when one goes into alarm. Only the systems in terminals B, C, and E are known. Terminal D will be included in this page, but is speculation. Terminals A and B are the oldest, and opened in 1969. Terminal C opened in 1981, followed by Terminal D in 1990. Terminal E is the newest, and opened officially in 2004. Only Terminal E has its original system.  
'''George Bush Intercontinental Airport''' is an international airport located in Houston, Texas, USA. This airport serves the Houston area, and is the second largest airport in the state of Texas. The airport has 5 terminals, each with their own system. The systems likely operate independently from each other. Only the systems in terminals B, C, and E are known. Terminal D will be included in this page, but is speculation. Terminals A and B are the oldest, and opened in 1969. Terminal C opened in 1981, followed by Terminal D in 1990. Terminal E is the newest, and opened officially in 2004. Only Terminal E has its original system.  
 
==System Specifications (Terminal B) (2014-present)==
==System Specifications (Terminal B) (2014-present)==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 12: Line 11:
This system was installed in 2014, following a large renovation.
This system was installed in 2014, following a large renovation.
====FACP====
====FACP====
The terminal is protected by a Notifier NFS2-3030 addressable fire alarm system. The panel location is unknown. This panel is equipped with a DVC (Digital Voice Command) voice evac module.  The system runs Notifier’s FlashScan addressable protocol, and does the default Notifier slow whoop and female message in alarm.
The terminal is protected by a Notifier NFS2-3030 addressable fire alarm system. The system is networked and has several nodes; no panel locations are currently known. This system is equipped with Notifier's "Digital Voice Command" (DVC) voice evacuation system, and runs Notifier's FlashScan addressable protocol. The evacuation signal is slow whoop, followed by the default female message.
 
====Notification Appliances====
====Notification Appliances====
All notification appliances are from System Sensor’s “SpectrAlert Advance” line of products. Most areas have System Sensor SPSW speaker/strobes (white, wall-mount, 70v). The candela setting is unknown on these. The restrooms have System Sensor SW remote strobes (white, wall-mount), set to 15 candela.
All notification appliances are from System Sensor’s “SpectrAlert Advance” line of products. Most areas have System Sensor SPSW speaker/strobes (white, wall-mount, 70v). The candela setting is unknown on these. The restrooms have System Sensor SW remote strobes (white, wall-mount), set to 15 candela.
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Notifier FSP-851 addressable photoelectric smoke detectors throughout the terminal.
There are Notifier FSP-851 addressable photoelectric smoke detectors throughout the terminal.
 
==System Specifications (Terminal C) (2000s-present)==
==System Specifications (Terminal C)==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 35: Line 30:
This system was installed in the 2000s, and received a panel upgrade in 2017.
This system was installed in the 2000s, and received a panel upgrade in 2017.
====FACP====
====FACP====
The terminal is protected by a Notifier NFS2-3030 addressable fire alarm system. The panel location is unknown. This panel is equipped with a DVC (Digital Voice Command) voice evac module. The system runs Notifier’s FlashScan addressable protocol, and does the default Notifier slow whoop and female message in alarm.
The terminal is protected by a Notifier NFS2-3030 addressable fire alarm system. The system is networked with several nodes; no panel locations are known. This panel is equipped with Notifier's "Digital Voice Command" (DVC) voice evacuation system. The system runs Notifier’s FlashScan addressable protocol, and the evacuation signal is slow whoop followed by Notifier's default female message.
 
====Notification Appliances====
====Notification Appliances====
Most notification appliances are Wheelock E70-24MCW-FW speaker/strobes (white, wall-mount, 70v). There are also some Wheelock RSS-24MCW-FW remote strobes (white, wall-mount). In the main hallways of the terminal, these are arranged in a pattern of: Speaker/strobe, strobe, speaker/strobe, strobe.
Most notification appliances are Wheelock E70-24MCW-FW speaker/strobes (white, wall-mount, 70v). There are also some Wheelock RSS-24MCW-FW remote strobes (white, wall-mount). In the main hallways of the terminal, these are arranged in a pattern of: Speaker/strobe, strobe, speaker/strobe, strobe.
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Notifier BNG-1TS conventional single-action pull stations. These likely have Notifier FMM-101 addressable modules behind them.
All pull stations are Notifier BNG-1TS conventional single-action pull stations. These likely have Notifier FMM-101 addressable monitor modules attached to them.
 
