More actions
(HI hostels often have interesting systems. We like these systems!!) |
No edit summary |
||
(One intermediate revision by the same user not shown) | |||
Line 1: | Line 1: | ||
'''HI Lake Louise Alpine Centre''' is a hostel located at 203 Village Rd, Lake Louise, AB. It was originally built in 1990 as the Canadian Alpine Centre. A second building was built in 1995. The fire alarm systems in these buildings were upgraded around 2017. | '''HI Lake Louise Alpine Centre''' is a hostel located at 203 Village Rd, Lake Louise, AB. It was originally built in 1990 as the Canadian Alpine Centre. A second building was built in 1995. The fire alarm systems in these buildings were upgraded around 2017. | ||
=Main Building/West Wing (1990) = | =Main Building/West Wing (1990) = | ||
== System Specifications (2017-present) == | == System Specifications (2017-present) == | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 11: | Line 8: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier NFS-320C <br />FACP Location: Unknown <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized Yes, | | FACP: Notifier NFS-320C <br />FACP Location: Unknown <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized Yes, System Sensor <br />Date of last known Upgrade: 2017 <br />Year Opened: 1990 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal. | The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). | All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are Notifier NBG-12LX addressable dual-action pull stations. | All pull stations are Notifier NBG-12LX addressable dual-action pull stations. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building, as well as Notifier FST-851A addressable thermal heat detectors in some areas. All detectors are mounted on System Sensor B210LPA bases. | |||
There are Notifier | ==== EOLs ==== | ||
There are Notifier EOL-CR end of line resistor plates on all signal circuits. | |||
== Former System Specifications (1990-2017) == | == Former System Specifications (1990-2017) == | ||
Line 39: | Line 30: | ||
| | | | ||
|- | |- | ||
| FACP: Edwards 6616 <br />FACP Location: Unknown <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2017 | | FACP: Edwards 6616 <br />FACP Location: Unknown <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2017 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building was protected by an Edwards 6616 conventional fire alarm system. The panel location was unknown, and the model was unconfirmed. The system coding was continuous. | The building was protected by an Edwards 6616 conventional fire alarm system. The panel location was unknown, and the model was unconfirmed. The system coding was continuous. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances were Edwards 439D-6AWC vibrating bells (6” gong). | All notification appliances were Edwards 439D-6AWC vibrating bells (6” gong). | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations were Edwards 270-SPO conventional pull stations. | All pull stations were Edwards 270-SPO conventional pull stations. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There were Edwards 6250C ionization smoke detectors located throughout. There were also Edwards 281C rate-of-rise/fixed heat detectors in some areas. | |||
There were Edwards | ==== EOLs ==== | ||
There were Edwards EOL-P1 end of line resistor plates on all initiating and signal circuits. | |||
= East Wing/Building 2 (1995) = | = East Wing/Building 2 (1995) = | ||
== System Specifications (2017-present) == | |||
== System Specifications (2017-present) == | |||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 68: | Line 53: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier NFS-320C <br />FACP Location: Unknown <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized Yes, | | FACP: Notifier NFS-320C <br />FACP Location: Unknown <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized Yes, System Sensor <br />Date of last known Upgrade: 2017 <br />Year Opened: 1995 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal. | The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). | All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd). | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations are Notifier MPS-950B conventional pull stations, wired to Notifier FMM-101A addressable monitor modules. | |||
All pull stations are Notifier MPS-950B conventional pull stations | |||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There are Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building, mounted on System Sensor B210LPA bases. There is one Notifier FSP-951A addressable photoelectric smoke detector in the kitchen as a deficiency replacement, mounted on a System Sensor B300A-6 base. There are also Notifier FST-851A addressable thermal heat detectors in some areas. | |||
There are Notifier | ==== EOLs ==== | ||
There are Notifier EOL-CR end of line resistor plates on all signal circuits. | |||
== Former System Specifications (2000s-2017) == | == Former System Specifications (2000s-2017) == | ||
{| style="float:right;border:2px solid black" | {| style="float:right;border:2px solid black" | ||
|- | |- | ||
Line 95: | Line 75: | ||
| | | | ||
|- | |- | ||
