Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Costco Wholesale (Beacon Hill): Difference between revisions

From FireAlarmPedia
mNo edit summary
No edit summary
 
(7 intermediate revisions by 2 users not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Mircom FX-2000
| FACP: Mircom FX-2000 <br>FACP Location: By Returns Desk<br />System Type: Single-Stage Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br>System Coding: Temporal <br>Strobes Synchronized: No<br />Date of last known Upgrade: 2021 <br />Year Opened: 2006
FACP Location: By Returns Desk<br />System Type: Addressable <br /> System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR  
 
System Coding: Temporal
 
Strobes Synchronized: No<br />Date of last known Upgrade: 2021 <br />Year Opened: 2006
|}
|}
'''Costco Wholesale''' is a members only sales club. This location is located at 11588 Sarcee Trail NW in Beacon Hill Shopping Centre in NW Calgary, and was built in 2006. The fire alarm system is original to the store, with replacement parts installed as deficiencies occur.
'''Costco Wholesale''' is a members only sales club. This location is located at 11588 Sarcee Trail NW, in the Beacon Hill Shopping Centre, in Calgary, Alberta, Canada.  The store was built in 2006, and the fire alarm system is original excluding deficiency replacements.
== System Specifications (2006-present) ==
== System Specifications (2006-present) ==
==== FACP ====
==== FACP ====
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located by the returns desk. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.  
The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located by the returns desk. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.  
===== Annunciators =====
===== Annunciators =====
There is a Mircom RAX-LCD annunciator at the entrance.
There is a Mircom RAX-LCD annunciator in the main entrance vestibule.
==== Notification Appliances ====
==== Notification Appliances ====
Most of the notification appliances are the original Mircom "Select-A-Horn/Strobe" FHS-240R (red, 30cd) horn/strobes. By the bakery, there is a Mircom "Select-A-Horn/Strobe" FHS-340R (red) horn/strobe, installed as a replacement for a damaged FHS-240R (strobe popped out) in 2012. At the photography desk, there's a System Sensor "SpectrAlert Advance" PC4RA (red, ceiling-mount, 4-wire) horn/strobe in summer of 2017 as a deficiency replacement. There is a Mircom FHS-240W (white) horn/strobe specifically chosen to blend in with the wall, under a cover.  
Most notification appliances are Mircom "Select-A-Horn/Strobe" FHS-240R horn/strobes (red, wall-mount, set to broadband/30cd).  
 
By the bakery, there is a Mircom "Select-A-Horn/Strobe" FHS-340R (red) horn/strobe, installed as a deficiency replacement for a damaged FHS-240R (strobe ripped out) in 2012.  
 
At the photography desk, there's a System Sensor "SpectrAlert Advance" PC4RA (red, ceiling-mount, 4-wire) horn/strobe installed 2017 as a deficiency replacement.  
 
In the meat cutting area, there is a Mircom FHS-240W (white) horn/strobe specifically chosen to blend in with the wall, under a cover.
 
The freezers and dairy coolers have System Sensor "SpectrAlert" P1224MCKA (red, wall-mount, multi-candela) horn/strobes, which are also original.  


The freezers and dairy rooms have System Sensor "SpectrAlert" P1224MCKA (red, wall-mount, multi-candela) horn/strobes, which are also original. The produce cooler has a System Sensor "SpectrAlert Advance" P4RKA (red, wall-mount) weatherproof horn/strobe, installed as a deficiency replacement in November 2021. For outdoor notification, there are two System Sensor "SpectrAlert" S1224MCKA (red, wall-mount) weatherproof remote strobes, one at the entrance, and one behind the store.  
The produce cooler has a System Sensor "SpectrAlert Advance" P4RKA (red, wall-mount) weatherproof horn/strobe, installed as a deficiency replacement in 2021.  
 
For outdoor notification, there are two System Sensor "SpectrAlert" S1224MCKA (red, wall-mount) weatherproof remote strobes, one at the entrance, and one behind the store.  
=== Initiating Devices ===
=== Initiating Devices ===
==== Pull Stations ====
==== Pull Stations ====
The pull stations are all Mircom MS-401AD addressable pull stations. There is one deficiency replacement MS-401AD by an exit, installed in 2015.
All pull stations are Mircom MS-401AD addressable single-action pull stations.
 
==== Automatic Detection Devices ====
==== Automatic Detection Devices ====
Most of the store is protected by waterflow, however there are Mircom MIX-2251AD addressable photoelectric smoke detectors in the cafeteria, bakery, and meat.
There are Mircom MIX-5251RBA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the bakery and cafeteria, mounted on System Sensor B210LPA bases.
[[]
==== Modules ====
[[]
There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system's tamper and flow switches.
 
There are Mircom MIX-M500RA addressable relay modules serving various purposes.
 
==== EOLs ====
There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.
[[Category:Calgary]]
[[Category:Retail Stores]]

Latest revision as of 12:40, 24 October 2024

System Specifications
FACP: Mircom FX-2000
FACP Location: By Returns Desk
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: No
Date of last known Upgrade: 2021
Year Opened: 2006

Costco Wholesale is a members only sales club. This location is located at 11588 Sarcee Trail NW, in the Beacon Hill Shopping Centre, in Calgary, Alberta, Canada. The store was built in 2006, and the fire alarm system is original excluding deficiency replacements.

System Specifications (2006-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Mircom FX-2000 addressable fire alarm system. The panel is located by the returns desk. The system runs Mircom's CLIP addressable protocol, and the system coding is temporal.

Annunciators[edit | edit source]

There is a Mircom RAX-LCD annunciator in the main entrance vestibule.

Notification Appliances[edit | edit source]

Most notification appliances are Mircom "Select-A-Horn/Strobe" FHS-240R horn/strobes (red, wall-mount, set to broadband/30cd).

By the bakery, there is a Mircom "Select-A-Horn/Strobe" FHS-340R (red) horn/strobe, installed as a deficiency replacement for a damaged FHS-240R (strobe ripped out) in 2012.

At the photography desk, there's a System Sensor "SpectrAlert Advance" PC4RA (red, ceiling-mount, 4-wire) horn/strobe installed 2017 as a deficiency replacement.

In the meat cutting area, there is a Mircom FHS-240W (white) horn/strobe specifically chosen to blend in with the wall, under a cover.

The freezers and dairy coolers have System Sensor "SpectrAlert" P1224MCKA (red, wall-mount, multi-candela) horn/strobes, which are also original.

The produce cooler has a System Sensor "SpectrAlert Advance" P4RKA (red, wall-mount) weatherproof horn/strobe, installed as a deficiency replacement in 2021.

For outdoor notification, there are two System Sensor "SpectrAlert" S1224MCKA (red, wall-mount) weatherproof remote strobes, one at the entrance, and one behind the store.

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Mircom MS-401AD addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Mircom MIX-5251RBA addressable 135°F fixed-temperature/rate-of-rise heat detectors in the bakery and cafeteria, mounted on System Sensor B210LPA bases.

Modules[edit | edit source]

There are Mircom MIX-M500MA addressable monitor modules supervising the sprinkler system's tamper and flow switches.

There are Mircom MIX-M500RA addressable relay modules serving various purposes.

EOLs[edit | edit source]

There are Mircom MP-300 end of line resistor plates on all sprinkler and signal circuits.