Hilton Niagara Falls/Fallsview Hotel & Suites: Difference between revisions

From FireAlarmPedia
(Eduardos)
 
(Addressable)
 
(7 intermediate revisions by 3 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Addressable (Networked, Two-Stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: Unknown <br> Strobes Synchronized <br />Date of last known Upgrade: 2019 <br />Year Opened: 2001
| FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Two-Stage Networked Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br>24VDC (Visual) <br />System Coding: Unknown <br>Strobes Synchronized <br />Date of last known Upgrade: 2019 <br />Year Opened: 2001
|}
|}


Line 12: Line 12:
==System Specifications (2019-present)==
==System Specifications (2019-present)==
====FACP====
====FACP====
The hotel is protected by an Edwards EST3 addressable fire alarm system.  The system is a network of panels, however the locations of these panels is unknown at this time.  The system runs EST’s Signature-series addressable protocol, and is configured for two-stage operation.  The system is equipped with voice evacuation, however the messages and/or tones are unknown at this time.
The hotel is protected by an Edwards EST3 addressable fire alarm system.  This is a networked system with many nodes; the main node may be located in a CACF room, although this is unconfirmed.  The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation.  The system is equipped with voice evacuation, however the messages and/or tones are unknown at this time.


====Notification Appliances====
====Notification Appliances====
The corridors of the hotel have EST “Genesis” G4-S7VM speaker/strobes (white, wall-mount, 70V).  The pool area has EST WG4RF-SVMC weatherproof speaker/strobes (red, wall-mount, 70V).  All guest rooms have EST GC-S7 remote speakers (white, ceiling-mount, 70V).  Some guest rooms have EST G1RF-VM remote strobes (red, wall-mount).
===== Common Areas =====
 
The corridors of the hotel have Edwards “Genesis” G4-S7VM speaker/strobes (white, wall-mount, 70V).  The pool area has Edwards WG4RF-SVMC weatherproof speaker/strobes (red, wall-mount, 70V).   
===== Guest Rooms =====
All guest rooms have Edwards GC-S7 remote speakers (white, ceiling-mount, 70V).  Some guest rooms have EST G1RF-VM remote strobes (red, wall-mount).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA2-PS addressable photoelectric smoke detectors throughout the hotel, mounted on SIGA-SB bases.
There are EST SIGA2-PS addressable photoelectric smoke detectors throughout the hotel, mounted on SIGA-SB bases. There is also a sprinkler system with waterflow detection.
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.  <br>There are EST SIGA-CR addressable relay modules serving various purposes.  <br>There are EST SIGA-IM addressable isolator modules on all SLCs.
====EOLs====
There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.


{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 30: Line 35:
|  
|  
|-
|-
| FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Addressable (Networked, Two-Stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: 20BPM chime (First Stage) <br> Temporal 520Hz (GA) <br> Strobes Synchronized <br />Year Installed: 2001 <br />Year Decommissioned: 2001
| FACP: Edwards EST3 <br /> FACP Location: Unknown <br />System Type: Addressable (Networked, Two-Stage) <br /> System Line Voltage: 120VAC<br />NAC Voltage: 70.7VRMS (Audible) <br> 24VDC (Visual) <br /> System Coding: 20BPM chime (Alert) <br> Temporal 520Hz (Alarm) <br> Strobes Synchronized <br />Year Installed: 2001 <br />Year Decommissioned: 2019
|}
|}


==System Specifications (2001-2019)==
==System Specifications (2001-2019)==
====FACP====
====FACP====
The hotel was protected by an Edwards EST3 addressable fire alarm system.  Like the current system, this system was networked, and the panel locations were not known.  The system ran EST’s Signature-series addressable protocol, and was configured for two-stage operation.  The system was equipped with voice evacuation.  The tones were as follows: A 20BPM chime tone in first stage, followed by a temporal “air horn” tone in general alarm.
The hotel was protected by an Edwards EST3 addressable fire alarm system.  Like the current system, this system was networked, and the panel locations were not known.  The system ran EST’s Signature addressable protocol, and was configured for two-stage operation.  The system was equipped with voice evacuation.  The tones were as follows: A 20BPM chime tone for the alert signal, followed by a temporal “air horn” tone for the evacuation signal.


====Notification Appliances====
====Notification Appliances====
The corridors had a mix of EST 964-1A-4RW remote speakers (white, ceiling-mount, 70V) and EST “Genesis” GC-S7 remote speakers (white, ceiling-mount, 70V).  Areas with high ceilings had EST 757-1A-S70 remote speakers (red, wall-mount, 70V).  The pool area has one Atlas-Soundolier SVTF-77UC remote speaker (red, wall-mount, 70V).  The guest rooms had EST 964-1A-4RW remote speakers (white, ceiling-mount, 70V).  Some guest rooms had EST G1RF-VM remote strobes (red, wall-mount).
 