| FACP: Notifier AFP-200C <br />FACP Location: Unknown <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal? <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2000s <br />Year Decommissioned: 2017 | | FACP: Notifier AFP-200C <br />FACP Location: Unknown <br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal? <br>Strobes Synchronized: No <br />Date of last known Upgrade: 2000s <br />Year Decommissioned: 2017 | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building was protected by a Notifier AFP-200C addressable fire alarm system. The panel location was unknown. The system ran Notifier’s CLIP addressable protocol, and the system coding was temporal. | The building was protected by a Notifier AFP-200C addressable fire alarm system. The panel location was unknown. The system ran Notifier’s CLIP addressable protocol, and the system coding was temporal. | ||
==== Notification Appliances ==== | ==== Notification Appliances ==== | ||
===== Common Areas ===== | ===== Common Areas ===== | ||
All common area notification appliances were EST 792-7A-006 horn/strobes (red, wall-mount, 15/75cd). | All common area notification appliances were EST 792-7A-006 horn/strobes (red, wall-mount, 15/75cd). | ||
===== Guest Rooms ===== | ===== Guest Rooms ===== | ||
All guest rooms had EST 692-7A-103 mini-horn/strobes (white, wall-mount, 15/75cd). | All guest rooms had EST 692-7A-103 mini-horn/strobes (white, wall-mount, 15/75cd). | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations were Notifier MPS-950B conventional pull stations. These were wired to Notifier FMM-101A addressable monitor modules. These are still in use on the current system. | All pull stations were Notifier MPS-950B conventional pull stations. These were wired to Notifier FMM-101A addressable monitor modules. These are still in use on the current system. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There were Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building. There were also Notifier FST-851A addressable thermal heat detectors in some areas. All detectors were mounted on System Sensor B210LPA bases. These are still in use on the current system. | |||
There were Notifier | ==== EOLs ==== | ||
There were Notifier EOL-CR end of line resistor plates on all signal circuits. | |||
== Former System Specifications (1995-2000s) == | == Former System Specifications (1995-2000s) == | ||
{| style="float:right;border:2px solid black" | |||
|- | |- | ||
! System Specifications | ! System Specifications | ||
Line 128: | Line 100: | ||
| | | | ||
|- | |- | ||
| FACP: EST 6616 <br />FACP Location: Unknown <br />System Type: Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2000s | | FACP: EST 6616 <br />FACP Location: Unknown <br />System Type: Single-Stage Conventional <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VFWR <br />System Coding: Continuous <br>Strobes Synchronized: No <br />Date of last known Upgrade: N/A <br />Year Decommissioned: 2000s | ||
|} | |} | ||
==== FACP ==== | ==== FACP ==== | ||
The building was protected by an EST 6616 conventional fire alarm system. The panel location was unknown, and the model was unconfirmed. The system coding was continuous. The system was replaced in the 2000s, likely after a main board failure. | The building was protected by an EST 6616 conventional fire alarm system. The panel location was unknown, and the model was unconfirmed. The system coding was continuous. The system was replaced in the 2000s, likely after a main board failure. | ||
==== Notification Appliances ==== | |||
==== Notification Appliances ==== | |||
===== Common Areas ===== | ===== Common Areas ===== | ||
All common area notification appliances were EST 792-7A-006 horn/strobes (red, wall-mount, 15/75cd). These were kept on the AFP-200C. | |||
All common area notification appliances were EST 792-7A-006 horn/strobes (red, wall-mount, 15/75cd). | |||
===== Guest Rooms ===== | ===== Guest Rooms ===== | ||
All guest rooms had EST 692-7A-103 mini-horn/strobes (white, wall-mount, 15/75cd). These were kept on the AFP-200C. | All guest rooms had EST 692-7A-103 mini-horn/strobes (white, wall-mount, 15/75cd). These were kept on the AFP-200C. | ||
=== Initiating Devices === | === Initiating Devices === | ||
==== Pull Stations ==== | ==== Pull Stations ==== | ||
All pull stations were Edwards 270-SPO conventional pull stations. | All pull stations were Edwards 270-SPO conventional pull stations. | ||
==== Automatic Detection Devices ==== | ==== Automatic Detection Devices ==== | ||
There were Edwards 6250C ionization smoke detectors located throughout. There were also Edwards 281C rate-of-rise/fixed heat detectors in some areas. | |||
There were Edwards | ==== EOLs ==== | ||
There were Edwards EOL-P1 end of line resistor plates on all initiating and signal circuits. | |||
[[Category:Alberta]] | |||
[[Category:Hostels]] |
Latest revision as of 20:54, 29 September 2024
HI Lake Louise Alpine Centre is a hostel located at 203 Village Rd, Lake Louise, AB. It was originally built in 1990 as the Canadian Alpine Centre. A second building was built in 1995. The fire alarm systems in these buildings were upgraded around 2017.
Main Building/West Wing (1990)[edit | edit source]
System Specifications (2017-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized Yes, System Sensor Date of last known Upgrade: 2017 Year Opened: 1990 |
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier NBG-12LX addressable dual-action pull stations.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building, as well as Notifier FST-851A addressable thermal heat detectors in some areas. All detectors are mounted on System Sensor B210LPA bases.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all signal circuits.
