More actions
(Great new system! Module changes XD) |
No edit summary |
||
(One intermediate revision by the same user not shown) | |||
Line 5: | Line 5: | ||
| | | | ||
|- | |- | ||
|FACP: Notifier NFS-320C <br />FACP Location: Electrical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, | |FACP: Notifier NFS-320C <br />FACP Location: Electrical Room <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, System Sensor <br />Date of last known Upgrade: 2020 <br />Year Opened: 2004 | ||
|} | |} | ||
'''Crystal View Elementary''' is an elementary school located at 2662 Silverstone Way, Victoria, BC. It is part of the Sooke School District. It was built in 2004, and the fire alarm system was upgraded in 2020. Only the pull stations in the gymnasium are original. | '''Crystal View Elementary''' is an elementary school located at 2662 Silverstone Way, Victoria, BC. It is part of the Sooke School District. It was built in 2004, and the fire alarm system was upgraded in 2020. Only the pull stations in the gymnasium are original. | ||
Line 22: | Line 22: | ||
=====Modules===== | =====Modules===== | ||
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
==== EOLs ==== | |||
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits. | |||
==Former System Specifications (2004-2020)== | ==Former System Specifications (2004-2020)== | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
Line 29: | Line 33: | ||
| | | | ||
|- | |- | ||
|FACP: EST QuickStart QS1 <br />FACP Location: Electrical Room <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2020 | |FACP: EST QuickStart QS1 <br />FACP Location: Electrical Room <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes, EST <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2020 | ||
|} | |} | ||
====FACP==== | ====FACP==== | ||
Line 44: | Line 48: | ||
====Modules==== | ====Modules==== | ||
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches. | ||
==== EOLs ==== | |||
There were Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits. | |||
[[Category:British Columbia]] | |||
[[Category:Schools]] |
Latest revision as of 15:32, 24 September 2024
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized: Yes, System Sensor Date of last known Upgrade: 2020 Year Opened: 2004 |
Crystal View Elementary is an elementary school located at 2662 Silverstone Way, Victoria, BC. It is part of the Sooke School District. It was built in 2004, and the fire alarm system was upgraded in 2020. Only the pull stations in the gymnasium are original.
System Specifications (2020-present)[edit | edit source]
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel is located in the electrical room. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Annunciators[edit | edit source]
There is a Notifier ACM-24AT LED annunciator outside, with a disconnected graphic annunciator under it.
Notification Appliances[edit | edit source]
Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to electromechanical 15cd). The classrooms contain System Sensor “SpectrAlert Advance” SRA remote strobes (red, wall-mount, set to 15cd).
For outdoor notification, there is a System Sensor P2RLA horn/strobe outside a classroom.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations except for the gymnasium are Notifier NBG-12LX addressable dual-action pull stations. The gymnasium has the original EST SIGA-270 addressable single-action pull stations, the original modules were removed and the switches are wired to Notifier FMM-101A addressable modules, located directly behind the station.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-951A addressable photoelectric smoke detectors located throughout, mounted on System Sensor B300A-6 bases. There is also a sprinkler system with waterflow detection.
Modules[edit | edit source]
There are Notifier FMM-1A addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all sprinkler and signal circuits.
Former System Specifications (2004-2020)[edit | edit source]
System Specifications |
---|
FACP: EST QuickStart QS1 FACP Location: Electrical Room System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Temporal Strobes Synchronized: Yes, EST Date of last known Upgrade: N/A Year Decommissioned: 2020 |
FACP[edit | edit source]
The building was protected by an EST QuickStart QS1 addressable fire alarm system. The panel was located in the electrical room. The system ran EST’s Signature addressable protocol, and the system coding was temporal.
Annunciators[edit | edit source]
There was an EST QS1-CPU-1 LCD annunciator and an SL30 LED annunciator mounted in a QSA-1-S cabinet outside. There was also a graphic annunciator; this remains but is disconnected.
Notification appliances[edit | edit source]
All common area notification appliances were Edwards MB10-24 motor bells (10” gong). The classrooms had EST “Genesis” G1R-VM remote strobes (red, wall-mount, no lettering, set to 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were EST SIGA-270 addressable single-action pull stations. The ones in the gymnasium remain, but have their original modules removed and are wired to Notifier modules.
Automatic Detection Devices[edit | edit source]
There were EST SIGA-PS addressable photoelectric smoke detectors located throughout the building, mounted on SIGA-SB bases. There was also a sprinkler system with waterflow detection.
Modules[edit | edit source]
There were EST SIGA-CT1 addressable monitor modules supervising the sprinkler system’s tamper and flow switches.
EOLs[edit | edit source]
There were Edwards EOL-P1 end of line resistor plates on all sprinkler and signal circuits.