Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

St. Timothy High School: Difference between revisions

From FireAlarmPedia
No edit summary
mNo edit summary
 
(29 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Kidde VS4 <br /> FACP Location: Custodian's Office <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: 2020 <br />Year Opened: 2004
| FACP: Kidde VS4 <br /> FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes<br />Date of last known Upgrade: 2020 <br />Year Opened: 2004
|}
|}
 
'''St. Timothy High School''' is a junior and senior high school located at 501 Sunset Drive, Cochrane, AB. It is operated by the Calgary Catholic School District. The school was built in 2004, and the fire alarm system was upgraded in 2020; only the pull stations are original.
'''St. Timothy High School''' is a junior and senior high school located at 501 Sunset Drive in the neighborhood of Sunset Ridge in Cochrane, AB. It was built in 2004, and the fire alarm system is from 2020. Only the pull stations are original. The system is managed and serviced by Altex Security Systems.
 
== System Specifications (2020-present) ==
== System Specifications (2020-present) ==
 
This system took two months to install, starting in May 2020 and ending that summer.
==== FACP ====
==== FACP ====
The building is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the caretaker's office. The system runs Kidde's GSA addressable protocol, and the system coding is temporal.
===== Annunciators =====
There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.
==== Notification Appliances ====
All notification appliances except for one are from Kidde's "Genesis" line of products.


The school is protected by a Kidde VS4 fire alarm system. The panel is located in the caretaker's office, and was installed in spring 2020. The system runs Kidde's GSA addressable protocol, and the system coding is temporal. It took Altex Security two whole months to install this system.  
The main notification appliances are Kidde EGC-HDVM horn/strobes (white, ceiling-mount, no lettering, set to 30 or 75cd). There is one horn/strobe per classroom, and the library contains three horn/strobes.  
 
===== Annunciators =====


There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.
Open ceiling areas (the top floor atrium, gymnasium, band/music room and the shop) have Kidde EG1R-HDVM horn/strobes (red, wall-mount, no lettering, set to either 15, 75, or 110cd). The gym has four; two of the horn/strobes where the bell/strobes were, but the other two are in new locations.  


==== Notification Appliances ====
All washrooms have a Kidde EGC-VM remote strobe (white, ceiling-mount, no lettering, set to 75cd).


The notification appliance circuits were mostly redone when the VS4 was installed. The main notification appliances are EST "Genesis" GC-HDVM (white, ceiling, no FIRE marking) horn/strobes, located in hallways and classrooms. There is one horn/strobe per classroom, and the library contains three horn/strobes. The open ceiling areas, such as the atrium, gymnasium, band/music room and the shop have EST "Genesis" G1R-HDVM (red, wall, no FIRE marking) horn/strobes. The gym has two of the horn/strobes where the old bell/strobes were, but the other two are in new locations, having two per side. In each washroom, there is an EST "Genesis" GC-VM (white, ceiling mount, no FIRE) remote strobe. All horn/strobes are set to high volume, and random candelas (a few are at 110cd).  Plates are covering where the bell/strobes were. One of the three outdoor bells was replaced with an EST "Genesis" WG4RN-HVMC (red, no FIRE) horn/strobe by the tarmac, and it is covered by a wire grill. Metal plates are covering the former outdoor bells' space. There is an EST "Integrity" CS405-8A-T weatherproof strobe by the bike rack that was replaced in February 2020 when the QuickStart was still in use. It is the only notification appliance to remain from the previous system.
For exterior notification, there is an Edwards WG4RN-HVMC weatherproof horn/strobe (red, no lettering, set to 60cd) by the tarmac, behind a wire grill.  


There is also an Edwards "Integrity" CS405-8A-T weatherproof remote strobe (red, 110cd) by the bike rack that was installed in early 2020 when the QuickStart was still in service; the only notification appliance to remain from the previous system.
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
All pull stations are the original EST SIGA-270 addressable pull stations. These were kept from the previous system as they are compatible.
==== Automatic Detection Devices ====
There are Kidde KI-PD optical addressable smoke detectors throughout the building.


All of the pull stations are the original EST SIGA-270 addressable pull stations, which were installed during construction.
Certain rooms have Kidde KIR-HD addressable 135°F fixed-temperature/rate-of-rise heat detectors. All detectors installed on KI-SB bases.  


