| FACP: Mircom FX-2000 <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />Date of last known Upgrade: 2017 <br />Year Opened: 2003/2004
| FACP: Mircom FX-2000 <br>FACP Location: Sobeys Entrance Vestibule <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br>System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor<br />Date of last known Upgrade: 2023<br />Year Opened: 2003/2004
|}
|}
 
8888 Country Hills Blvd NW aka Royal Oak Center is a shopping centre with many plazas. This one is for the units number 125-198. This plaza consists of a Sobeys, Ohana Care, PetValu, Williams Paints, Subway, Freshii and Royal Oak Clinic. It was built in 2003, and the fire alarm system was fully upgraded in 2017.
8888 Country Hills Blvd NW aka Royal Oak Center is a shopping centre with many plazas. This one is for the units number 125-198 in a plaza. This plaza was built in 2003 or 2004, but has had its current fire alarm system since July 2017. It is unknown why the alarms were replaced. This plaza consists of a Sobeys, Ohana Care, PetValu, Williams Paints, Subway, Freshii and Royal Oak Clinic.
 
== System Specifications (2017-present)==
== System Specifications (2017-present)==
==== FACP ====
==== FACP ====
 
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the Sobeys main entrance vestibule. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.
The fire alarm system is a Mircom FX-2000 installed in 2017. It replaced an EST QuickStart QS1, after a CPU fail. The panel is located inside the entrance of Sobeys, and is commonly blocked by shopping carts, which is considered a code violation.
 
==== Notification Appliances ====
==== Notification Appliances ====
 
All indoor notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd). These are ceiling-mounted in Sobeys, and wall-mounted in the bakery of Sobeys and elsewhere. <br>For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside PetValu.
All of the indoor notification appliances are from System Sensor's "SpectrAlert Advance" lineup. The main notification appliances are System Sensor P2RA (red, wall mount, 2 wire) horn/strobes, which are all set to low volume, code-3, and 30cd. They are in place of the Genesis horn/strobes, even on the ceilings at Sobeys. For outdoor notification, there's a System Sensor SRKA (red, wall mount) weatherproof remote strobe outside of PetValu, which did not replace anything as there was no alarm there before. All of these alarms are operating independently, and were installed in 2017 along with the Mircom system.
 
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
 
All pull stations are Mircom MS-401AD addressable single-action pull stations.
All of the pull stations are Mircom MS-401AP "Advanced Protocol" pull stations. They are also installed where the original pull stations were.
 
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
None noticed, waterflow present.
==== Modules ====
There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system’s tamper and flow switches. <br>There is a System Sensor MDL synchronization module for synchronizing the horns and strobes, added in 2023.


The smoke detectors are Mircom MIX-2251AP addressable photoelectric smoke detectors, installed in 2017 when the Mircom system was.
==== EOLs ====
There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits.


== Former System Specifications (2003-2017) ==
== Former System Specifications (2003-2017) ==
Line 37: Line 31:
|  
|  
|-
|-
| FACP: EST QuickStart QS1 <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />Date of last known Upgrade: 2012 <br />Final year in active service: 2017  
| FACP: EST QuickStart QS1 <br>FACP Location: Sobeys Entrance Vestibule<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br>System Coding: Temporal<br />Date of last known Upgrade: 2012 <br>Year Installed: 2003<br />Year Decommissioned: 2017
|}
|}
==== FACP ====
==== FACP ====
 
The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the Sobeys main entrance vestibule. The system ran EST's Signature addressable protocol, and the system coding was temporal.
The original panel was an EST QuickStart QS1, installed during construction. It was where the Mircom FX-2000 is now. The system was replaced in 2017.
 
==== Notification Appliances ====
==== Notification Appliances ====
 
Most notification appliances in Sobeys were EST "Genesis" GC-HDVM horn/strobes (white, ceiling-mount, no lettering, set to 30cd). <br>The other tenants and some areas in Sobeys had EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).
The original notification appliances seen on the walls of tenants were EST "Genesis" G1R-HDVM (red, wall mount, no FIRE marking) horn/strobes. On the ceilings of Sobeys were EST "Genesis" GC-HDVM (white, ceiling mount, no FIRE marking) horn/strobes. These were all replaced in 2017 with System Sensor "SpectrAlert Advance" horn/strobes. Unlike the Mircom system, there were no outdoor notification appliances.
 
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
 
All pull stations were EST SIGA-270 addressable single-action pull stations.
The original pull stations were EST SIGA-270 addressable pull stations. There was one from 2012 as a replacement by the pharmacy, but all of them were replaced in 2017 due to not being compatible with the FX-2000.
 
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
None noticed, waterflow present.
==== Modules ====
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.


The original smoke detectors were EST SIGA-PS addressable photoelectric smoke detectors.
==== EOLs ====
There were Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.


== List of known activations ==
== List of known activations ==
July 12, 2018 - alarm at around 10:54 AM, activated by a pull station in the Sobeys backroom after being hit by an object. Store was almost evacuated, cause found to be false as confirmed by manager and Calgary Fire Department. Alarm shut off after 20 minutes.


July 12, 2018 - alarm at around 10:54 AM, activated by a pull station in the Sobeys backroom after being hit by an object. Store was almost evacuated, cause found to be false as confirmed by manager and Calgary Fire Department. Alarm shut off after 20 minutes.
[[Category:Calgary]]
[[Category:Facilities]]
[[Category:Retail Stores]]
[[Category:Buildings with code violations]]
[[Category:Strip Malls]]

Latest revision as of 11:56, 19 August 2024

System Specifications
FACP: Mircom FX-2000
FACP Location: Sobeys Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes, System Sensor
Date of last known Upgrade: 2023
Year Opened: 2003/2004

8888 Country Hills Blvd NW aka Royal Oak Center is a shopping centre with many plazas. This one is for the units number 125-198. This plaza consists of a Sobeys, Ohana Care, PetValu, Williams Paints, Subway, Freshii and Royal Oak Clinic. It was built in 2003, and the fire alarm system was fully upgraded in 2017.

System Specifications (2017-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located in the Sobeys main entrance vestibule. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All indoor notification appliances are System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd). These are ceiling-mounted in Sobeys, and wall-mounted in the bakery of Sobeys and elsewhere.
For outdoor notification, there is a System Sensor SRKA weatherproof remote strobe (red, wall-mount) outside PetValu.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed, waterflow present.

Modules[edit | edit source]

There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
There is a System Sensor MDL synchronization module for synchronizing the horns and strobes, added in 2023.

EOLs[edit | edit source]

There are Mircom MP-300 end-of-line resistor plates on all sprinkler and signal circuits.

Former System Specifications (2003-2017)[edit | edit source]

System Specifications
FACP: EST QuickStart QS1
FACP Location: Sobeys Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Date of last known Upgrade: 2012
Year Installed: 2003
Year Decommissioned: 2017

FACP[edit | edit source]

The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the Sobeys main entrance vestibule. The system ran EST's Signature addressable protocol, and the system coding was temporal.

Notification Appliances[edit | edit source]

Most notification appliances in Sobeys were EST "Genesis" GC-HDVM horn/strobes (white, ceiling-mount, no lettering, set to 30cd).
The other tenants and some areas in Sobeys had EST "Genesis" G1R-HDVM horn/strobes (red, wall-mount, no lettering, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

None noticed, waterflow present.

Modules[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There were Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.

List of known activations[edit | edit source]

July 12, 2018 - alarm at around 10:54 AM, activated by a pull station in the Sobeys backroom after being hit by an object. Store was almost evacuated, cause found to be false as confirmed by manager and Calgary Fire Department. Alarm shut off after 20 minutes.