More actions
(Page rewritten to fit modern format.) |
No edit summary |
||
(6 intermediate revisions by 3 users not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier NFS-320C <br /> FACP Location: Unknown <br> System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />Date of last known Upgrade: N/A <br />Year Opened: 2008 | | FACP: Notifier NFS-320C <br />FACP Location: Unknown <br>System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor<br>Date of last known Upgrade: N/A <br />Year Opened: 2008 | ||
|} | |} | ||
'''Holiday Inn''' is a chain of hotels owned by IHG. The chain is headquartered in Denham, England. This particular hotel is located at 45 Hopewell Way Northeast, in Calgary, Alberta, Canada. The hotel primarily serves the Calgary International Airport. The hotel opened in 2008, and the fire alarm system is original. | |||
'''Holiday Inn''' is a chain of hotels owned by IHG. | ==System Specifications (2008-present)== | ||
==System Specifications== | |||
====FACP==== | ====FACP==== | ||
The building is protected by a Notifier NFS-320C addressable fire alarm system. | The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal. | ||
=====Annunciators===== | =====Annunciators===== | ||
There is a Notifier LCD-80 annunciator behind the front desk. | There is a Notifier LCD-80 annunciator behind the front desk. | ||
====Notification Appliances==== | ====Notification Appliances==== | ||
All common areas have System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd). | All common areas have System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd). The guest rooms have System Sensor PA400SWA silenceable mini-horns (white, wall-mount). | ||
===Initiating Devices=== | ===Initiating Devices=== | ||
====Pull Stations==== | ====Pull Stations==== | ||
All pull stations are Notifier MPS-950B conventional single-action pull stations. | All pull stations are Notifier MPS-950B conventional single-action pull stations. All stations are wired to Notifier FMM-101A addressable monitor modules, located directly behind each station. | ||
====Automatic Detection Devices==== | |||
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the hotel, mounted on Notifier B710LPA bases. | |||
==== | ==== Modules ==== | ||
There are Notifier | There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches. | ||
There are Notifier FRM-1A addressable relay modules serving various purposes. | |||
There are Notifier ISO-XA isolator modules on the SLC. | |||
==== EOLs ==== | |||
There are Notifier EOL-CR end of line resistor plates on all sprinkler and Class-B signal circuits. | |||
[[Category:Calgary]] | |||
[[Category:Hotels]] |
Latest revision as of 11:05, 30 September 2024
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: N/A Year Opened: 2008 |
Holiday Inn is a chain of hotels owned by IHG. The chain is headquartered in Denham, England. This particular hotel is located at 45 Hopewell Way Northeast, in Calgary, Alberta, Canada. The hotel primarily serves the Calgary International Airport. The hotel opened in 2008, and the fire alarm system is original.
System Specifications (2008-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier's FlashScan addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There is a Notifier LCD-80 annunciator behind the front desk.
Notification Appliances[edit | edit source]
All common areas have System Sensor "SpectrAlert Advance" P2RA horn/strobes (red, wall-mount, set to 15cd). The guest rooms have System Sensor PA400SWA silenceable mini-horns (white, wall-mount).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier MPS-950B conventional single-action pull stations. All stations are wired to Notifier FMM-101A addressable monitor modules, located directly behind each station.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors throughout the hotel, mounted on Notifier B710LPA bases.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system's tamper and flow switches.
There are Notifier FRM-1A addressable relay modules serving various purposes.
There are Notifier ISO-XA isolator modules on the SLC.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all sprinkler and Class-B signal circuits.