Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Dr. Martha Cohen School: Difference between revisions

From FireAlarmPedia
(YAY BAD SYSTEM)
 
(7 intermediate revisions by 3 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: EST iO500<br />System Type:Addressable<br /> System Line Voltage: 120VAC<br />NAC Voltage:24VFWR<br />Date of last known Upgrade: 2019<br />Year Opened: 2017
| FACP: EST iO500<br />FACP Location: Second Floor Data Room #200 <br>System Type: Single-Stage Addressable<br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR<br />System Coding: Temporal <br>Strobes Synchronized: Partially, EST <br>Date of last known Upgrade: 2019<br />Year Opened: 2017
|}
|}
'''Dr. Martha Cohen School''' is a junior high school in the Calgary Board of Education. It is located in New Brighton, in SE Calgary, and has a capacity of about 900 students. It was built in 2017, and the system is original. It is known for having one of the loudest fire alarm systems in the whole district. <br>
'''Dr. Martha Cohen School''' is a junior high school located at 116 Brightondale Park Southeast, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education, and has a capacity of 900 students. The school opened in 2017, and the fire alarm system is original with the exception of some pull stations.
[[User:Yycsfirealarmnimrod|Yycsfirealarmnimrod]] used to go here, but no longer attends.
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The school is protected by an EST iO500 addressable fire alarm control panel. It is located in room #200 (second floor data room). This panel has had some issues in the past with false alarms, caused by a monitoring system error.
The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the second floor data room (Room #200). The system runs EST's Signature-series addressable protocol, and the system coding is temporal.
=====Annunciator=====
=====Annunciator=====
There is an EST RLCD-C LCD annunciator, as well as an EST RLED-24 LED annunciator, in the main entrance.
There is an EST RLCD-C LCD annunciator paired with an EST RLED-24 annunciator in the main entrance vestibule. Both annunciators are mounted in an Edwards RA-ENC2 2-bay annunciator enclosure.
====Notification Appliances====
====Notification Appliances====
The notification appliances are from EST's "Genesis" line of products. The hallways have EST G1R-HDVM horn/strobes (red, wall mount, no FIRE), set on low volume, code 3. The classrooms have EST G1R-HD remote horns (red, wall mount, no FIRE). The bathrooms have EST G1R-VM remote strobes (red, wall, no FIRE), but the second floor men's restroom has a G1RF-VM (red, wall mount, FIRE lettering) remote strobe.
All corridors plus the gym, wood shop, music room and aux gym have EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).  
 
The classrooms have EST G1R-HD remote horns (red, wall-mount, no lettering).  
 
All student washrooms but one have EST G1R-VM remote strobes (red, wall-mount, no lettering, set to 15cd).
 
The second floor men's washroom has an EST G1RF-VM remote strobe (red, wall-mount, FIRE marking, set to 15cd).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
Most pull stations are EST SIGA-270 Signature-series addressable single-action pull stations. These are located in the hallways and the main office. Due to the potential of false alarms or damage, the pull stations in the gymnasiums, boiler rooms and wood shop have been replaced with Edwards MPSR1-SHTW hazardous-location pull stations, These are wired into EST SIGA-CT1 Signature-series monitor modules, as they are conventional.
Most pull stations are EST SIGA-270 addressable single-action pull stations.  
 
The gyms, boiler rooms and wood shop have Edwards MPSR1-SHTW hazardous-location conventional single-action pull stations, wired to EST SIGA-CT1 addressable monitor modules.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA-PS smoke detectors located throughout the school.
There are EST SIGA-PS addressable photoelectric smoke detectors located throughout the school, as well as an EST SIGA-HFS addressable 135°F fixed-temperature heat detector in the cafeteria kitchen.
 
All detectors are mounted on EST SIGA-SB bases.
 
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
There are EST SIGA-CR addressable relay modules serving various purposes.
 
There are EST SIGA-IM addressable isolator modules on the SLC.
 
==== EOLs ====
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.
[[Category:Calgary]]
[[Category:Schools]]

Latest revision as of 16:52, 25 September 2024

System Specifications
FACP: EST iO500
FACP Location: Second Floor Data Room #200
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Partially, EST
Date of last known Upgrade: 2019
Year Opened: 2017

Dr. Martha Cohen School is a junior high school located at 116 Brightondale Park Southeast, in Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education, and has a capacity of 900 students. The school opened in 2017, and the fire alarm system is original with the exception of some pull stations.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an EST iO500 addressable fire alarm system. The panel is located in the second floor data room (Room #200). The system runs EST's Signature-series addressable protocol, and the system coding is temporal.

Annunciator[edit | edit source]

There is an EST RLCD-C LCD annunciator paired with an EST RLED-24 annunciator in the main entrance vestibule. Both annunciators are mounted in an Edwards RA-ENC2 2-bay annunciator enclosure.

Notification Appliances[edit | edit source]

All corridors plus the gym, wood shop, music room and aux gym have EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).

The classrooms have EST G1R-HD remote horns (red, wall-mount, no lettering).

All student washrooms but one have EST G1R-VM remote strobes (red, wall-mount, no lettering, set to 15cd).

The second floor men's washroom has an EST G1RF-VM remote strobe (red, wall-mount, FIRE marking, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

Most pull stations are EST SIGA-270 addressable single-action pull stations.

The gyms, boiler rooms and wood shop have Edwards MPSR1-SHTW hazardous-location conventional single-action pull stations, wired to EST SIGA-CT1 addressable monitor modules.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS addressable photoelectric smoke detectors located throughout the school, as well as an EST SIGA-HFS addressable 135°F fixed-temperature heat detector in the cafeteria kitchen.

All detectors are mounted on EST SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are EST SIGA-CR addressable relay modules serving various purposes.

There are EST SIGA-IM addressable isolator modules on the SLC.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.