Riverwest Condominiums: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- !System Specifications |- | |- |FACP: EST EST3 FACP Location: CACF Room System Type: Addressable System Line Voltage: 12...")
 
No edit summary
 
(4 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|
|
|-
|-
|FACP: EST EST3
|FACP: Edwards EST3 <br> FACP Location: CACF Room <br> System Type: Single-Stage Addressable <br> System Line Voltage: 120VAC <br> NAC Voltage: 70.7Vrms/24VDC (strobe) <br> System Coding: Temporal 3 (1200Hz) <br> Strobes Synchronized: Yes <br> Date of last known Upgrade: 2022 <br> Year Opened: 2005 (West) / 2006 (East)
 
|}'''Riverwest Condominums''' is pair of condo towers located at 1078 6 Ave SW, Calgary, Alberta. It was built in 2005 and the system is mostly original.
 
FACP Location: CACF Room  
 
System Type: Addressable  
 
System Line Voltage: 120VAC
 
NAC Voltage: 70.7Vrms/24VDC (strobe)  
 
System Coding: Temporal 3 (1200Hz)
 
Strobes Synchronized: Yes
 
Date of last known Upgrade: 2022
 
Year Opened: 2005 (West) / 2006 (East)
|}'''Buiding Name'''(General Building and System Description Goes Here)
==System Specifications==
==System Specifications==
===FACP===
===FACP===
The building is protected by a network of four CPU's all located in the West tower CACF room, two of which have control cards. (1/2) Nodes 4 and 5 are dedicated amplifier cabinets for both the East and West tower.  
The building is protected by an Edwards EST3 addressable fire alarm system. It is a network of four CPU's all located in the West tower CACF room, two of which have control cards. (1/2) Nodes 4 and 5 are dedicated amplifier cabinets for both the East and West tower. The system runs Edwards' Signature addressable protocol, and is equipped with voice-evacuation. The system coding is temporal.
=====Annunciators=====
=====Annunciators=====
There is an EST 3LCD-ANN in the East Tower "Fire Alarm Room"
There is an EST 3LCD-ANN in the East Tower "Fire Alarm Room"
Line 37: Line 20:
All pull stations are EST SIGA-270. Most are original with a few deficiency replacements noticed.
All pull stations are EST SIGA-270. Most are original with a few deficiency replacements noticed.
====Automatic Detection Devices====
====Automatic Detection Devices====
There are EST SIGA-PS detectors located throughout with a few SIGA2-PS and SIGA-OSD replacements.
There are EST SIGA-PS detectors located throughout with a few SIGA2-PS and SIGA-OSD replacements. These are mounted to SIGA-SB bases.
 
==== Modules ====
There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.
[[Category:Facilities]]
[[Category:Residential]]
[[Category:Calgary]]

Latest revision as of 22:13, 11 October 2024

System Specifications
FACP: Edwards EST3
FACP Location: CACF Room
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 70.7Vrms/24VDC (strobe)
System Coding: Temporal 3 (1200Hz)
Strobes Synchronized: Yes
Date of last known Upgrade: 2022
Year Opened: 2005 (West) / 2006 (East)

Riverwest Condominums is pair of condo towers located at 1078 6 Ave SW, Calgary, Alberta. It was built in 2005 and the system is mostly original.

System Specifications[edit | edit source]

FACP[edit | edit source]

The building is protected by an Edwards EST3 addressable fire alarm system. It is a network of four CPU's all located in the West tower CACF room, two of which have control cards. (1/2) Nodes 4 and 5 are dedicated amplifier cabinets for both the East and West tower. The system runs Edwards' Signature addressable protocol, and is equipped with voice-evacuation. The system coding is temporal.

Annunciators[edit | edit source]

There is an EST 3LCD-ANN in the East Tower "Fire Alarm Room"

Notification Appliances[edit | edit source]

Public Notification Appliances on Consist of mostly Edwards 965-7A-4RW 4-inch speaker strobes. With 757-7A-SS70 "Integrity" Speaker strobes installed in the parkade. EST 757S2-15PS are oddly installed on only the Third Floor. There was a few EST "Genesis" GCAVRF LED Ceiling mount strobes installed as deficiency replacements in 2022.

In the suites there are all Edwards 965-1C-4RW ceiling speakers with Edwards 965-7A-4RW ceiling speaker/strobes in sleeping areas. Edwards 684-1C Silence switches are provided in each unit. One GCAVRF LED Ceiling mount strobe was installed a deficiency replacement in 2022.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are EST SIGA-270. Most are original with a few deficiency replacements noticed.

Automatic Detection Devices[edit | edit source]

There are EST SIGA-PS detectors located throughout with a few SIGA2-PS and SIGA-OSD replacements. These are mounted to SIGA-SB bases.

Modules[edit | edit source]

There are EST SIGA-CT1 addressable monitor modules supervising the sprinkler system's tamper and flow switches.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistor plates on all sprinkler and signal circuits.