==== Automatic Detection Devices ====
There are Kidde GSA-SD two-wire photoelectric duct smoke detectors on each air handling unit and behind ceilings. They are connected to Kidde GSA-LED LED indicators.
==== Modules ====
There are Kidde GSA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.


The smoke detectors were replaced with Kidde KIR-PD optical addressable smoke detectors, which were installed when the new system was. The duct detectors in the air handling units are Kidde SD-2W two-wire photoelectric duct smoke detectors.
There are also Kidde GSA-CR addressable control modules for shutting down the HVAC system and releasing the fire doors, wired to EST 1508-AQN5 magnetic door holders.  


There are Kidde GSA-IM isolator modules on the SLC.
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.
== Former System Specifications (2004-2020) ==
== Former System Specifications (2004-2020) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
! System Specifications
! Former System Specifications
|-
|-
|  
|  
|-
|-
| FACP: EST QuickStart QS1 <br /> FACP Location: Custodian's Office <br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: Feb 2020 <br />Year Decomissioned: 2020
| FACP: EST QuickStart QS1 <br /> FACP Location: Custodian's Office <br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br /> System Coding: Temporal <br> Strobes Synchronized: Yes <br />Date of last known Upgrade: Feb 2020
Year Installed: 2004<br />Year Decomissioned: 2020
|}
|}
==== FACP ====
==== FACP ====
The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. The system ran EST's Signature addressable protocol, and the system coding was temporal.


The school was formerly protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. It was installed in 2016 as an emergency replacement for the original QuickStart QS1 after a CPU failure. The system ran EST's Signature-series addressable protocol, and the system coding was temporal. The original QuickStart however was set to continuous. The system was replaced with the Kidde system in 2020.
This panel was installed in 2016 as an emergency replacement for the original variant, which suffered a CPU failure.
 
===== Annunciators =====
===== Annunciators =====
There was a QSA-1-S cabinet in the main entrance vestibule, with an EST QS1-CPU-1 CPU and an SL30 card in it.
==== Notification Appliances ====
Most notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R strobe plates (15cd). These could also be found in the library, the music room, and the changerooms.


There was an  EST QS1-CPU-1 annunciator at the entrance, and an SL30 card in it.
The gym and shop had Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates due to higher ambient noise levels. There were three in the gym, and two in the shop.  


==== Notification Appliances ====
For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the front near the hill, one by the staff parking lot, and one at the tarmac.


The main notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R (15cd) strobe plates. These could also be found in the library, the music room, and even the changerooms. The gym and shop have louder ambient noise levels, and contained Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates. There were three in the gym. For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the hill where stairs to the basement are, in the staff parking lot, and in the tarmac. There is also an EST CS405-8A-T (110cd) weatherproof Integrity strobe installed in February 2020 as a deficiency replacement for the original one, which quit functioning in late 2019. The strobe is above the bike rack. It is still in use on the Kidde system.
There was also an Edwards CS405-8A-T weatherproof remote strobe (red, 110cd) above the bike rack; this was installed in February 2020 as a deficiency replacement for the original EST one, and is still in use on the current system.
=== Initiating Devices ===
==== Pull Stations ====
All pull stations were EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.
==== Automatic Detection Devices ====
There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building.  


=== Initiating Devices ===
Certain rooms such as the electrical room had EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.


==== Pull Stations ====
All detectors were mounted on SIGA-SB bases. Most were original, and some were deficiency replacements over the years.


All of the pull stations were and still are EST SIGA-270 addressable pull stations, original to the school. The gym one is missing its glass rod. These are still in use on the Kidde system.
There were EST SIGA-DH duct detector housings, on the air handling units and above some ceilings, with SIGA-PS addressable photoelectric heads inside them. These were connected to EST SIGA-LED LED indicators.  
==== Modules ====
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.  


==== Automatic Detection Devices ====
There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.


The smoke detectors were EST SIGA-PS addressable photoelectric smoke detectors, installed on EST SIGA-SB bases. Most were original, and some were deficiency replacements over the years.
There were EST SIGA-IM isolator modules on the SLC.
==== EOLs ====
There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.