====Automatic Detection Devices====
====Automatic Detection Devices====
None noticed.
None noticed.
 
==System Specifications (Terminal D) (1990-present, will be decommissioned soon) ==
==System Specifications (Terminal D)==
 
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 57: Line 47:
| FACP: Honeywell DeltaNet FS-90? <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: N/A <br />Year Opened: 1990
| FACP: Honeywell DeltaNet FS-90? <br />System Type: Conventional <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: N/A <br />Year Opened: 1990
|}
|}
This system is original from 1990, and only the notification appliances have been confirmed. This terminal will be redeveloped soon, so this system’s days are numbered.
This system is original from 1990, and only the notification appliances have been confirmed. This terminal will be redeveloped soon, so this system’s days are numbered.
 
====FACP====
====FACP====
 
The fire alarm panel for this terminal is unknown, but could be a Honeywell DeltaNet FS-90. No additional info is known about the panel.
The fire alarm panel for this terminal is unknown, but could be a Honeywell DeltaNet FS-90. No additional info is known about the panel.
 
====Notification Appliances====
====Notification Appliances====
All notification appliances are System Sensor MASS-24LO sounder/strobes (red, ceiling-mount). The tones are unknown.
All notification appliances are System Sensor MASS24LO sounder/strobes (red, ceiling-mount). The tones are unknown.
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
The pull stations are unknown, but are likely either Honeywell S464A single-action pull stations, or Fire-Lite BG-10 dual-action pull stations.
The pull stations are unknown, but are likely either Honeywell S464A single-action pull stations, or Fire-Lite BG-10 dual-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
No information is known.
No information is known.
 
==System Specifications (Terminal E) (2002-present)==
==System Specifications (Terminal E)==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 80: Line 64:
|  
|  
|-
|-
| FACP: Johnson Control IFC-3030 <br />System Type: Addressable (Networked) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (audible) <br> 24VDC (visuals) <br />Date of last known Upgrade: N/A <br />Year Opened: 2002
| FACP: Johnson Controls IFC-3030 <br />System Type: Addressable (Networked) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (audible) <br> 24VDC (visuals) <br />Date of last known Upgrade: N/A <br />Year Opened: 2002
|}
|}
This system is original from 2002.
This system is original from 2002.
====FACP====
====FACP====
The terminal is protected by a Johnson Controls IFC-3030 addressable fire alarm system. The panel location is unknown. This panel is equipped with a Notifier AMG-2 tone/message generator. The system does a code 3 whoop, followed by a female message in alarm. The system runs Notifier’s FlashScan protocol.
The terminal is protected by a Johnson Controls IFC-3030 addressable fire alarm system. The panel location is unknown. This panel is equipped with a Notifier AMG-2 tone/message generator. The system does a code 3 whoop, followed by a female message in alarm. The system runs Notifier’s FlashScan protocol.
 
====Notification Appliances====
====Notification Appliances====
Most notification appliances are Wheelock E70-24MCW-FR speaker/strobes (red, wall-mount, 70v). The washrooms have Wheelock RSS-24MCW-FR remote strobes (red, wall-mount).
Most notification appliances are Wheelock E70-24MCW-FR speaker/strobes (red, wall-mount, 70v). The washrooms have Wheelock RSS-24MCW-FR remote strobes (red, wall-mount).
 
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Johnson Controls JBG-12LX addressable dual-action pull stations.
All pull stations are Johnson Controls JBG-12LX addressable dual-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
None noticed.
None noticed.
[[Category:Texas]]
[[Category:Airports]]

Latest revision as of 15:34, 25 May 2024

George Bush Intercontinental Airport is an international airport located in Houston, Texas, USA. This airport serves the Houston area, and is the second largest airport in the state of Texas. The airport has 5 terminals, each with their own system. The systems likely operate independently from each other. Only the systems in terminals B, C, and E are known. Terminal D will be included in this page, but is speculation. Terminals A and B are the oldest, and opened in 1969. Terminal C opened in 1981, followed by Terminal D in 1990. Terminal E is the newest, and opened officially in 2004. Only Terminal E has its original system.

