Toggle menu
Toggle personal menu
Not logged in
Your IP address will be publicly visible if you make any edits.

We have switched hosting. Sorry for the recent downtime. :)

High River Public Health Centre: Difference between revisions

From FireAlarmPedia
(Created page with "{| style="float:right;border:2px solid black" |- ! System Specifications |- | |- | FACP: Simplex 4010ES <br />FACP Location: Main Entrance <br />System Type: Addressable <br...")
 
No edit summary
 
(One intermediate revision by the same user not shown)
Line 5: Line 5:
|  
|  
|-
|-
| FACP: Simplex 4010ES <br />FACP Location: Main Entrance <br />System Type: Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: 2013 <br />Year Opened: 1970s
| FACP: Simplex 4010ES <br />FACP Location: Main Entrance Vestibule<br />System Type: Single-Stage Addressable <br />System Line Voltage: 120VAC<br />NAC Voltage: 24VDC <br />System Coding: Temporal <br>Strobes Synchronized: Yes, SmartSync <br />Date of last known Upgrade: 2013 <br />Year Opened: 1970s
|}
|}
 
The '''High River Public Health Centre''' is a medical centre located at 310 Macleod Trail Southwest, in High River, Alberta, Canada. The building is owned and operated by Alberta Health Services. The building was built in the 1970s, and the fire alarm system was upgraded in 2013.
The '''High River Public Health Centre''' is a medical centre located at 310 Macleod Trail Southwest, in High River, Alberta, Canada. The building is owned and operated by Alberta Health Services. The building was built in the 1970s, and the fire alarm system was upgraded in 2013.
 
==System Specifications (2013-present)==
==System Specifications (2013-present)==
====FACP====
====FACP====
The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.
 
====Notification Appliances====
====Notification Appliances====
Most notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).  The washrooms have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).
Most notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).  


The washrooms have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).
===Initiating Devices===
===Initiating Devices===
====Pull Stations====
====Pull Stations====
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
All pull stations are Simplex 4099-9001 addressable single-action pull stations.
====Automatic Detection Devices====
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in most areas, and Simplex 4098-9733 addressable heat detectors in other areas. All detectors are mounted on Simplex 4098-9792 bases.


====Automatic Detection Devices====
==== EOLs ====
There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in most areas, and Simplex 4098-9733 addressable heat detectors in other areas.  All detectors are mounted on Simplex 4098-9792 bases.
There are Simplex 2081-9040C end of line resistor plates on all signal circuits.
[[Category:Alberta]]
[[Category:Healthcare]]

Latest revision as of 10:46, 30 September 2024

System Specifications
FACP: Simplex 4010ES
FACP Location: Main Entrance Vestibule
System Type: Single-Stage Addressable
System Line Voltage: 120VAC
NAC Voltage: 24VDC
System Coding: Temporal
Strobes Synchronized: Yes, SmartSync
Date of last known Upgrade: 2013
Year Opened: 1970s

The High River Public Health Centre is a medical centre located at 310 Macleod Trail Southwest, in High River, Alberta, Canada. The building is owned and operated by Alberta Health Services. The building was built in the 1970s, and the fire alarm system was upgraded in 2013.

System Specifications (2013-present)[edit | edit source]

FACP[edit | edit source]

The building is protected by a Simplex 4010ES addressable fire alarm system. The panel is located in the main entrance vestibule. The system runs Simplex’s IDNet addressable protocol, and the system coding is temporal.

Notification Appliances[edit | edit source]

Most notification appliances are Simplex “TrueAlert” 4906-9127 horn/strobes (red, wall-mount, set to 15cd).

The washrooms have Simplex 4906-9101 remote strobes (red, wall-mount, set to 15cd).

Initiating Devices[edit | edit source]

Pull Stations[edit | edit source]

All pull stations are Simplex 4099-9001 addressable single-action pull stations.

Automatic Detection Devices[edit | edit source]

There are Simplex “TrueAlarm” 4098-9714 addressable photoelectric smoke detectors in most areas, and Simplex 4098-9733 addressable heat detectors in other areas. All detectors are mounted on Simplex 4098-9792 bases.

EOLs[edit | edit source]

There are Simplex 2081-9040C end of line resistor plates on all signal circuits.