== List of known activations ==
== List of known activations ==
September 21, 2020 - alarm at around 9:45 AM, activated by duct detector in air handling unit in gymnasium. Scent of smoke reported in gym and nearby areas prior to alarm. School was evacuated, Cochrane Fire Services responded and the cause was found to be a motor overheating, burning red hot and smoking from the electrical panel outputting 4x the rated current, due to FORTIS working on power. Alarm shut off after 30 minutes.
September 21, 2020 - alarm at around 9:45 AM, activated by duct detector in air handling unit in gymnasium. Scent of smoke reported in gym and nearby areas prior to alarm. School was evacuated, Cochrane Fire Services responded and the cause was found to be a motor overheating, burning red hot and smoking from the electrical panel outputting 4x the rated current, due to FORTIS working on power. Alarm shut off after 30 minutes.
== Gallery ==
== Gallery ==
<gallery>
<gallery>
StTimothyBellStrobe.jpeg|An Edwards MB6-24 bell/strobe combo in the basement. (This alarm does not exist anymore)
StTimothyBellStrobe.jpeg|An Edwards MB6-24 bell/strobe combo in the basement. (This alarm does not exist anymore)
StTimothyBellStrobe2.jpeg|This one was located by Room 209. Note the sticker on the bell. (This alarm does not exist anymore)
StTimothyBellStrobe2.jpeg|This one was located by Room 209. Note the sticker on the bell. (This alarm does not exist anymore)
StTimothyBandRoomBellStrobe.jpeg|This bell/strobe was in the band room. Note the Incredibles logo on it, which was vandalized by the band teacher. (This alarm does not exist anymore)
StTimothyBandRoomBellStrobe.jpeg|This bell/strobe was in the band room. Note the Incredibles logo on it, which was vandalized by the band teacher. This was a code violation, as the strobe flashes are not visible. (This alarm does not exist anymore)
StTimothySmoke.jpeg|An original EST SIGA-PS smoke detector in the stairwell. Also pictured is an Enforcer ceiling speaker. (This smoke detector does not exist anymore)
StTimothySmoke.jpeg|An original EST SIGA-PS smoke detector in the stairwell. Also pictured is an Enforcer ceiling speaker. (This smoke detector does not exist anymore)
StTimothyOriginalAnnunciator.jpeg|The QuickStart annunciator in the entrance. Note the new EST logo. (System has been replaced)
StTimothyOriginalAnnunciator.jpeg|The QuickStart annunciator in the entrance. Note the new EST logo. (System has been replaced)
StTimothyPull.jpeg|A pull station by the stairwell in the basement. This pull station is still installed on the Kidde system.
StTimothyPull.jpeg|A pull station by the stairwell in the basement. This pull station is still installed on the Kidde system.
</gallery>
</gallery>
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Facilities]]
[[Category:Cochrane]]
[[Category:Schools - Secondary]]

Latest revision as of 00:49, 17 November 2024

System Specifications
FACP: Kidde VS4
FACP Location: Custodian's Office
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2020
Year Opened: 2004

St. Timothy High School is a junior and senior high school located at 501 Sunset Drive, Cochrane, AB. It is operated by the Calgary Catholic School District. The school was built in 2004, and the fire alarm system was upgraded in 2020; only the pull stations are original.

System Specifications (2020-present)[edit | edit source]

This system took two months to install, starting in May 2020 and ending that summer.

FACP[edit | edit source]

The building is protected by a Kidde VS4 addressable fire alarm system. The panel is located in the caretaker's office. The system runs Kidde's GSA addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Kidde K-RLCD-C LCD annunciator and a K-RLED24 LED annunciator at the entrance, on a rectangular silver metal plate.

Notification Appliances[edit | edit source]

All notification appliances except for one are from Kidde's "Genesis" line of products.

The main notification appliances are Kidde EGC-HDVM horn/strobes (white, ceiling-mount, no lettering, set to 30 or 75cd). There is one horn/strobe per classroom, and the library contains three horn/strobes.

Open ceiling areas (the top floor atrium, gymnasium, band/music room and the shop) have Kidde EG1R-HDVM horn/strobes (red, wall-mount, no lettering, set to either 15, 75, or 110cd). The gym has four; two of the horn/strobes where the bell/strobes were, but the other two are in new locations.