===== Common Areas =====
The corridors had a mix of EST 964-1A-4RW remote speakers (white, ceiling-mount, 70V) and EST “Genesis” GC-S7 remote speakers (white, ceiling-mount, 70V).  Areas with high ceilings had EST 757-1A-S70 remote speakers (red, wall-mount, 70V).  The pool area has one Atlas-Soundolier SVTF-77UC remote speaker (red, wall-mount, 70V).   
===== Guest Rooms =====
The guest rooms had EST 964-1A-4RW remote speakers (white, ceiling-mount, 70V).  Some guest rooms had EST G1RF-VM remote strobes (red, wall-mount).


===Initiating Devices===
===Initiating Devices===
Line 45: Line 54:


====Automatic Detection Devices====
====Automatic Detection Devices====
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases.
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases. There was also a sprinkler system with waterflow detection.
 
==== Modules =====
 
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
[[Category:Ontario]]
[[Category:Hotels]]

Latest revision as of 11:51, 30 September 2024

System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Two-Stage Networked Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: Unknown
Strobes Synchronized
Date of last known Upgrade: 2019
Year Opened: 2001

Hilton is a chain of upscale hotels headquartered in McLean, Virginia, USA. They have hotels worldwide, and operate a number of other brands, including Hampton Inn and Homewood Suites. This particular hotel is located at 6361 Fallsview Boulevard, in Niagara Falls, Ontario, Canada. The hotel is also known as the Fallsview Hotel & Suites. The hotel opened in 2001, and the fire alarm system is from 2019.

System Specifications (2019-present)[edit | edit source]

FACP[edit | edit source]

The hotel is protected by an Edwards EST3 addressable fire alarm system. This is a networked system with many nodes; the main node may be located in a CACF room, although this is unconfirmed. The system runs Edwards' Signature addressable protocol, and is configured for two-stage operation. The system is equipped with voice evacuation, however the messages and/or tones are unknown at this time.

Notification Appliances[edit | edit source]

Common Areas[edit | edit source]

The corridors of the hotel have Edwards “Genesis” G4-S7VM speaker/strobes (white, wall-mount, 70V). The pool area has Edwards WG4RF-SVMC weatherproof speaker/strobes (red, wall-mount, 70V).

Guest Rooms[edit | edit source]

All guest rooms have Edwards GC-S7 remote speakers (white, ceiling-mount, 70V). Some guest rooms have EST G1RF-VM remote strobes (red, wall-mount).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are EST SIGA2-PS addressable photoelectric smoke detectors throughout the hotel, mounted on SIGA-SB bases. There is also a sprinkler system with waterflow detection.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are EST SIGA-CR addressable relay modules serving various purposes.
There are EST SIGA-IM addressable isolator modules on all SLCs.

EOLs[edit | edit source]

There are Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.

System Specifications
FACP: Edwards EST3
FACP Location: Unknown
System Type: Addressable (Networked, Two-Stage)
System Line Voltage: 120VAC
NAC Voltage: 70.7VRMS (Audible)
24VDC (Visual)
System Coding: 20BPM chime (Alert)
Temporal 520Hz (Alarm)
Strobes Synchronized
Year Installed: 2001
Year Decommissioned: 2019

System Specifications (2001-2019)[edit | edit source]

FACP[edit | edit source]

The hotel was protected by an Edwards EST3 addressable fire alarm system. Like the current system, this system was networked, and the panel locations were not known. The system ran EST’s Signature addressable protocol, and was configured for two-stage operation. The system was equipped with voice evacuation. The tones were as follows: A 20BPM chime tone for the alert signal, followed by a temporal “air horn” tone for the evacuation signal.

Notification Appliances[edit | edit source]

Common Areas[edit | edit source]

The corridors had a mix of EST 964-1A-4RW remote speakers (white, ceiling-mount, 70V) and EST “Genesis” GC-S7 remote speakers (white, ceiling-mount, 70V). Areas with high ceilings had EST 757-1A-S70 remote speakers (red, wall-mount, 70V). The pool area has one Atlas-Soundolier SVTF-77UC remote speaker (red, wall-mount, 70V).

Guest Rooms[edit | edit source]

The guest rooms had EST 964-1A-4RW remote speakers (white, ceiling-mount, 70V). Some guest rooms had EST G1RF-VM remote strobes (red, wall-mount).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270P addressable two-stage single-action pull stations.

Automatic Detection Devices[edit | edit source]

There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building, mounted on SIGA-SB bases. There was also a sprinkler system with waterflow detection.

Modules =[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.