Former System Specifications (1990-2017)[edit | edit source]
System Specifications |
---|
FACP: Edwards 6616 FACP Location: Unknown System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Date of last known Upgrade: N/A Year Decommissioned: 2017 |
FACP[edit | edit source]
The building was protected by an Edwards 6616 conventional fire alarm system. The panel location was unknown, and the model was unconfirmed. The system coding was continuous.
Notification Appliances[edit | edit source]
All notification appliances were Edwards 439D-6AWC vibrating bells (6” gong).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Edwards 270-SPO conventional pull stations.
Automatic Detection Devices[edit | edit source]
There were Edwards 6250C ionization smoke detectors located throughout. There were also Edwards 281C rate-of-rise/fixed heat detectors in some areas.
EOLs[edit | edit source]
There were Edwards EOL-P1 end of line resistor plates on all initiating and signal circuits.
East Wing/Building 2 (1995)[edit | edit source]
System Specifications (2017-present)[edit | edit source]
System Specifications |
---|
FACP: Notifier NFS-320C FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal Strobes Synchronized Yes, System Sensor Date of last known Upgrade: 2017 Year Opened: 1995 |
FACP[edit | edit source]
The building is protected by a Notifier NFS-320C addressable fire alarm system. The panel location is unknown. The system runs Notifier’s FlashScan addressable protocol, and the system coding is temporal.
Notification Appliances[edit | edit source]
All notification appliances are System Sensor “SpectrAlert Advance” P2RA horn/strobes (red, wall-mount, set to 15cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations are Notifier MPS-950B conventional pull stations, wired to Notifier FMM-101A addressable monitor modules.
Automatic Detection Devices[edit | edit source]
There are Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building, mounted on System Sensor B210LPA bases. There is one Notifier FSP-951A addressable photoelectric smoke detector in the kitchen as a deficiency replacement, mounted on a System Sensor B300A-6 base. There are also Notifier FST-851A addressable thermal heat detectors in some areas.
EOLs[edit | edit source]
There are Notifier EOL-CR end of line resistor plates on all signal circuits.
Former System Specifications (2000s-2017)[edit | edit source]
System Specifications |
---|
FACP: Notifier AFP-200C FACP Location: Unknown System Type: Single-Stage Addressable System Line Voltage: 120VAC NAC Voltage: 24VDC System Coding: Temporal? Strobes Synchronized: No Date of last known Upgrade: 2000s Year Decommissioned: 2017 |
FACP[edit | edit source]
The building was protected by a Notifier AFP-200C addressable fire alarm system. The panel location was unknown. The system ran Notifier’s CLIP addressable protocol, and the system coding was temporal.
Notification Appliances[edit | edit source]
Common Areas[edit | edit source]
All common area notification appliances were EST 792-7A-006 horn/strobes (red, wall-mount, 15/75cd).
Guest Rooms[edit | edit source]
All guest rooms had EST 692-7A-103 mini-horn/strobes (white, wall-mount, 15/75cd).
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Notifier MPS-950B conventional pull stations. These were wired to Notifier FMM-101A addressable monitor modules. These are still in use on the current system.
Automatic Detection Devices[edit | edit source]
There were Notifier FSP-851A addressable photoelectric smoke detectors located throughout the building. There were also Notifier FST-851A addressable thermal heat detectors in some areas. All detectors were mounted on System Sensor B210LPA bases. These are still in use on the current system.
EOLs[edit | edit source]
There were Notifier EOL-CR end of line resistor plates on all signal circuits.
Former System Specifications (1995-2000s)[edit | edit source]
System Specifications |
---|
FACP: EST 6616 FACP Location: Unknown System Type: Single-Stage Conventional System Line Voltage: 120VAC NAC Voltage: 24VFWR System Coding: Continuous Strobes Synchronized: No Date of last known Upgrade: N/A Year Decommissioned: 2000s |
FACP[edit | edit source]
The building was protected by an EST 6616 conventional fire alarm system. The panel location was unknown, and the model was unconfirmed. The system coding was continuous. The system was replaced in the 2000s, likely after a main board failure.
Notification Appliances[edit | edit source]
Common Areas[edit | edit source]
All common area notification appliances were EST 792-7A-006 horn/strobes (red, wall-mount, 15/75cd). These were kept on the AFP-200C.
Guest Rooms[edit | edit source]
All guest rooms had EST 692-7A-103 mini-horn/strobes (white, wall-mount, 15/75cd). These were kept on the AFP-200C.
Initiating Devices[edit | edit source]
Pull Stations[edit | edit source]
All pull stations were Edwards 270-SPO conventional pull stations.
Automatic Detection Devices[edit | edit source]
There were Edwards 6250C ionization smoke detectors located throughout. There were also Edwards 281C rate-of-rise/fixed heat detectors in some areas.
EOLs[edit | edit source]
There were Edwards EOL-P1 end of line resistor plates on all initiating and signal circuits.