All washrooms have a Kidde EGC-VM remote strobe (white, ceiling-mount, no lettering, set to 75cd).

For exterior notification, there is an Edwards WG4RN-HVMC weatherproof horn/strobe (red, no lettering, set to 60cd) by the tarmac, behind a wire grill.

There is also an Edwards "Integrity" CS405-8A-T weatherproof remote strobe (red, 110cd) by the bike rack that was installed in early 2020 when the QuickStart was still in service; the only notification appliance to remain from the previous system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are the original EST SIGA-270 addressable pull stations. These were kept from the previous system as they are compatible.

Automatic Detection Devices[edit | edit source]

There are Kidde KI-PD optical addressable smoke detectors throughout the building.

Certain rooms have Kidde KIR-HD addressable 135°F fixed-temperature/rate-of-rise heat detectors. All detectors installed on KI-SB bases.

There are Kidde GSA-SD two-wire photoelectric duct smoke detectors on each air handling unit and behind ceilings. They are connected to Kidde GSA-LED LED indicators.

Modules[edit | edit source]

There are Kidde GSA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.

There are also Kidde GSA-CR addressable control modules for shutting down the HVAC system and releasing the fire doors, wired to EST 1508-AQN5 magnetic door holders.

There are Kidde GSA-IM isolator modules on the SLC.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.

Former System Specifications (2004-2020)[edit | edit source]

Former System Specifications
FACP: EST QuickStart QS1
FACP Location: Custodian's Office
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: Feb 2020

Year Installed: 2004
Year Decomissioned: 2020

FACP[edit | edit source]

The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the caretaker's office. The system ran EST's Signature addressable protocol, and the system coding was temporal.

This panel was installed in 2016 as an emergency replacement for the original variant, which suffered a CPU failure.

Annunciators[edit | edit source]

There was a QSA-1-S cabinet in the main entrance vestibule, with an EST QS1-CPU-1 CPU and an SL30 card in it.

Notification Appliances[edit | edit source]

Most notification appliances were Edwards MB6-24 motor bells (6" gong) on EST "Integrity" 403-5A-R strobe plates (15cd). These could also be found in the library, the music room, and the changerooms.

The gym and shop had Edwards MB10-24 (10" gong) motor bells on EST "Integrity" 403-5A-R strobe plates due to higher ambient noise levels. There were three in the gym, and two in the shop.

For outdoor notification, there were three Edwards MB6-24 motor bells (6" gong), located at the front near the hill, one by the staff parking lot, and one at the tarmac.

There was also an Edwards CS405-8A-T weatherproof remote strobe (red, 110cd) above the bike rack; this was installed in February 2020 as a deficiency replacement for the original EST one, and is still in use on the current system.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations were EST SIGA-270 addressable pull stations. These are still in use on the Kidde system.

Automatic Detection Devices[edit | edit source]

There were EST SIGA-PS addressable photoelectric smoke detectors throughout the building.

Certain rooms such as the electrical room had EST SIGA-HRS addressable 135°F fixed-temperature/rate-of-rise heat detectors.

All detectors were mounted on SIGA-SB bases. Most were original, and some were deficiency replacements over the years.

There were EST SIGA-DH duct detector housings, on the air handling units and above some ceilings, with SIGA-PS addressable photoelectric heads inside them. These were connected to EST SIGA-LED LED indicators.

Modules[edit | edit source]

There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system and tamper switches.

There were also EST SIGA-CR control modules for shutting down the HVAC system, and releasing the fire doors, wired to Edwards 1508-AQN5 magnetic door holders.

There were EST SIGA-IM isolator modules on the SLC.

EOLs[edit | edit source]

There are Edwards EOL-P1 end-of-line resistors on all sprinkler and signal circuits.

List of known activations[edit | edit source]

September 21, 2020 - alarm at around 9:45 AM, activated by duct detector in air handling unit in gymnasium. Scent of smoke reported in gym and nearby areas prior to alarm. School was evacuated, Cochrane Fire Services responded and the cause was found to be a motor overheating, burning red hot and smoking from the electrical panel outputting 4x the rated current, due to FORTIS working on power. Alarm shut off after 30 minutes.

Gallery[edit | edit source]