Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Dr. George Stanley School: Difference between revisions

From FireAlarmPedia
(Page tweaked to fit modern format.)
No edit summary
 
(5 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Simplex 4100ES <br /> FACP Location: Main Entrance <br> System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage:24VDC <br /> System Coding: Temporal <br> Strobes Synchronized: Yes, IDNAC <br> Date of last known Upgrade: N/A <br />Year Opened: 2017
| FACP: Simplex 4100ES <br />FACP Location: Main Entrance <br>System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage:24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, IDNAC <br>Date of last known Upgrade: N/A <br />Year Opened: 2017
|}
|}
'''Dr. George Stanley School''' is a middle school located at 585 Cranston Drive Southeast, in the Cranston neighborhood of Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. It has a capacity of 900 students, and opened in 2017. The fire alarm system is original.
'''Dr. George Stanley School''' is a middle school located at 585 Cranston Drive Southeast, in the Cranston neighborhood of Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. It has a capacity of 900 students, and opened in 2017. The fire alarm system is original.
==System Specifications==
==System Specifications==
====FACP====
====FACP====
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
====Notification Appliances====
====Notification Appliances====
All areas except washrooms have Simplex "TrueAlert ES" 49AV-WRF horn/strobes (red, wall-mount, set to 15cd). The student washrooms have Simplex 49VO-WRF addressable remote strobes (red, wall-mount, set to 15cd).
All areas except washrooms have Simplex "TrueAlert ES" 49AV-WRF addressable horn/strobes (red, wall-mount, set to 15cd). The student washrooms have Simplex 49VO-WRF addressable remote strobes (red, wall-mount, set to 15cd).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
All pull stations are Simplex 4099-9004 addressable single-action pull stations.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors throughout the facility, as well as some Simplex 4098-9734 IDNet addressable fixed/rate-of-rise heat detectors in some areas. All detectors are mounted on Simplex 4098-9792 addressable bases.
There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors throughout the facility, as well as Simplex 4098-9734 IDNet addressable fixed/rate-of-rise heat detectors in some areas.  
 
All detectors are mounted on Simplex 4098-9792 addressable bases.
 
==== Modules ====
There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
==== EOLs ====
There are Simplex 2081-9040C end of line resistor plates on all signal circuits.
[[Category:Calgary]]
[[Category:Schools]]

Latest revision as of 16:24, 25 September 2024

System Specifications
FACP: Simplex 4100ES
FACP Location: Main Entrance
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage:24VDC
System Coding: Temporal
Strobes Synchronized: Yes, IDNAC
Date of last known Upgrade: N/A
Year Opened: 2017

Dr. George Stanley School is a middle school located at 585 Cranston Drive Southeast, in the Cranston neighborhood of Calgary, Alberta, Canada. The school is owned and operated by the Calgary Board of Education. It has a capacity of 900 students, and opened in 2017. The fire alarm system is original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4100ES addressable fire alarm system. The panel is located at the main entrance. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

All areas except washrooms have Simplex "TrueAlert ES" 49AV-WRF addressable horn/strobes (red, wall-mount, set to 15cd). The student washrooms have Simplex 49VO-WRF addressable remote strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9004 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex "TrueAlarm" 4098-9714 addressable photoelectric smoke detectors throughout the facility, as well as Simplex 4098-9734 IDNet addressable fixed/rate-of-rise heat detectors in some areas.

All detectors are mounted on Simplex 4098-9792 addressable bases.

Modules[edit | edit source]

There are Simplex 4090-9001 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all signal circuits.