System Specifications (Terminal B) (2014-present)[edit | edit source]

System Specifications
FACP: Notifier NFS2-3030
System Type: Addressable (Networked)
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (audible)
24VDC (visuals)
Date of last known Upgrade: 2014
Year Opened: 1969

This system was installed in 2014, following a large renovation.

FACP[edit | edit source]

The terminal is protected by a Notifier NFS2-3030 addressable fire alarm system. The system is networked and has several nodes; no panel locations are currently known. This system is equipped with Notifier's "Digital Voice Command" (DVC) voice evacuation system, and runs Notifier's FlashScan addressable protocol. The evacuation signal is slow whoop, followed by the default female message.

Notification Appliances[edit | edit source]

All notification appliances are from System Sensor’s “SpectrAlert Advance” line of products. Most areas have System Sensor SPSW speaker/strobes (white, wall-mount, 70v). The candela setting is unknown on these. The restrooms have System Sensor SW remote strobes (white, wall-mount), set to 15 candela.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier NBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Notifier FSP-851 addressable photoelectric smoke detectors throughout the terminal.

System Specifications (Terminal C) (2000s-present)[edit | edit source]

System Specifications
FACP: Notifier NFS2-3030
System Type: Addressable (Networked)
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (audible)
24VDC (visuals)
Date of last known Upgrade: 2017
Year Opened: 1981

This system was installed in the 2000s, and received a panel upgrade in 2017.

FACP[edit | edit source]

The terminal is protected by a Notifier NFS2-3030 addressable fire alarm system. The system is networked with several nodes; no panel locations are known. This panel is equipped with Notifier's "Digital Voice Command" (DVC) voice evacuation system. The system runs Notifier’s FlashScan addressable protocol, and the evacuation signal is slow whoop followed by Notifier's default female message.

Notification Appliances[edit | edit source]

Most notification appliances are Wheelock E70-24MCW-FW speaker/strobes (white, wall-mount, 70v). There are also some Wheelock RSS-24MCW-FW remote strobes (white, wall-mount). In the main hallways of the terminal, these are arranged in a pattern of: Speaker/strobe, strobe, speaker/strobe, strobe.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier BNG-1TS conventional single-action pull stations. These likely have Notifier FMM-101 addressable monitor modules attached to them.

Automatic Detection Devices[edit | edit source]

None noticed.

System Specifications (Terminal D) (1990-present, will be decommissioned soon)[edit | edit source]

System Specifications
FACP: Honeywell DeltaNet FS-90?
System Type: Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VDC
Date of last known Upgrade: N/A
Year Opened: 1990

This system is original from 1990, and only the notification appliances have been confirmed. This terminal will be redeveloped soon, so this system’s days are numbered.

FACP[edit | edit source]

The fire alarm panel for this terminal is unknown, but could be a Honeywell DeltaNet FS-90. No additional info is known about the panel.

Notification Appliances[edit | edit source]

All notification appliances are System Sensor MASS24LO sounder/strobes (red, ceiling-mount). The tones are unknown.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

The pull stations are unknown, but are likely either Honeywell S464A single-action pull stations, or Fire-Lite BG-10 dual-action pull stations.

Automatic Detection Devices[edit | edit source]

No information is known.

System Specifications (Terminal E) (2002-present)[edit | edit source]

System Specifications
FACP: Johnson Controls IFC-3030
System Type: Addressable (Networked)
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (audible)
24VDC (visuals)
Date of last known Upgrade: N/A
Year Opened: 2002

This system is original from 2002.

FACP[edit | edit source]

The terminal is protected by a Johnson Controls IFC-3030 addressable fire alarm system. The panel location is unknown. This panel is equipped with a Notifier AMG-2 tone/message generator. The system does a code 3 whoop, followed by a female message in alarm. The system runs Notifier’s FlashScan protocol.

Notification Appliances[edit | edit source]

Most notification appliances are Wheelock E70-24MCW-FR speaker/strobes (red, wall-mount, 70v). The washrooms have Wheelock RSS-24MCW-FR remote strobes (red, wall-mount).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Johnson Controls JBG-12LX addressable dual-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed.