Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

Jasper Inn & Suites: Difference between revisions

From FireAlarmPedia
mNo edit summary
(Hotel survived!)
 
(20 intermediate revisions by 2 users not shown)
Line 1: Line 1:
'''Jasper Inn & Suites''' is a 3-star hotel located at 98 Geikie St, Jasper, AB. It features an indoor pool, many suites and spans two floors. It was formerly owned by Best Western, when INNHotels bought them in the last few years. The hotel was built in 1972. Three buildings have systems; the main office building and the hotel wing in it, the Inn Grill/pool building, both built in 1972, and the Maligne Suites, built in the late 1980s-early 1990s. The other areas are protected by Kidde 900-0119 talking ionization smoke & carbon monoxide alarms, as they are outdoor suites. The systems are not original, however the pull stations in one building are original. All buildings had their NACs redone in 2020.
==System Specifications (Reception & Cedar Suites) (2000s-present) ==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
|-
|-
Line 7: Line 5:
|  
|  
|-
|-
| FACP: Grinnell Series M-1000 <br />FACP Location: Stairwell near Reception <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal (self-coded) <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2022 <br />Year Opened: 1972
| FACP: Grinnell Series M-1000 <br />FACP Location: West Building, Cedar Suites Entrance<br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal (self-coded) <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2022 <br />Year Opened: 1972
|}
|}
'''Jasper Inn & Suites''' is a 3-star hotel located at 98 Geikie St, Jasper, AB. It features an indoor pool, many suites and spans two floors. It was formerly owned by Best Western, when INNHotels bought them in the last few years. The hotel was built in 1971.
Three buildings have systems: the main office/Cedar Suites building and the Inn Grill/pool building, both built in 1972 share the same system. The Maligne Suites, built in the late 1980s-early 1990s is protected by its own fire alarm system.
Both fire alarm systems underwent panel upgrades in the 2000s, and NAC upgrades in 2020. The pull stations in Maligne Suites and most of the main building are original.
==System Specifications (Cedar Suites & Main Building) (2000s-present) ==
====FACP====
====FACP====
This building is protected by a Grinnell Series M-1000 conventional fire alarm system. The panel is located by the stairwell adjacent to reception, which is accessible by an exterior doorway. It has about 20 zones in use, and replaced an Edwards 6500 in the 2000s; the cabinet remains. The system coding is most likely continuous, but the notification appliances are self-coded to temporal.
The buildings are protected by a Grinnell Series M-1000 conventional fire alarm system. The panel is located in the Cedar Suites entrance vestibule in the west building, adjacent to reception, which is accessible by an exterior doorway. It has about 20 zones in use, and is in an Edwards Custom 6500 cabinet. The system coding is most likely continuous, but the notification appliances are self-coded to temporal.
 
The Series M-1000 replaced an Edwards Custom 6500 in the 2000s. There were formerly two separate 6500's supervising each building. After the upgrade, they were wired into one panel. The other cabinet is now covered, which was used for the main building.
====Notification Appliances====
====Notification Appliances====
The notification appliances are mostly System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, set to 15cd, electromechanical). They replaced Edwards 439D-6AWC vibrating bells (6" gong) in 2020. Above the panel in the stairwell, there is a System Sensor PA400SWA mini-horn (red, silenceable) with a System Sensor SS-24 strobe beside it (red, wall-mount, 1.5cd), the only notification appliances to remain unchanged after the upgrade.
Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd/electromechanical), except for above the panel and the south hotel hallways of the main building.
 
The south hallways in the main building have System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd), likely new old stock.
 
Above the panel in the stairwell, there is a System Sensor PA400SWA mini-horn (red, silenceable) with a System Sensor SS-24 remote strobe beside it (red, wall-mount, 1.5cd), the only notification appliances to remain untouched after the upgrade; these were installed to indicate that the main building was in alarm when there were two separate panels. These are now wired to the one panel, and will go off during any alarm.
 
The P2RA's and P2RLA's were installed in 2020, replacing Edwards 439D-6AWC vibrating bells (6" gong, 1986) and some Edwards "Durabel" 6100D vibrating bells (6" gong, original).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Edwards 270-SPO conventional pull stations, installed in the mid-1980s (270A font, no FIRE ALARM)
All pull stations are Edwards 270-SPO conventional pull stations. Most are original in the main building, and there are some installed in 1986. The west building's 270-SPO's were all installed around 1986.
====Automatic Detection Devices====
====Automatic Detection Devices====
Most smoke detectors are System Sensor “i3” C2W-BA photoelectric smoke detectors. There is a Mircom “i3” 2W-BA photoelectric smoke detector by the panel, installed as a deficiency replacement for a System Sensor 1412A ionization smoke detector in 2022.
Most smoke detectors are System Sensor “i3” C2W-BA photoelectric smoke detectors, located throughout both buildings.  
==System Specifications (Inn Grill, pools, 200-400 suites) (2000s-present)==
 
{| style="float:right;border:2px solid black"
There is a Mircom “i3” 2W-BA photoelectric smoke detector by the panel, installed as a deficiency replacement for a System Sensor 1412A ionization smoke detector in 2022.
|-
 
! System Specifications
The laundry hallway and ski locker hallway both contain Mircom 5601A fixed-temperature/rate of rise mechanical heat detectors.
|-
|
|-
| FACP: Mircom Series 1000? <br />FACP Location: Unknown <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2020 <br />Year Opened: 1972
|}
====FACP====
The building is protected by a Mircom Series 1000 conventional fire alarm system. The panel location is unknown, but is confirmed from the other two buildings. The system coding is likely continuous, as the notification appliances are self-coded to temporal.
====Notification Appliances====
The notification appliances in the Inn Grill, pool area and first two floors of the suites are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual, set to electromechanical temporal 15cd). The upper floors have System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd), likely new old stock.  


These horn/strobes were installed in 2020, replacing a mix of Edwards 439D-6AWC vibrating bells (6” gong) and Edwards “Durabel” 6100D vibrating bells (6” gong).
The pool hallway contains one Mircom TD-135 fixed-temperature heat detector. These replaced Edwards 281C fixed/rate-of-rise heat detectors after a recall.
===Initiating Devices===
====Pull Stations====
All pull stations are Edwards 270-SPO conventional pull stations. Most are the original first-generation variants, mixed with the variant above, along with a few second-generation variants.
====Automatic Detection Devices====
The smoke detectors are all Mircom “i3” 2W-BA photoelectric conventional smoke detectors. The laundry hallway contains Mircom 5601A fixed-temperature/rate of rise mechanical heat detectors, and the pool hallway contains one Mircom TD-135 fixed-temperature heat detector.
==System Specifications (Maligne Suites) (2000s-present)==
==System Specifications (Maligne Suites) (2000s-present)==
{| style="float:right;border:2px solid black"
{| style="float:right;border:2px solid black"
Line 45: Line 43:
|  
|  
|-
|-
| FACP: Mircom Series 1000 <br />FACP Location: Main Entrance Vestibule <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes <br />Date of last known Upgrade: 2022 <br />Year Opened: Late 80s-early 90s
| FACP: Mircom Series 1000 <br />FACP Location: Main Entrance Vestibule <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Temporal <br>Strobes Synchronized: Yes <br />Date of last known Upgrade: 2022 <br />Year Opened: Late 80s-early 90s
|}
|}
====FACP====
====FACP====
This building is protected by a Mircom Series 1000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous, as the notification appliances are self-coded to temporal. The panel was installed sometime before 2015.
This building is protected by a Mircom Series 1000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous, as the notification appliances are self-coded to temporal.  
 
The Series 1000 replaced a Notifier System 500 in the late 2000s.
====Notification Appliances====
====Notification Appliances====
All notification appliances are System Sensor “L-Series” P2RLA-E horn/strobes (red, wall-mount, English only, set to electromechanical, temporal, 15cd). These were installed in 2020 replacing Notifier KMS-6-24VDC/P motor bells (6” gong).
All notification appliances are System Sensor “L-Series” P2RLA-E horn/strobes (red, wall-mount, English only, set to electromechanical/15cd).
 
These were installed in 2020 replacing Notifier KMS-6-24VDC/P motor bells (6” gong).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Notifier MPS-950B conventional pull stations. These are the original models, with the black labels.
All pull stations are Notifier FM950-B conventional pull stations. These are the original models, with the black labels.
====Automatic Detection Devices====
====Automatic Detection Devices====
The smoke detectors are Mircom “i3” 2W-BA conventional photoelectric smoke detectors.
The smoke detectors are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors.
[[Category:Alberta]]
[[Category:Hotels]]

Latest revision as of 00:29, 28 July 2024

System Specifications
FACP: Grinnell Series M-1000
FACP Location: West Building, Cedar Suites Entrance
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal (self-coded)
Strobes Synchronized: No
Date of last known Upgrade: 2022
Year Opened: 1972

Jasper Inn & Suites is a 3-star hotel located at 98 Geikie St, Jasper, AB. It features an indoor pool, many suites and spans two floors. It was formerly owned by Best Western, when INNHotels bought them in the last few years. The hotel was built in 1971.

Three buildings have systems: the main office/Cedar Suites building and the Inn Grill/pool building, both built in 1972 share the same system. The Maligne Suites, built in the late 1980s-early 1990s is protected by its own fire alarm system.

Both fire alarm systems underwent panel upgrades in the 2000s, and NAC upgrades in 2020. The pull stations in Maligne Suites and most of the main building are original.

System Specifications (Cedar Suites & Main Building) (2000s-present)[edit | edit source]

FACP[edit | edit source]

The buildings are protected by a Grinnell Series M-1000 conventional fire alarm system. The panel is located in the Cedar Suites entrance vestibule in the west building, adjacent to reception, which is accessible by an exterior doorway. It has about 20 zones in use, and is in an Edwards Custom 6500 cabinet. The system coding is most likely continuous, but the notification appliances are self-coded to temporal.

The Series M-1000 replaced an Edwards Custom 6500 in the 2000s. There were formerly two separate 6500's supervising each building. After the upgrade, they were wired into one panel. The other cabinet is now covered, which was used for the main building.

Notification Appliances[edit | edit source]

Most notification appliances are System Sensor “L-Series” P2RLA horn/strobes (red, wall-mount, bilingual lettering, set to 15cd/electromechanical), except for above the panel and the south hotel hallways of the main building.

The south hallways in the main building have System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd), likely new old stock.

Above the panel in the stairwell, there is a System Sensor PA400SWA mini-horn (red, silenceable) with a System Sensor SS-24 remote strobe beside it (red, wall-mount, 1.5cd), the only notification appliances to remain untouched after the upgrade; these were installed to indicate that the main building was in alarm when there were two separate panels. These are now wired to the one panel, and will go off during any alarm.

The P2RA's and P2RLA's were installed in 2020, replacing Edwards 439D-6AWC vibrating bells (6" gong, 1986) and some Edwards "Durabel" 6100D vibrating bells (6" gong, original).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Edwards 270-SPO conventional pull stations. Most are original in the main building, and there are some installed in 1986. The west building's 270-SPO's were all installed around 1986.

Automatic Detection Devices[edit | edit source]

Most smoke detectors are System Sensor “i3” C2W-BA photoelectric smoke detectors, located throughout both buildings.

There is a Mircom “i3” 2W-BA photoelectric smoke detector by the panel, installed as a deficiency replacement for a System Sensor 1412A ionization smoke detector in 2022.

The laundry hallway and ski locker hallway both contain Mircom 5601A fixed-temperature/rate of rise mechanical heat detectors.

The pool hallway contains one Mircom TD-135 fixed-temperature heat detector. These replaced Edwards 281C fixed/rate-of-rise heat detectors after a recall.

System Specifications (Maligne Suites) (2000s-present)[edit | edit source]

System Specifications
FACP: Mircom Series 1000
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Conventional
System Line Voltage: 120VAC
NAC Voltage: 24VFWR
System Coding: Temporal
Strobes Synchronized: Yes
Date of last known Upgrade: 2022
Year Opened: Late 80s-early 90s

FACP[edit | edit source]

This building is protected by a Mircom Series 1000 conventional fire alarm system. The panel is located in the main entrance vestibule. The system coding is continuous, as the notification appliances are self-coded to temporal.

The Series 1000 replaced a Notifier System 500 in the late 2000s.

Notification Appliances[edit | edit source]

All notification appliances are System Sensor “L-Series” P2RLA-E horn/strobes (red, wall-mount, English only, set to electromechanical/15cd).

These were installed in 2020 replacing Notifier KMS-6-24VDC/P motor bells (6” gong).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Notifier FM950-B conventional pull stations. These are the original models, with the black labels.

Automatic Detection Devices[edit | edit source]

The smoke detectors are System Sensor “i3” C2W-BA conventional photoelectric smoke detectors.